background image

18

English

2. 

Trial operation and testing

• 

To test cooling, set for the lowest temperature. To test heating, set for the highest temperature. (Depending on the room 
temperature, only heating or cooling (but not both) may be possible.)

• 

After the unit is stopped, it will not start again (heating or cooling) for about 3 minutes.

•  During the test run, first check the operation of each unit individually. Then also check the simultaneous operation of all indoor 

units. Check both heating and cooling operation.

• 

After running the unit for about 20 minutes, measure the temperatures at the indoor unit inlet and outlet. If the measurements are 
above the values shown in the table below, then they are normal. 

Temperature difference between 
inlet and outlet

About 14°F (8°C)

Cooling

About 36°F (20°C)

Heating

(When running in one room)

• 

During cooling operation, frost may form on the gas stop valve or other parts. This is normal.

• 

Operate the indoor units in accordance with the included operation manual. Check that they operate normally.

3. 

Test items

Are the indoor units installed securely?

Has an inspection been made to check for gas leakage?

Has complete thermal insulation been done (gas pipes, liquid 
pipes, indoor portions of the drain hose extension)?

Is the drainage secure?

Are the ground wire connections secure?

Are the electric wires connected correctly?

Is the wiring in accordance with the specifications?

Are the inlets/outlets of the indoor and outdoor units free of any obstructions?

Are the stop valves open?

Do the marks match (room A, room B, room C, room D) on the 
wiring and piping for each indoor unit?

Is the priority room setting set for 2 or more rooms?

Test item

Check

Consequences of trouble

Fall, vibration, noise

Incomplete cooling/heating function

Water leakage

Water leakage

Electrical leakage

Incomplete cooling/heating function

No operation or burn damage

Incomplete cooling/heating function

Incomplete cooling/heating function

Incomplete cooling/heating function

The priority room setting will not function.

ATTENTION

• 

Have the customer actually operate the unit while looking at the manual included with the indoor unit. Instruct the customer 

how to operate the unit correctly (particularly cleaning of the air filters, operation procedures, and temperature adjustment).

•  Even when the air conditioner is not operating, it consumes some electric power. If the customer is not going to use the unit 

soon after it is installed, turn off the circuit breaker to avoid wasting electricity.

• 

If additional refrigerant has been charged because of long piping, list the amount added on the nameplate on the reverse 
side of the stop valve cover.

English

01_EN_3P379970-9C.indd   18

10/17/2019   4:42:20 PM

Содержание R-410A

Страница 1: ...ish Fran ais Espa ol MODELS 2MXS18NMVJU 2MXS18NMVJUA DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R410A Split Series Installation manual Manuel dinstallation Manual de instalaci n Manuel dinstallat...

Страница 2: ...oxygen A massive leak can lead to oxygen depletion especially in basements and an asphyxiation hazard could occur leading to serious injury or death Do not ground units to water pipes gas pipes teleph...

Страница 3: ...getting into the system b Tight R410A does not contain any chlorine does not destroy the ozone layer and does not reduce the earth s protection again harmful ultraviolet radiation R410A can contribut...

Страница 4: ...d radio sets This is to prevent interference to images and sounds Noise may be experienced even if they are more than 10ft 3m away depending on radio wave conditions 8 In coastal areas or other places...

Страница 5: ...t for one room only Be sure to connect at least 2 rooms Cut thermal insulation pipe to an appropriate length and wrap it with tape making sure that no gap is left in the insulation pipe s cut line Wra...

Страница 6: ...u The line set piping size is determined by the size of the indoor unit fittings Reducers are used at the outdoor unit to accommodate the correct gas line pipe size 3MXS24 4MXS36 Port 2MXS18 B 07 09 1...

Страница 7: ...oor unit Connection port of outdoor unit Connection port of outdoor unit Be sure to attach the gasket No 5 No 6 Flare nut for 3 8 inch 9 5mm Be sure to attach the gasket No 4 No 2 Flare nut for 1 2 in...

Страница 8: ...ecting a Location for Installation of the Indoor Units The maximum allowable length of refrigerant piping and the maximum allowable height difference between the outdoor and indoor units are listed be...

Страница 9: ...nuts to prevent damage to the flare nuts and gas leakage Align the centers of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them fully with a spanner and a torque wrench Do...

Страница 10: ...hours recommended If there is a pressure drop check for leaks make repairs and perform the pressure test again 2 Connect projection side of charging hose which comes from gauge manifold to gas stop v...

Страница 11: ...hen lling There is a siphon pipe inside so the cylinder need not be upside down to ll with liquid Filling other cylinders Turn the cylinder upside down when lling Be sure to use the R410A tools to ens...

Страница 12: ...m I D 9 16 5 8 inch 14 16mm I D 5 8 13 16 inch 16 20mm I D 5 16 13 32 inch 8 10mm 13 32 inch 10mm Min Minimum bend radius Piping thickness Thermal insulation size Thermal insulation thickness Liquid s...

Страница 13: ...rcuit interrupter itself Use an all pole disconnection type circuit breaker with at least 1 8 inch 3mm between the contact point gaps When carrying out wiring connection take care not to pull at the c...

Страница 14: ...Shape the wires so that there is no lifting of the service hatch or other structural parts Use the speci ed wires and connect them securely Room A Room C Room D Room B power supply CAUTION Precautions...

Страница 15: ...standby mode according to the operation mode of the set indoor unit 2 Priority during powerful operation If the indoor unit which is set for Priority Room Setting is operating at powerful the capabili...

Страница 16: ...t Mode is running cooling capacity will be saved Setting procedure Turn the Night Quiet Mode switch SW6 1 to on Service PC board HEAT COOL 4 3 2 1 2 1 E D C B A Night Quiet Mode setting switch SW6 1 2...

Страница 17: ...screws 3 Remove the service PC board switch cover 1 screw 4 Switch SW5 and SW6 to off 5 Turn the operation mode switch SW2 to COOL 6 Screw the service PC board switch cover back on 1 screw 7 Switch th...

Страница 18: ...e manual If self correction is not possible check the indoor unit wiring and piping in the usual manner Service PC board A 1 2 3 4 5 Wiring error check switch SW3 LED Status 1 2 3 4 All Flashing Autom...

Страница 19: ...e extension Is the drainage secure Are the ground wire connections secure Are the electric wires connected correctly Is the wiring in accordance with the speci cations Are the inlets outlets of the in...

Страница 20: ...Two dimensional bar code is a manufacturing code 3P379970 9C M19B228 1912 HT...

Отзывы: