Setting gas/air regulation
The CO
2
setting has been set at the factory and does not require any adjustments, in principle. The
setting can be checked by measuring the CO
2
percentage in the combustion gases. In case of any
disturbance of the setting, the replacement of the gas valve or the conversion to a different type of
gas must be checked, and if necessary set in accordance with the following instructions. Always
check the CO
2
percentage when the lid is open.
Checking the carbon dioxide setting
1
Switch off the heat pump module with the user interface.
2
Switch off the gas boiler with the button.
-
appears on the service display.
3
Remove the front panel from the gas boiler.
4
Remove the cover from the sample point (X) and enter an appropriate chimney analysis probe.
IMPORTANT
Ensure the start-up procedure of the analysis machine has been
completed before inserting the probe in the sample point.
IMPORTANT
Wait for the gas boiler to run stable. Faulty measurements may occur if
the measuring probe is connected before the boiler is running stable.
5
Switch on the gas boiler with the button and create a request for space heating.
6
Select the High setting by twice pressing the
and buttons simultaneously. A capital letter
“H” will appear on the service display. The user display will show a Busy symbol. Do NOT carry
out a test when a small letter “h” is shown. If this is the case, press
and again.
7
Allow the display values to stabilize. Wait at least 3 minutes and compare the CO
2
percentage
to the values in the following table.
CO
2
value at
maximum power
Natural gas G20
(20 nbar)
Natural gas G25
(25 mbar)
Only for Belgium
Propane G31
(30/37/50 mbar)
Maximum value
9.6
8.3
10.8
Minimum value
8.4
7.3
9.8
8
Note the CO
2
percentage at maximum power. This is important in relation to the following
steps.
IMPORTANT
It is NOT possible to adjust the CO
2
percentage when the test program is being
carried out. If the CO
2
percentage deviates from the values in the above table,
contact your local service department.
9
Select the High setting by once pressing the
and buttons simultaneously. “L” appears on
the service display. The user display will show a Busy symbol.
10
Allow the display values to stabilize. Wait at least 3 minutes and compare the CO
2
percentage to
the values in the following table.
CO
2
value at
minimum power
Natural gas G20
(20 mbar)
Natural gas G25
(25 mbar)
Only for Belgium
Propane G31
(30/37/50 mbar)
Maximum value
(a)
Minimum value
8.4
7.4
9.4
(a)
CO
2
value at maximum power registered at setting High.
11
If the CO
2
percentage at maximum and minimum power is within the reach stated in the
above tables, the CO
2
setting of the boiler is correct. If NOT, adjust the CO
2
setting in
accordance with the instruction in the following chapter.
12
Switch off the unit by pressing the button and return the sample point to its position.
Make sure it is gas tight.
13
Return the front panel to its place.
Содержание ROTEX GW-20 H12
Страница 1: ...ROTEX 4P374380 1D 88554801 02 2016 4P374380 1D 88554801 02 2016...
Страница 29: ...30...
Страница 81: ...30...
Страница 133: ...30...
Страница 185: ...30...
Страница 237: ...30...
Страница 290: ...30...
Страница 342: ...30...
Страница 395: ...31...
Страница 421: ...57...
Страница 422: ...58...
Страница 423: ...59...
Страница 424: ...ROTEX 008 1548799_00 88554803 05 2018 4P374380 1D 88554801 02 2016...