4
|
Components
Service manual
67
RXTM-R+RXTP-R+ARXTP-R+RXTA-B+FTXTA30B2V1B(W)
(B)+35M5V1B
R32 Optimized Heating 4 Split
ESIE21-12A – 2022.02
a
a
a
Compressor pipe
CAUTION
Overheating the compressor pipes (and the oil inside the compressor pipes) will
damage or destroy the compressor.
8
After soldering is done, stop the nitrogen supply after the component has
cooled‑down.
9
Install the cover of the compressor wire terminals.
a
a
Compressor wire terminals cover
10
Install the compressor insulation, see
62].
11
Perform a pressure test, see
211].
12
Add
refrigerant
to
the
refrigerant
circuit,
see
216].