ESIE15-13C
Symptom-based Troubleshooting
Service Diagnosis
111
2.8
Equipment Discharges White Mist
Applicable Model
All models of SkyAir series
Supposed
Causes
Humid installation site
Installation site is dirty and with dense oil mists.
Soiled heat exchanger
Clogged air filter
Defective fan motor
Troubleshooting
YES
Caution
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Continue the unit operation.
Dust or oil mists should be removed.
Normal
NO
Remove the source of humid
condition.
It may be necessary to remove the
source of humid condition.
YES
YES
Cleaning of heat exchanger is
necessary.
NO
NO
YES
Did the trouble generate on switching
to heating mode after complete of
defrosting during heating?
Remove the source of oil mist or
dust.
Cleaning of air filter
Check the fan motor.
(Refer to troubleshooting
“
A6
”)
Normal
(Mist is generated due to
defrosting operation)
Possible causes as follows
* Clogged air filter
* Defective fan motor
NO
YES
NO
Is the room
temperature higher than set
value in cooling
operation?
Is the
heat exchanger of indoor
unit soiled?
Is the site dusty or
with dense oil mist?
Is the airflow
rate too small?
Is white mist coming
out from the unit?
Содержание RZQG71L9V1
Страница 2: ......
Страница 6: ...ESIE15 13C iv Table of Contents...
Страница 14: ...Introduction ESIE15 13C xii...
Страница 18: ...Outlook Outdoor Units ESIE15 13C 4 General Information 2 Outlook Outdoor Units...
Страница 22: ...Operating range ESIE15 13C 8 General Information...
Страница 108: ...Emergency Operation ESIE15 13C 94 Field Setting...