41
7.6
Weather dependent regulation
When connecting an outdoor sensor, the leaving water temperature is automatically
regulated dependent on the outdoor temperature, in accordance with the set fuel line.
The maximum leaving water temperature (T max) is set via the display. If so desired,
the fuel line can be changed by using the service code (see par.7.3).
Fuel line graph
X.
T outside in °C
Y.
T leaving water in °C
A.
Factory setting
(Tmax CH = 80°C, Tmin CH = 25°C, Tmin ex = -7°C, Tmax ex = 25°C)
B.
Example
(Tmax CH = 60°C, Tmin CH = 25°C, Tmin ex = -7°C, Tmax ex = 25°C)
Содержание ROTEX GW-20 H12
Страница 1: ...ROTEX 4P374380 1D 88554801 02 2016 4P374380 1D 88554801 02 2016...
Страница 29: ...30...
Страница 81: ...30...
Страница 133: ...30...
Страница 185: ...30...
Страница 237: ...30...
Страница 290: ...30...
Страница 342: ...30...
Страница 395: ...31...
Страница 421: ...57...
Страница 422: ...58...
Страница 423: ...59...
Страница 424: ...ROTEX 008 1548799_00 88554803 05 2018 4P374380 1D 88554801 02 2016...