background image

EDUS04-906

Installation Manual

Room Air Conditioners H-Series

33

Accessories

Safety Precautions (2)

Precautions for Selecting the Location

1) Choose a place strong enough to bear the weight and vibration of the unit, The location should not amplified the unit noise.
2) Choose a location where the hot air discharged from the unit and  the operationing noise will not be  a nuisance to the neighbors. 
3) Avoid noise sensitive locations such as bedrooms to avoid future problems. 
4) There must be sufficient clearance for carrying the unit into and out of the site.
5) There must be sufficient space  around the air inlet and the air outlet with no obstructions to airflow.
6) The surrounding area must be free from the possibility of flammable gas leakage. 
7) Install units, power cords and inter-connecting cables at least 10 feet (3m) away from television and radio 

sets.  This is to prevent interference to images and sounds.  (Noises may be heard even if they are more 
than 10 feet (3m) away depending on radio wave conditions.)

8) In coastal areas or other places with salty atmosphere of sulfate gas, corrosion may shorten the life of the air conditioner.
9) Do not place moisture sensitive equipment or articles under the outdoor unit condenstate drain.

NOTE: 

Do not install unit by hanging from a ceiling or stacking units.

Accessories supplied 
with the outdoor unit:

(A) Installation manual

1

(C) Binding band

1

(B) Drain plug (Heat pump-Models)

There is on the 
bottom packing case.

1

When operating the air conditioner in a  outdoor  temperature 
below, be sure to follow the instructions described below.
1) To prevent exposure to wind, install the outdoor unit with its 

suction side facing the wall.

2) Never install the outdoor unit at a site where the suction side 

may be exposed directly to wind.

3) To prevent exposure to wind, it is recommended to install a 

baffle plate on the air discharge side of the outdoor unit.

4) In heavy snowfall areas, select an installation site where the 

snow will not affect the unit.

CAUTION

CAUTION

• Establish drain piping according to the instructions of this manual. 

Inadequate piping may cause water damage.

• Be very careful about product transportation. 

Some products use PP bands for packaging. Do not use any PP bands for a means of transportation. It is dangerous.

• Do not install the air conditioner where gas leakage would be exposed to open flames.

If the gas leaks and builds up around the unit, it may catch fire.

• Tighten the flare nut according to the specified torque. A torque wrench should be used.

If the flare nut is tightened too much, the flare nut may crack over time and cause refrigerant leakage.

• Do not touch the heat exchanger fins. 

Improper handling may result in injury.

• Make sure to provide for adequate measures in order to prevent that the outdoor unit be used as a shelter by small animals.

Small animals making contact with electrical parts can cause malfunctions, smoke or fire. Please instruct the customer to keep the area around the unit clean.

WARNING

• Be sure to install a ground fault circuit interrupter breaker.  

Failure to install a ground fault circuit interrupter breaker may result in electrically shocks, or fire personal injury.

• During pump-down, stop the compressor before removing the refrigerant piping.  

If the compressor is still running and the stop valve is open during 

pump-down, air will be sucked in when the refrigerant piping is removed, causing abnormally high pressure which could lead to equipment damage or and personal injury.

• During installation, attach the refrigerant piping securely before running the compressor.  

If the compressor is not attached and the stop valve is 

open during pump-down, air will be sucked in when the compressor is run, causing abnormally high pressure which could lead to equipment damage and personal injury.

Construct a large canopy.
Construct a pedestal.

Install the unit high enough off the 
ground to prevent burying in snow.

Содержание Quaternity FTXG09HVJU

Страница 1: ...EDUS04 906_a H Series Heat Pump...

Страница 2: ...ity Tables 9 7 1 Heat Pump 9 8 Operation Limit 15 9 Sound Level 16 9 1 Measuring Location 16 9 2 Octave Band Level 17 10 Electric Characteristics 19 11 Installation Manual 20 11 1 Indoor Units 20 11 2...

Страница 3: ...906 2 Room Air Conditioners H Series 1 Power Supply Note Power Supply Intake Outdoor Unit Indoor Units Outdoor Units Power Supply Quaternity FTXG09HVJU RXG09HVJU 1 208 230V 60Hz FTXG12HVJU RXG12HVJU F...

Страница 4: ...Control Auto Fan Speed Timer Weekly Timer Indoor Unit Quiet Operation 24 Hour ON OFF Timer Night Quiet Mode Automatic Count Up down ON OFF Timer OFFonly Outdoor Unit Quiet Operation Manual Night Set...

Страница 5: ...ashable Mildew Proof Removable Washable Mildew Proof Running Current Rated A 0 12 0 14 0 14 0 15 Power Consumption Rated W 24 26 29 31 Power Factor 87 80 7 90 1 89 9 Temperature Control Microcomputer...

