M
eChanICal
I
nsTallaTIon
www.DaikinApplied.com 21
IM 893-10 • ROOFPAK SINGLEZONE UNITS
Roof Curb Assembly and Installation
Locate the roof curb and unit on a portion of the roof that can
support the weight of the unit. The unit must be supported to
prevent bending or twisting of the machine.
If building construction allows sound and vibration into the
occupied space, locate the unit over a non-critical area.
It
is the responsibility of the system designer to make
adequate provisions for noise and vibration in the
occupied space .
Install the curb and unit level to allow the condensate drain to
flow properly and allow service access doors to open and close
without binding.
Integral supply and return air duct flanges are provided with
the RPS/RFS roof curb, allowing connection of duct work to the
curb before the unit is set. The gasketed top surface of the duct
flanges seals against the unit when it is set on the curb.
WARNING
Mold can cause personal injury. Some materials such as
gypsum wall board can promote mold growth when damp.
Such materials must be protected from moisture that can
enter units during maintenance or normal operation.
These flanges must not support the total weight of the
ductwork. See
Installing Ductwork on page 39
for details on
duct connections. It is critical that the condensate drain side of
the unit be no higher than the opposite side.
Assembly of a typical RPS/RDT roof curb is shown in
. Parts A through K are common to all units having bottom
supply and return openings. Depending on the unit length,
Parts L and M may be included with the roof curb kit to create
the correct overall curb length.
RCS Assembly instructions
shows the assembly of the RCS roof curb.
1. Set curbing parts (A) in place making sure that the
orientation complies with the assembly instructions.
Check alignment of all mating bolt holes.
2. Bolt curbing parts together using fasteners provided.
3. Curb must be level from side to side and over its length.
4. Weld curbing in place. Caulk all seams watertight and
insulate between channels.
5. Flash curbing into roof as shown in Detail C.
Figure 23: RCS Roof Curb Assembly
See
DETAIL A
(INSIDE)
015D - 025D = 52.00
030D - 068D = 64.00
070D - 105D = 83.00
110D - 140D = 120.00
(INSIDE)