Function Details
ESIE15-13C
56
Function and Control
Control logic of the Free Cooling
DT-fc: Indoor T - Outdoor T
DT-rs: Room T - Setpoint T
X: To increase the free cooling start temperature
Y: The minimum required DT-fc to start the free cooling
ON
DT-fc
Y/2
0
DT-rs ≥ 2+X
Thermo off
Y & Thermo on + X
OFF
Free cooling
Содержание RZQG71L9V1
Страница 2: ......
Страница 6: ...ESIE15 13C iv Table of Contents...
Страница 14: ...Introduction ESIE15 13C xii...
Страница 18: ...Outlook Outdoor Units ESIE15 13C 4 General Information 2 Outlook Outdoor Units...
Страница 22: ...Operating range ESIE15 13C 8 General Information...
Страница 108: ...Emergency Operation ESIE15 13C 94 Field Setting...