Appendix - Keypad Display Menu Structure
www.DaikinApplied.com
151
IM 1125-13 • REBEL ROOFTOPS
Figure 114: Optional Outdoor Air Monitor
–
Set Up Menu
Press and release
↑
/
↓
during normal operation to select
IP/SI Units ↓
Set Up ↓↑
LCD1 U/M=FPM ↓
1
LCD1 U/M=FPM ↓
Set LCD1 Units?
Set Area1?
Set Out1 Units?
2
Set Out1?
Set FS1?
Adjust Filter1?
Set Flow Buff?
Set Altitude
Set Out2 Type?
3
Set Out2?
LCD1 U/M=CPM ↑
AR1=0.00SQF ↑
1
AR1=0.000 SQF ↓↑
*ALT=0FT ↑
1
ALT=0 ↓↑
OUT1 U/M=FPM ↓
1
OUT1 U/M=FPM ↓↑
OUT2 TYPE=TEMP↓
1
OUT2 TYP=TEMP↓↑
2
OUT1=0–10V ↓
3
OUT2=0-10V ↓
OUT1 U/M=CPM ↑
OUT2 TYPE=ALRM ↑
2
OUT1=0–5V ↓↑
BUFF SIZE=30 ↓↑
1
FLOW BUFF=30 ↓↑
FS1=5000FPM ↓↑
FS1=10000FPM for GF1
or
FS1=5000CFM ↓↑
FS1=10000CFM for GF1
1
FS1=5000FPM ↓↑
1
FS1=10000FPM for GF1
or
1
FS1=5000CFM ↓↑
1
FS1=10000CFM for GF1
FILTER1=0 ↑
1
FILTER1=0 ↓↑
3
OUT2=0-5V ↓↑
2
OUT1=4–20mA ↑
1
OUT1=4-20mA ↓↑
3
OUT2=4-20mA ↑
1
OUT2=4-20mA ↓↑
See
System
Units Menu,
Enter (Move →)
Esc (Normal Operation)
Enter (Move →)
Esc (Move ←)
Enter (Move →)
Esc (Move ←)
Enter (Action, Move →→)
Esc (Move ←←)
Visible only when LCD U/M=CFM
FS1 units determined by
OUT1 U/M setting
Displays airflow in FPM.
Outputs airflow in FPM.
Adjust dampening filter value
from 0 (OFF) to 99%.
Set the altitude for flow correction
from 0 to 18,000 ft.
Set the number of flow
calculations to be averaged:
1 to 1,000.
Sets OUT2 to produce
Temperature output.
Sets OUT2 to produce
Alarm output .
In addition, “SW1” must be set
to the VDC position to change
airflow output to 0–10VDC.
In addition, “SW2” must be set
to the VDC position to change
airflow output to 0–10VDC.
In addition, “SW1” must be set
to the VDC position to change
airflow output to 0–5VDC.
In addition, “SW2” must be set
to the VDC position to change
airflow output to 0–5VDC.
In addition, “SW1” must be set to
the mA position to change airflow
output to 4–20mA.
In addition, “SW2” must be set to
the mA position to change airflow
output to 4–20mA.
Set area between
0.00 and 999.99 sq.ft. Area
affects the LCD display reading
and output when set for CFM.
Fullscale analog output value
from 100 to 15,000 for FPM
(up to 999,999 for CFM) in
increments of 1.
Value must be ≥ LL1 + 10 or, if
LL1=0, value must be ≥ 100.
Displays airflow in CFM (User
must input AR1 area .
Outputs airflow in CFM (User
must input AR1 area .
1 .
Factory default/current setting
2 .
If a selection is made that requires SW1 to be set, the LCD displays “Set
SW1 on Board”.
3 .
If a selection is made that requires SW2 to be set, the LCD displays “Set
SW2 on Board”.