SiUS371901EB
Field Setting from Outdoor Unit
Part 5 Field Settings and Test Operation
236
2.5.3 Details of Setting Mode 2 (m2)
Mode 2 is used to change the field settings of the system. Consulting the current field setting value
and changing the current field setting value is possible.
In general, normal operation can be resumed without special intervention after changing field
settings.
Some field settings are used for special operation (e.g. 1 time operation, recovery/vacuuming
setting, adding refrigerant setting, etc.). In such a case, it is required to abort the special operation
before normal operation can restart. It will be displayed in below explanations.
[2-0]:
Cool/Heat selection setting
Cool/Heat selection setting is used in case the optional Cool/Heat selector
(KRC19-26A) is used. Depending on the outdoor unit setup (single outdoor unit
setup or multi outdoor unit setup), the correct setting should be chosen. More details
on how to use the Cool/Heat selector option can be found in the manual of the
Cool/Heat selector.
Default value: 0.
0: Each individual outdoor unit can select Cool/Heat operation (by Cool/Heat
selector if installed).
1: Master unit decides Cool/Heat operation when outdoor units are connected in
multiple system combination
2: Slave unit for Cool/Heat operation when outdoor units are connected in multiple
system combination
Change [2-0] to 0, 1 or 2 in function of required functionality.
[2-2]:
Low noise/demand address
Address for low noise/demand operation.
1 or more systems (maximum 10 systems wired by “F1F2 OUT/D”) can operate use
the LNO (Low Noise Operation) or/and the DE (Demand Operation) by instruction of
field supplied input to optional PCB DTA104A61/62.
To link the system to the corresponding DTA104A61/62, set the address same as
the DIP switches position on the related optional PCB DTA104A61/62.
Ensure that also field setting 2-12-1 is set to enable input from optional PCB
DTA104A61/62.
[2-5]:
Cross wiring check
Default value: 0. Not active.
Set 1: force all connected indoor units to operate the indoor fan on high speed. This
setting can be made to check which units are missing in the communication if the
number of indoor units do not correspond to the system lay out. Ensure that after
cross wiring check was confirmed, to return setting to default 2-5-0. Once setting
2-5-1 is active, it is not automatically returning to default when exit mode 2.
[2-6]:
Forced thermostat ON command all connected indoor units
Default value: 0. Not active.
Set 1: force all connected indoor units to operate under “Test” (forced thermostat
ON command to outdoor). Ensure that when the forced thermostat ON needs to be
ended, to return setting to default 2-6-0. Once setting 2-6-1 is active, it is not
automatically returning to default when exit mode 2.
Содержание REYQ72-432XAYCU
Страница 1: ...Service Manual Heat Recovery 60 Hz REYQ72 456XATJU A REYQ72 456XAYDU A REYQ72 432XAYCU A SiUS371901EB ...
Страница 92: ...Refrigerant Circuit Piping Diagrams SiUS371901EB 85 Part 2 Refrigerant Circuit BSF6Q54TVJ 3D125655 ...
Страница 93: ...SiUS371901EB Refrigerant Circuit Piping Diagrams Part 2 Refrigerant Circuit 86 BSF8Q54TVJ 3D125656 ...
Страница 455: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 448 REYQ144 168XATJU REYQ144 168XATJA 2D119206B ...
Страница 456: ...Wiring Diagrams SiUS371901EB 449 Part 7 Appendix REYQ72 96 120XAYDU REYQ72 96 120XAYDA 2D119207C ...
Страница 457: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 450 REYQ144 168XAYDU REYQ144 168XAYDA 2D119208C ...
Страница 458: ...Wiring Diagrams SiUS371901EB 451 Part 7 Appendix REYQ72 96 120 144 168XAYCU REYQ72 96 120 144 168XAYCA 2D119209B ...
Страница 459: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 452 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B ...
Страница 460: ...Wiring Diagrams SiUS371901EB 453 Part 7 Appendix BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A ...
Страница 461: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 454 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Страница 463: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 456 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Страница 464: ...Wiring Diagrams SiUS371901EB 457 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C ...
Страница 465: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 458 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C ...
Страница 466: ...Wiring Diagrams SiUS371901EB 459 Part 7 Appendix FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B ...
Страница 468: ...Wiring Diagrams SiUS371901EB 461 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C ...
Страница 469: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 462 FXAQ07 09 12 18 24PVJU 3D075354F ...
Страница 475: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 468 VAM1200GVJU 3D073270D ...
Страница 477: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 470 1 4 2 Multi Branch Selector Unit Standard Series BS4Q54TVJ 3D089123B ...
Страница 478: ...Wiring Diagrams SiUS371901EB 471 Part 7 Appendix BS6 8Q54TVJ 2D089122B ...
Страница 479: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 472 BS10 12Q54TVJ 2D089121B ...
Страница 480: ...Wiring Diagrams SiUS371901EB 473 Part 7 Appendix 1 4 3 Multi Branch Selector Unit Flex Series BSF4Q54TVJ 3D123904A ...
Страница 481: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 474 BSF6 8Q54TVJ 2D123905A ...