Страница 6: ...orizontal Downward Air Filter Removable Washable Mildew Proof Running Current Rated A 0 15 0 16 Power Consumption Rated W 33 35 Power Factor 95 7 95 1 Temperature Control Microcomputer Control Dimensi...

Страница 7: ...SPACE REAR WALL HOLE LIQUID PIPE 1 4 6 4 Cut AIR PURIFYING INDIVIDUAL OPERATION SPACE FOR PERFORMANCE GEAR CASE UNIT FIXED SCREWS INSIDE PANEL INCLUDING MOUNTING PLATE LEFT SPACE FOR PERFORMANCE THE...

Страница 8: ...PRINTED CIRCUIT BOARD R1T R2T CONNECTOR OPERATION SWITCH TERMINAL STRIP SWING MOTOR M1S M4S F1U M1F H2P H3P S1 S403 CN1 FG X1M S1W THERMISTOR A1P A5P MULTI MONITOR H1P LIMIT SWITCH FOR PANEL S1C LIMIT...

Страница 9: ...OR TEMPERATURE THERMISTOR 7 9 CuT FIELD PIPING 7 9 CuT COOLING GAS STOP VALVE M MOTOR OPERATED VALVE OUTDOOR UNIT FOUR WAY VALVE ON HEATING 1 2 12 7 CuT 3 8 9 5 CuT HEAT EXCHANGER 3 8 9 5 CuT 6 4 CuT...

Страница 10: ...96 0 48 8 80 7 78 0 52 8 64 7 71 0 54 8 39 7 61 0 57 7 97 7 44 0 61 64 4 77 0 10 06 8 72 0 44 9 64 8 56 0 48 9 22 8 39 0 53 9 05 8 33 0 54 8 80 8 23 0 57 8 38 8 07 0 61 67 0 80 0 10 27 9 37 0 44 9 85...

Страница 11: ...them with around values in direct proportion 5 Capacities are based on the following conditions Corresponding refrigerant piping length 25ft 7 5 m Level difference 0ft 6 Airflow rate AFR and Bypass f...

Страница 12: ...9 01 0 82 11 18 8 86 0 85 10 62 8 62 0 92 64 4 77 0 13 41 10 15 0 67 12 85 9 92 0 73 12 29 9 69 0 79 12 07 9 60 0 82 11 73 9 46 0 86 11 17 9 24 0 92 66 9 80 1 13 69 10 80 0 67 13 13 10 57 0 73 12 57 1...

Страница 13: ...them with around values in direct proportion 5 Capacities are based on the following conditions Corresponding refrigerant piping length 25ft 7 5 m Level difference 0ft 6 Airflow rate AFR and Bypass f...

Страница 14: ...8 1 10 13 98 10 28 1 15 13 28 9 97 1 24 64 4 77 0 16 76 11 80 0 90 16 07 11 49 0 99 15 37 11 19 1 07 15 09 11 07 1 11 14 67 10 89 1 16 13 97 10 60 1 24 67 0 80 0 17 11 12 45 0 90 16 41 12 15 0 99 15 7...

Страница 15: ...them with around values in direct proportion 5 Capacities are based on the following conditions Corresponding refrigerant piping length 25ft 7 5 m Level difference 0ft 6 Airflow rate AFR and Bypass f...

Страница 16: ...ce Continuous operation 4 50 Outdoor temp FWB 68 50 68 4 FDB 68 0ft Outdoor temp FDB Air flow rate High 77 77 86 82 4 50 Cooling 5 75 32 Indoor temp FDB Indoor temp FWB 25ft 14 32 109 86 Notes 23 59 5...

Страница 17: ...1 Operation sound is measured in an anechoic chamber 2 The data are based on the conditions shown in the table below Indoor Unit Outdoor Unit 3 3ft 2 6ft R5162 3 3ft R4796 Cooling Heating Piping Lengt...

Страница 18: ...30 50 40 63 OCTAVE BAND CENTER FREQUENCY Hz 125 250 500 1000 2000 4000 8000 OCTAVE BAND SOUND PRESSURE LEVEL dB 0dB 0 0002 bar THRESHOLDHEARING APPROXIMATE FORCONTINUOUS NOISE POWER SOURCE JIS STANDAR...

Страница 19: ...NC 60 NC 40 NC 50 NC 20 NC 30 60Hz 208 230V 49 208 230V 60Hz Cooling NC 20 NC 50 NC 60 NC 30 NC 40 48 60Hz 208 230V 208 230V 60Hz Heating 3D063011 COOLING NC 40 NC 30 NC 50 NC 60 NC 20 POWER SOURCE JI...

Страница 20: ...4 6 0 15 Symbols Note MCA MIN CIRCUIT AMPS A 1 RLA is based on the following conditions Indoor temp 80 FDB 67 FWB 26 7 CDB 19 4 CWB Outdoor temp 95 FDB 35 CDB 2 Maximum allowable voltage variation be...

Страница 21: ...severe injury or death and to gas pipes because a gas leak could result in an explosion which could lead to severe injury or death WARNING Installation should be left to the authorized dealer or anoth...

Страница 22: ...top valve is open during pump down air will be sucked in when the compressor is run causing abnormally high pressure which could lead to equipment damage and personal injury Be sure to install a groun...

Страница 23: ...tion pipe with the finishing tape from bottom to top Install the hose with a downward slope Cut thermal insulation pipe to an appropriate length and wrap it with tape making sure that no gap is left i...

Страница 24: ...anel air filter and upper panel 2 Fully open the top and bottom horizontal louvers See Fig 1 3 Remove the 3 screws in the front grille 4 Lift the hooks 3 locations on the front grille with a flathead...

Страница 25: ...d tighten with included indoor unit fixing screw 6 How to set the different addresses When 2 indoor units are installed in 1 room the 2 wireless remote controllers can be set for different addresses 1...

Страница 26: ...pull out if bending up the wire edge in advance 3 To connect the inter unit wiring after hooking the unit onto the mounting plate connect the inter unit wiring as shown in the figure at right A A A Bo...

Страница 27: ...e pipes If it is difficult to do remove the front panel first 5 Wrap the insulation on the piping with insulation tape If you are not replacing the drain hose store it in the location shown below 4 3...

Страница 28: ...ecting to the HA system 6 Shape the wires so that the service lid fits securely then close service lid WARNING 1 Do not use tapped wires strand wires extension cords or starburst connections as they m...

Страница 29: ...scharge the tab 3 4 2 Pull up the electric parts box cover slowly discharge the tab 4 slide up and discharge the tab 5 5 Insert the connection cord into the HA connector S21 6 Lay the connection cord...

Страница 30: ...s a joint 8 Improving installation strength We recommend screwing the indoor unit onto a mounting plate in order to improve the installation strength 1 Remove the front grille 2 Screw in the indoor un...

Страница 31: ...erve the following 1 Insulation material Polyethylene foam Heat transfer rate 0 041 to 0 052W mK 0 024 to 0 030 Btu fth F 0 035 to 0 045 kcal mh C Choose heat insulation materials that are designed fo...

Страница 32: ...d bases Fall vibration noise Did you install the deodorizing filter for the streamer and the titanium apatite photocatalytic air purifying filter Noise water leakage Have you performed a gas leak test...

Страница 33: ...put undue stress on the electrical covers panels or terminals Install covers over the wires Incomplete cover installation may cause terminal overheating electrical shock fire or equipment damage When...

Страница 34: ...e air discharge side of the outdoor unit 4 In heavy snowfall areas select an installation site where the snow will not affect the unit CAUTION CAUTION Establish drain piping according to the instructi...

Страница 35: ...5 16 50 More than 5 7 8 150 Top view More than 3 15 16 100 Walls facing two sides More than 1 15 16 50 More than 3 15 16 100 Side view 47 3 16 1200 or less Wall facing one side Wrap the insulation pip...

Страница 36: ...of the units 3 Never use piping which has been used for previous installations Only use parts which are delivered with the unit 4 Do never install a drier to this R410A unit in order to guarantee its...

Страница 37: ...of charging hose which comes from gauge manifold to gas stop valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure val...

Страница 38: ...gas and liquid refrigerant pipes Be sure to use the R410A tools to ensure pressure and to prevent foreign objects entering 6 Refilling the refrigerant Check the type of refrigerant to be used on the m...

Страница 39: ...e circuit by adding drain pump or other electrical equipment to unit terminals Doing so may cause electric shock or fire 3 Be sure to install an earth leak detector One that can handle higher harmonic...

Страница 40: ...tip Place the round crimp style terminals on the wires up to the covered part and secure in place Test items Incomplete cooling heating function No refrigerant gas leaks Draining line is properly inst...

Страница 41: ...Operation Manual EDUS04 906 40 Room Air Conditioners H Series 12 Operation Manual Avoid exposure to airflow for long periods of time...

Страница 42: ...EDUS04 906 Operation Manual Room Air Conditioners H Series 41 Avoid direct exposure to airflow Keep unit free of leaves and insects that can cause malfunction or electrical fire...

Страница 43: ...Operation Manual EDUS04 906 42 Room Air Conditioners H Series QUATERNITY DRYING DRY COOLING YELLOW The lamp color also changes according to the optional function...

Страница 44: ...EDUS04 906 Operation Manual Room Air Conditioners H Series 43 Ground terminal...

Страница 45: ...Operation Manual EDUS04 906 44 Room Air Conditioners H Series DRY button...

Страница 46: ...EDUS04 906 Operation Manual Room Air Conditioners H Series 45...

