Table 10: Amp Draw Data
Unit
Size
(Tons)
Compressor RLA
Compressor LRA
Condenser Fan
FLA Each
Compressor 1 - Variable
Compressor 2 - Fixed
Compressor 1
Compressor 2
Qty 208 230 460
Voltage
Voltage
Voltage
Voltage
208
230
460
575
[%]
208
230
460
575
208
230
460
575
208
230
460
575
3
7 .7
7.0
3 .5
—
45%
0.0
0.0
0.0
—
See Note
0.0
0.0
0.0
—
1
0.9 0.8 0.4
4
10.0
9.0
4 .5
—
55%
0.0
0.0
0.0
—
0.0
0.0
0.0
—
1
0.9 0.8 0.4
5
11 .9
10.8
5 .4
—
68%
0.0
0.0
0.0
—
0.0
0.0
0.0
—
1
2.0 1.8 0.9
6
15.0
13 .6
6.8
—
89%
0.0
0.0
0.0
—
0.0
0.0
0.0
—
1
2.0 1.8 0.9
7 .5
11 .9
10.8
5 .4
—
68%
8.6
7.8
3 .9
—
67 .5
73 .7
37 .1
—
2
2.0 1.8 0.9
10
10.0
9.0
4 .5
—
59%
17 .5
15.8
7 .9
—
93 .1
84.2
42 .1
—
2
2.0 1.8 0.9
12
15.0
13 .6
6.8
—
89%
17 .5
15.8
7 .9
—
93 .1
84.2
42 .1
—
2
2.0 1.8 0.9
15
28.3
25 .6
12.8
—
100%
17 .5
15.8
7 .9
—
93 .1
84.2
42 .1
—
2
2.0 1.8 0.9
16
47.0
42 .5
22 .9
20.5
—
0
0
0
0
See Note
1
8.0 8.0 4.0
18
47.0
42 .5
22 .9
20.5
—
0
0
0
0
1
8.0 8.0 4.0
20
47.0
42 .5
22 .9
20.5
—
0
0
0
0
1
8.0 8.0 4.0
25
47.0
42 .5
22 .9
20.5
—
39 .1
35 .4
18.6
15 .4
1
8.0 8.0 4.0
28
47.0
42 .5
22 .9
20.5
—
39 .1
35 .4
18.6
15 .4
1
8.0 8.0 4.0
NOTE:
The inverter compresor is controlled to have a soft start and an LRA <1.0
Horse Power
Supply Fan FLA
Exhaust Fan FLA
Voltage
Voltage
208
230
460
kW
208
230
460
kW
1 .3
3 .1
2.8
1 .4
1.0
3 .1
2.8
1 .4
1.0
2 .3
5
4 .6
2 .3
1 .7
5
4 .6
2 .3
1 .7
4
8.8
7 .4
4.0
3.0
8.8
7 .4
4.0
3.0
8
13 .5
12 .2
6 .1
6.0
—
—
—
—
NOTE:
575V Amp Draws: Compressors and motors will be run off a 575 to 460V transformer. Motors will be nameplated at 460V. 575 voltage is for large cabinet only.
IM-1125-13 • REBEL ROOFTOPS
22
www.DaikinApplied.com
Electrical Installation