Optional Electric Heat
Electric Heater Design
If the 10th digit in the model number is an “E”, the rooftop
unit was furnished with a factory installed electric furnace
(Example, DPS010AHCE). The Rebel rooftop units are
available with 4-stage heat output (see capacities in
.
This packaged electric heat rooftop unit is designed for outdoor
non-residential installations only.
The electric heat design consists of a heating coil, DDC staging
control, and all operational safeties. The safety switches include
high-limit temperature switches and individual coil fusing.
The high limit switch is an automatic reset switch. It opens the
control circuit and shuts the heater down when the temperature
reaches the high limit switch closes again allows the heater
to run when the temperature gets below dead band. There is
a second level of protection with an auxiliary high limit switch.
This switch opens up and shuts the heater down when the
temperature exceeds the set point. This switch requires a
manual reset .
NOTE:
It is not recommended to utilize the auxiliary electric
heat as a reheat source for space control.
Electric Heating Capacity Data
Table 14: Heating Capacity – Electric Heaters
Unit
Stages
Option #1
Option #2
Option #3
Option #4
Option #5
Option #6
Option #7
Option #8
Option #9
KW MBH Delta
T
1
Min
cfm KW MBH
Delta
T
1
Min
cfm KW MBH
Delta
T
1
Min
cfm KW MBH
Delta
T
1
Min
cfm KW MBH
Delta
T
1
Min
cfm KW MBH
Delta
T
1
Min
cfm KW MBH
Delta
T
1
Min
cfm KW MBH
Delta
T
1
Min
cfm KW MBH
Delta
T
1
Min
cfm
003,
004
2,
SCR
6
20.5
12 .6
316 12
40.9
25 .1
632
18
61 .4
37 .7
948 30 102.4
62 .9
316
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
004
9 .4
18.8
28.3
47 .2
006
7 .6
15 .1
22 .6
37.8
007
2,
SCR
18
61 .4
16 .2
948
36
122.8
32 .3
1896
54
184.3
48.5
2844
72 2 245 .7
64 .7
948
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
010,
012
12 .6
25 .2
37 .7
50.3
015
10.3
20.6
30.9
41 .2
016,
018
4,
SCR
10
34 .1
4 .2
4
20 68.2
8.4
4
30 102.4
12 .6
1580
45 153 .5
18.9
2369
60 204.7
25 .2
3159 72 245 .7
30.2
3774
90 307.1
37 .7
4739
120 2 409.5
50.3
6319
150 2 511.8
62 .9
7898
020
3 .3
6 .6
9 .9
14 .9
19 .9
23.8
29.8
39 .7
49 .7
025,
028
3
6
9
13 .5
18
21 .6
27
35 .9
44 .9
1. Temperature is calculated at nominal air flow
2. Not available in 208 & 230 Volt
3. 60 degree max rise
4. 2-stage in DPS 016–028 is only available with 10kW nominal heater
Optional Electric Heat
www.DaikinApplied.com
43
IM 1125-13 • REBEL ROOFTOPS