10 Troubleshooting
Installation manual
47
RWEQ96~432TAYD
∗
+ RWEQ96~432TATJ
∗
VRV W T-Series water-cooled system air conditioner
10 .3
Error codes: Overview
Malfunction code
Contents
Solution
Main
code
Sub code
Master/sub 1/sub 2
E3
01/03/05
▪ High pressure switch is activated.
(S1PH)-A1P (X3A)
▪ High pressure switch connectors are detached.
-A1P (X3A)
▪ Check stop valves situation or abnormalities in
(field) piping or waterflow.
▪
Securely connect each connector. Refer to the wiring
diagram attached to the back of the control box cover.
02/04/06
▪ Stop valves are closed.
▪ Refrigerant overcharge.
▪ Open stop valves.
▪ Check refrigerant amount and recharge.
E4
01/02/03
Low pressure malfunction:
▪ Stop valves are closed.
▪ Refrigerant shortage.
▪ Indoor unit malfunction
▪ Open stop valves.
▪ Check refrigerant amount and recharge.
▪
Check the user interface’s display or transmission
wiring between the outside unit and the indoor unit.
E9
01/05/08
Electronic expansion valve malfunction
(Y1E)-A1P (X21A)
Check connection on printed circuit board or actuator.
03/06/09
Electronic expansion valve malfunction
(Y2E)-A1P (X22A)
Check connection on printed circuit board or actuator.
04/07/10
Electronic expansion valve malfunction
(Y3E)-A1P (X25A)
Check connection on printed circuit board or actuator.
F3
01/03/05
Discharge temperature too high (R12T):
▪ Stop valves are closed.
▪
Refrigerant shortage.
▪
Open stop valves.
▪
Check refrigerant amount and recharge.
20/21/22
Compressor casing temperature too high (R13T):
▪
Stop valves are closed.
▪
Refrigerant shortage.
▪
Open stop valves.
▪
Check refrigerant amount and recharge.
F6
02
▪
Stop valves are closed.
▪
Refrigerant overcharge.
▪
Open stop valves.
▪
Check refrigerant amount and recharge.
H9
01/02/03
Temperature sensor malfunction
(R1T)-A4P (X11A)
Check connection on printed circuit board or actuator.
HJ
01/02/03
Water system malfunction
▪ Check water pump and waterflow.
▪ Check flow switch interlock connection (X2M
terminals 5, 6).
J3
16/22/28
17/23/29
56/57/58
Temperature sensor malfunction
(R12T)-A1P (X19A)
Check connection on printed circuit board or actuator.
47/49/51
48/50/52
Temperature sensor malfunction
(R13T)-A1P (X19A)
Check connection on printed circuit board or actuator.
J5
01/03/05
Temperature sensor malfunction
(R3T)-A1P (X30A)
Check connection on printed circuit board or actuator.
J6
01/02/03
Temperature sensor malfunction
(R7T)-A1P (X30A)
Check connection on printed circuit board or actuator.
J7
01/02/03
Temperature sensor malfunction
(R6T)-A1P (X30A)
Check connection on printed circuit board or actuator.
06/07/08
Temperature sensor malfunction
(R8T)-A1P (X29A)
Check connection on printed circuit board or actuator.
18/19/20
Temperature sensor malfunction
(R11T)-A1P (X18A)
Check connection on printed circuit board or actuator.
J9
01/02/03
Temperature sensor malfunction
(R5T)-A1P (X30A)
Check connection on printed circuit board or actuator.
17/18/19
Temperature sensor malfunction
(R2T)-A4P (X12A)
Check connection on printed circuit board or actuator.
JA
01/02/03
High pressure sensor malfunction
(S1NPH)-A1P (X32A)
Check connection on printed circuit board or actuator.
JC
01/02/03
Low pressure sensor malfunction
(S1NPL)-A1P (X31A)
Check connection on printed circuit board or actuator.
LC
01/06/08
Transmission trouble.
A3P (X6A)-A1P (X28A)
Check connection.
P1
01/02/03
Unbalanced power supply voltage.
Check if power supply is within the range.
U1
01/05/07
No power supplied to outside unit or indoor unit
(Reverse phase/open phase).
Check if the power supply wiring for the outside unit
or indoor unit is correctly connected, and correct if
necessary.