7 Configuration
Installation manual
38
RWEQ96~432TAYD
∗
+ RWEQ96~432TATJ
∗
VRV W T-Series water-cooled system air conditioner
The main unit should be used to input field settings in mode 2 .
[1-0]
Description
No indication
Undefined situation.
0
Outside unit is main unit.
1
Outside unit is sub 1 unit.
2
Outside unit is sub 2 unit.
[1-2]
Shows the status of power consumption limitation operation.
Power consumption limitation reduces the power consumption of the
unit compared to nominal operating conditions.
[1-2]
Description
0
Unit is currently not operating under power
consumption limitations.
1
Unit is currently operating under power
consumption limitation.
Power consumption limitation can be set in mode 2. There are two
methods to activate power consumption limitation of the outside unit
system.
▪ The first method is to enable a forced power consumption
limitation by field setting. The unit will always operate at the
selected power consumption limitation.
▪ The second method is to enable power consumption limitation
based on an external input. For this operation an optional
accessory is required.
[1-5] [1-6]
Shows:
▪ [1-5]: The current T
e
target parameter position.
▪ [1-6]: The current T
c
target parameter position.
[1-13]
Shows the total number of connected outside units (in case of
multiple module system).
It can be convenient to check if the total number of outside units
which are installed matches the total number of outside units which
are recognized by the system. In case there is a mismatch, it is
recommended to check the communication wiring path between
outside and outside units (Q1/Q2 communication line).
[1-17] [1-18] [1-19]
Shows:
▪ [1-17]: The latest malfunction code.
▪ [1-18]: The 2nd last malfunction code.
▪ [1-19]: The 3rd last malfunction code.
When the latest malfunction codes were reset by accident on an
indoor unit user interface, they can be checked again through this
monitoring settings.
For the content or reason behind the malfunction code see
"10.2 Solving problems based on error codes" on page 46, where
most relevant malfunction codes are explained. Detailed information
about malfunction codes can be consulted in the service manual of
this unit.
7 .2 .8
Mode 2: Field settings
[2-0]
Cool/Heat selection setting.
Cool/Heat selection setting is used in case the optional Cool/Heat
selector (KRC19-26A6) is used.
Depending on the outside unit setup (single outside unit setup or
multi outside unit setup), the correct setting should be chosen. More
details on how to use the Cool/Heat selector option can be found in
the manual of the Cool/Heat selector.
[2-0]
Cool/Heat selection setting
0 (default)
Each individual outside unit can select Cool/
Heat operation (by Cool/Heat selector if
installed).
1
Master unit decides Cool/Heat operation when
outside units are connected in multiple system
combination.
2
Sub unit for Cool/Heat operation when outside
units are connected in multiple system
combination.
[2-8]
T
e
target temperature during cooling operation without variable
refrigerant temperature (VRT) control.
[2-8]
T
e
target
1
37.4°F (3°C)
2 (default)
42.8°F (6°C)
3
44.6°F (7°C)
4
46.4°F (8°C)
5
48.2°F (9°C)
6
50°F (10°C)
7
51.8°F (11°C)
[2-9]
T
c
target temperature during heating operation without variable
refrigerant temperature (VRT) control.
[2-9]
T
c
target
1
105.8°F (41°C)
2
107.6°F (42°C)
3
109.4°F (43°C)
4
111.2°F (44°C)
5
113°F (45°C)
6 (default)
114.8°F (46°C)
7
120.2°F (49°C)
[2-12]
Enable the power consumption limitation via external control adaptor
(DTA104A61/62).
If the system needs to be running under power consumption
limitation conditions when an external signal is sent to the unit, this
setting should be changed. This setting will only be effective when
the optional external control adaptor (DTA104A61/62) is installed.
[2-12]
Description
0 (default)
Deactivated.
1
Activated.
[2-20]
Manual additional refrigerant charge.
In order to add the additional refrigerant charge amount in a manual
way, following setting should be applied. Further instructions
regarding the different ways to charge additional refrigerant into your
system can be found in chapter "5.6.2 Charging refrigerant" on
page 26.
[2-20]
Description
0 (default)
Deactivated.