Страница 47: ...Operation Manual EDUS04 906 46 Room Air Conditioners H Series...

Страница 48: ...EDUS04 906 Operation Manual Room Air Conditioners H Series 47...

Страница 49: ...LING Operation Note on Dry Cooling operation DRY COOLING may raise humidity temporarily Hi Std Lo Constant 60 RH 55 RH 50 RH no change DRY operation Note on Dry Operation The operation mode change fro...

Страница 50: ...EDUS04 906 Operation Manual Room Air Conditioners H Series 49...

Страница 51: ...Operation Manual EDUS04 906 50 Room Air Conditioners H Series...

Страница 52: ...EDUS04 906 Operation Manual Room Air Conditioners H Series 51...

Страница 53: ...Operation Manual EDUS04 906 52 Room Air Conditioners H Series COOLING or DRY COOLING operation the A FLASH STEAMER AIR PURIFYING individual operation B DRY COOLING COOLING C HEATING...

Страница 54: ...EDUS04 906 Operation Manual Room Air Conditioners H Series 53 COOLING BREEZE operation is for COOLING DRY COOLING AND FLASH STREAMER AIR PURIFYING operation...

Страница 55: ...Operation Manual EDUS04 906 54 Room Air Conditioners H Series...

Страница 56: ...EDUS04 906 Operation Manual Room Air Conditioners H Series 55 1 8 F 1 C 3 6 F 2 C...

Страница 57: ...Operation Manual EDUS04 906 56 Room Air Conditioners H Series...

Страница 58: ...EDUS04 906 Operation Manual Room Air Conditioners H Series 57 COOLING or DRY COOLING mode or...

Страница 59: ...Operation Manual EDUS04 906 58 Room Air Conditioners H Series...

Страница 60: ...EDUS04 906 Operation Manual Room Air Conditioners H Series 59...

Страница 61: ...Operation Manual EDUS04 906 60 Room Air Conditioners H Series...

Страница 62: ...EDUS04 906 Operation Manual Room Air Conditioners H Series 61...

Страница 63: ...Operation Manual EDUS04 906 62 Room Air Conditioners H Series...

Страница 64: ...EDUS04 906 Operation Manual Room Air Conditioners H Series 63...

Страница 65: ...Operation Manual EDUS04 906 64 Room Air Conditioners H Series...

Страница 66: ...EDUS04 906 Operation Manual Room Air Conditioners H Series 65...

Страница 67: ...Operation Manual EDUS04 906 66 Room Air Conditioners H Series...

Страница 68: ...EDUS04 906 Operation Manual Room Air Conditioners H Series 67...

Страница 69: ...Operation Manual EDUS04 906 68 Room Air Conditioners H Series...

Страница 70: ...EDUS04 906 Operation Manual Room Air Conditioners H Series 69 3P226009 1...

Страница 71: ...ter for Time Clock Remote Control 2 Normal Open Pulse Contact Normal Open Contact KRP413A1S 3 Central Remote Controller Fahrenheit 1 DCS302C71 4 Central Remote Controller Celsius 1 DCS302CA61 5 Unifie...

Страница 72: ...in this manual Be sure to follow instructions Be sure to perform grounding work Never attempt After installation is complete test the unit to confirm that it is working properly and instruct the owne...

Страница 73: ...Indoor unit Adaptor case Install the adaptor case assy as close to the indoor unit as possible Removing case front Adaptor PCB Case front Screw Screw cover Remove the screw cover one of the screws and...

Страница 74: ...ay contacts Manufacturer Type Coil rated voltage Coil resistance Omron MY relay 12 V DC 160 ohm 10 Matsushita HC relay 12 V DC 160 ohm 10 4 Connection with Remote Controller Example connections with t...

Страница 75: ...s Off ON Off if operation was in Off mode before power failure On if operation was in On mode before power failure Instantaneous contact Normal contact S1 1 S2 1 OPEN CLOSE S1 1 S1 2 Pulse input OPEN...

Страница 76: ...ed from the Ve up controller 2 Component Parts and Separately Sold Parts which are Required This kit includes the following components Check to ensure that none of these are missing 1 2 3 4 1 2 3 4 1...

Страница 77: ...ol is rejected operate stop timer prohibition NOTE 2 During a forced stop all remote controller actions are prohibited Last command priority Contact Open to close air condition stops forced stop Close...

Страница 78: ...ached to the louver zFirst temporarily attach the louver with 4 screws then check that the angle is correct and finally tighten the screws fully 1 Install so that a short circuit is prevented 2 For th...

Страница 79: ...Optional Accessories EDUS04 906 78 Room Air Conditioners H Series...

Страница 80: ...ollton TX75006 info daikinac com www daikinac com AMERICAS Specifications designs and other content appearing in this brochure are current as of June 2009 but subject to change without notice EDUS04 9...

Отзывы: