• Outdoor Units • R-410A • RXS-G2V1B
• Split Sky Air • Outdoor Units
10
3
Electrical data
3
24
3
Representative unit combination
Power supply
Comp.
OFM
IFM
Indoor unit
Outdoor unit
Hz-volts
Voltage range
MCA
MFA
RHz
RLA
W
FLA
W
FLA
FFQ35B8V1B
RXS35G2V2B
50 - 220
50 - 230
50 - 240
Max. 50Hz 264V
Min. 50Hz 198V
9.75
10
79
4.8
23
0.16
55
0.6
4.6
4.4
3D055011B
SYMBOLS
MCA
: Min. Circuit Amps (A)
MFA
: Max. Fuse Amps (A)
RHz
: Rated operating frequency (Hz)
RLA
: Rated Load Amps (A)
OFM
: Outdoor Fan Motor
IFM
: Indoor Fan Motor
FLA
: Full Load Amps (A)
W
: Rated motor output (W)
NOTES
1. RLA is based on the following conditions:
Indoor temp.: 27°CDB/19.0°CWB
Outdoor temp. : 35°CDB
2. Maximum allowable voltage unbalance between phases is 2%
3. Select wire size based on the larger value of MCA.
4. Instead of fuse, use circuit breaker.
5. For more details concerning conditional connections, see
http://extranet.daikineurope.com, select ’’E-Data Books’’. Finally, click on
the document title of your choice.
SYMBOLS
MCA: Min. Circuit Amps. (A)
MFA: Max. Fuse Amps (A) (see note 4). (A)
RHZ: Rated Operating Frequency (Hz)
RLA: Rated Load Amps. (A)
OFM: Outdoor Fan Motor (A)
IFM:
Indoor Fan Motor
FLA:
Full Load Amps. (A)
w:
Fan Motor Rated Outdput (W.)
Units
Power supply
Compressor
OFM
IFM
Indoor units
Outdoor units
Hz
Voltage range
MCA
MFA
RHz
RLA
W
FLA
W
FLA
FBQ35C7VEB
RXS35G2V1B
50 - 230
Max. 50Hz 253V
Min. 50Hz 207V
15
16
70
4.42
19
0.35
140
1.2
FBQ50C7VEB
RXS50G2V1B
18
20
75
7
53
0.18
140
1.2
NOTES
1 RLA is based on the following conditions.
Indoor temp. 27°CDB / 19.0°CWB
Outdoor temp. 35°C
2 Maximum allowable woltage variation between fases is 2%
3 Select wire size based on the value of MCA
4 MFA is used to select the circuit break earth leakage circuit breaker.
5 Voltage range.
Units are suitable for use on electrical systems where voltage
supplied to unit terminals is not below or above listed range limits.
6 MCA represents maximum input current.
MFA represents capacity which may accept MCA
(next lower standard fuse rating minimum 15A)
3TW25081-2F