• Split Sky Air • Outdoor Units
13
• Outdoor Units • R-410A • RXS-G2V1B
4
Capacity tables
4 - 1 Cooling/Heating capacity tables
3
4
FTXS2 RXS20G2V1B
Cooling 50Hz
220-240V
Heating 50Hz
220-240V
3D059714
Indoor
Outdoor temperature (°C DB)
EWB
EDB
20
25
30
32
35
40
°C
°C
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
14.0
20
2.05
1.84
0.36
1.96
1.80
0.40
1.86
1.76
0.43
1.83
1.74
0.44
1.77
1.71
0.46
1.68
1.67
0.50
16.0
22
2.14
1.81
0.36
2.05
1.77
0.40
1.95
1.73
0.43
1.92
1.72
0.45
1.86
1.69
0.47
1.77
1.66
0.50
18.0
25
2.23
1.94
0.36
2.14
1.90
0.40
2.05
1.87
0.43
2.01
1.85
0.45
1.95
1.83
0.47
1.86
1.80
0.50
19.0
27
2.28
2.09
0.37
2.19
2.05
0.40
2.09
0.40
2.09
2.02
0.44
2.06
2.00
1.98
0.47
1.91
1.95
0.50
22.0
30
2.42
2.03
0.37
2.32
2.00
0.40
2.23
1.97
0.44
2.19
1.96
0.45
2.14
1.94
0.47
2.05
1.91
0.51
24.0
0.51
2.51
1.99
0.37
2.42
1.96
0.41
2.32
1.93
0.44
2.29
1.92
0.45
2.23
1.91
0.48
2.14
1.88
0.51
Indoor
Outdoor temperature (°C DB)
EDB
-10
-5
0
6
10
°C
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
15.0
1.82
0.53
2.12
0.56
2.43
0.58
2.79
0.62
3.04
0.64
20.0
1.72
0.55
2.03
0.57
2.33
0.60
2.70
0.63
2.94
0.65
22.0
1.69
0.55
1.99
0.58
2.30
0..60
2.66
0.64
2.91
0.66
24.0
1.65
0.56
1.95
0.58
2.26
0.61
2.63
0.64
2.87
0.66
25.0
1.63
0.56
1.94
0.59
2.24
0.61
2.61
0.64
2.85
0.66
27.0
1.59
0.57
1.90
0.59
2.20
0.62
2.57
0.65
2.81
0.67
S
YMBOLS
N
OTES
AFR : Air flow rate
(m3/mim.)
1
Ratings shown are net capacities which include a deduction for indoor
fan motor heat.
2
shows nominal (rated) capacities and power input.
3
TC, PI and SHC must be calculated by interpolation using the figures
in the above tables. (Figures out of the tables should be used for
calculation.)
4
About SHC which are not mentioned on the table.
please calculate them with around values in direct proportion.
5
Capacities are based on the following conditions.
Corresponding refrigerant piping lenght : 5m
Level difference : 0m
6
Air flow rate (AFR) and Bypass factor (BF) are tabulated above table.
BF
: Bypass factor
EWB : Entering wet bulb temp.
(°C)
EDB
: Entering dry bulb temp.
(°C)
TC
: Total capacity
(kW)
SHC : Sensible heat capacity
(kW)
PI
: Power input
(kW)
AFR
9.4
BF
0.14
AFR
9.9