Mechanical Installation
www.DaikinApplied.com 47
IM 926-3 • ROOFPAK APPLIED SYSTEMS
Ductwork
Installing Ductwork
WARNING
Mold can cause personal injury. Materials such as gypsum
wall board can promote mold growth when damp. Such
materials must be protected from moisture that can enter
units during maintenance or normal operation.
NOTICE
Installer must provide access in the ductwork for plenum-
mounted controls.
Once duct work is installed in units with side discharge,
access to plenum-mounted components is difficult.
On bottom-supply/bottom-return units, if a Daikin roof curb
is not used, the installing contractor should make an airtight
connection by attaching field-fabricated duct collars to the
bottom surface of either the roof curb’s duct flange or the unit’s
duct opening. Do not support the total weight of the ductwork
from the unit or these duct flanges. See
Units with optional back return, side discharge, or end discharge
(on RFS units), all have duct collars provided. To expose the
discharge duct collars on a side discharge unit, remove the
plenum section access door and the door gasketing.
Use flexible connections between the unit and ductwork to
avoid transmission of vibration from the unit to the structure.To
minimize losses and sound transmission, design duct work per
ASHRAE and SMACNA recommendations.
To minimize losses and sound transmission, design duct work
per ASHRAE and SMACNA recommendations.
Ductwork exposed to outdoor conditions must be built in
accordance with ASHRAE and SMACNA recommendations
and local building code.
Table 18: Rated Airflow
Unit AHRI
Rated Airflow
015
3750
017
4375
020
5000
026
6875
030
7500
035
8750
040
10000
050
12500
Figure 64: Installing Ductwork
Содержание RoofPak RCS Series
Страница 71: ...Wiring Diagrams www DaikinApplied com 71 IM 926 3 ROOFPAK APPLIED SYSTEMS Figure 87 VFD Control SAF and RAF...
Страница 72: ...IM 926 3 ROOFPAK APPLIED SYSTEMS 72 www DaikinApplied com Wiring Diagrams Figure 88 VAV Control Inputs...
Страница 76: ...IM 926 3 ROOFPAK APPLIED SYSTEMS 76 www DaikinApplied com Wiring Diagrams Figure 90 Electric Heat Control...
Страница 129: ......