IM 1272 • OPTILINE VERTICAL FAN COILS 10 www.DaikinApplied.com

Troubleshooting

Troubleshooting

•  2-Pipe valve control heating/cooling units
•  2-Pipe valve control heating/cooling auxiliary heat units
•  2-Pipe valve control heating/cooling with total electric 

heat units

•  4-Pipe valve control heating/cooling units

Most problems can be promptly diagnosed at the thermostat. 

The fan assembly is accessible and removable through the 

return air opening, after removal of the return air grill and fan 

access cover. The fan assembly has a five wire plug harness 

for power and 0-10VDC speed control signal. 

The 2-pipe units are equipped with a change-over aqua-

stat mounted on the riser accessed through the return air 

panel. The 2-pipe with auxiliary heat units have 2 aqua-stats 

and the 2-pipe with primary electric heat have no aqua-stat. 

Thermostats and control valves are 24VAC. 

If Fan Motor Fails To Start 

•  Check main power supply, (circuit breaker) and unit 

switch are “ON” and unit has power 

•  Set thermostat ON/OFF switch to “ON” and press fan 

button to “ON” 

•  If fan will not operate, check that there is 24VAC coming 

from the transformer

•  If 24VAC is not present, replace the transformer 
•  If 24 VAC is present from the transformer, check  the 

thermostat wiring connections and motor wiring harness 

plug and thermostat connections 

•  If all is good  and system is 4-pipe (no aquastat), check 

the DC voltage on terminals 11 & 12 on the thermostat. If 

no voltage is present, replace the thermostat

•  If the voltage is between 1 & 10VDC on terminals 11 & 

12, and there is supply voltage to the fan motor, replace 

the fan assembly 

•  If the system is change-over or has auxiliary electric 

there, check the voltage at the aquastats*

•  If no voltage is present at BLK or YEL, replace the 

aquastat 

* Aquastat with black, yellow and orange wire leads 

closes for heating at 85F +/- 5F through BLK and ORG 

and cooling at 65F +/ 5F through BLK and YEL.

Control Valve Fails to Operate  

Check the voltage from the thermostat, if no voltage, replace 

the thermostat. If 24 volts or a DC voltage for modulating 

valves is present, replace the actuator. If the system has an 

aquastat(s), check that 24 volts is present from the aquastat. 

If 24 volts is present, replace the actuator. If no voltage is 

present, replace the aquastat 

Electric Heat Coil Fails to Operate 

The electric heat coil module is located behind the motor 

cover above the fan and consists of a relay operated by the 

thermostat, a high temperature automatic limit control and 

thermal cut-off directly attached to the heating element. Both 

the thermal cut off and high temperature limit control are in the 

heating coil power circuit. 
The temperature limit control sensing element protrudes 

through the control box directly above the heating element 

to sense over heating of the coil including fan failure. This is 

an auto-reset type and will reset when the temperature drops 

below the preset limit. 

The thermal cut off is located below one of the coil terminals 

directly attached to the coil element. Both safety devices can 

be replaced easily in the field if continuity test reveal an open 

circuit. If these circuits are both closed, replace the heating 

element by removing the 4 screws securing the mounting plate 

and removing the entire heating assembly. 

Содержание OptiLine FSG

Страница 1: ...Installation Operation and Maintenance IM 1272 Group Fan Coils Part Number 910243712 Date July 2018 OptiLine Vertical Stack Fan Coil Model FSG...

Страница 2: ...Receiving Inspection 4 Installation 5 Installation of Units with Risers Attached 5 Maintenance 7 Operating Instructions 8 Standard Thermostat Digital Programmable Thermostat 8 Adjusting the Maximum CF...

Страница 3: ...Provide adequate combustion and ventilation air to the unit space as specified in the combustion and ventilation air section of these instructions WARNING Install this unit only in a location and pos...

Страница 4: ...rocedure It is stressed that the component manufacturer s recommended procedures be strictly followed Thermostats and other accessories which have been shipped separately should be inspected for trans...

Страница 5: ...fittings must be checked prior to pressure testing the system by the contractor as part of the installation procedure Mechanical fittings can loosen during transportation and handling If contractor in...

Страница 6: ...ian must carry out the work The junction box is located behind the fan motor shield Electrical power to the unit should be disconnected by opening the remote disconnect device prior to removing the fa...

Страница 7: ...the grille panel Grasp the bottom edge of the door and sharply pull the door forwards Lift the door to the horizontal position The filter is now accessible and is removed by sliding it upwards out of...

Страница 8: ...al to a 0 10VDC Adjusting the Maximum CFM WARNING If the maximum CFM is adjusted to a value above the design airflow excessive air noise could occur The maximum CFM is factory set to the closest nomin...

Страница 9: ...e than 100 F the A2 aquastat energizes the control valve If the water drops below 75 F the aquastat de energizes the control valve and energizes the electric heat relay The A2 aquatat has black yellow...

Страница 10: ...d there is supply voltage to the fan motor replace the fan assembly If the system is change over or has auxiliary electric there check the voltage at the aquastats If no voltage is present at BLK or Y...

Страница 11: ...r free and proper fan rotation Record electrical supply voltage and amperage Check all wiring for secure connections Close all unit isolation valves Flush water systems Open all isolation valves after...

Страница 12: ...1 2 TB1 1 2 5 6 YEL BLK QC3 5 8 2 1 QC3 BLK BLK BLK BLK BLK N L L2 L1 MAX FUSE 15 AMPS SYM Description DISC SWITCH 1 POLE 120 277V 30A XMR1 TRANSFORMER 120 208 240 277 TO 24V 40VA CLASS 2 F1 FUSE 250V...

Страница 13: ...12 AMPS BLK BLK BLK 2 1 BLK BLK L2 L1 TB1 1 2 5 6 YEL BLK QC3 5 8 2 1 QC3 L1 L2 SYM Description DISC SWITCH 2 POLE 120 277V 30A XMR1 TRANSFORMER 120 208 240 277 TO 24V 40VA CLASS 2 M1 MOTOR 208V 1 10...

Страница 14: ...LD 22AWG 2 COND SHIELD AC DC SHIELDED WIRE GND L N QC3 QC3 2 M1 L2 GND SYM Description DISC SWITCH 1 POLE 120 277V 15A XMR1 TRANSFORMER 120 208 240 277 TO 24V 40VA CLASS 2 M1 EBM MOTOR 120V 1 5 HP CVA...

Страница 15: ...WIRE N GND NC GND 1 8 AMPS FAN MOTOR QC3 M1 2 QC3 SYM Description DISC SWITCH 1 POLE 120 277V 15A XMR1 TRANSFORMER 120 208 240 277 TO 24V 40VA CLASS 2 M1 MOTOR 208 277 2 3 HP QC3 9 PIN QUICK CONNECT...

Страница 16: ...rn ON OFF thermostat 7 Set point icons Display set point temperature while it is flashing 8 Fan icons Indicate Fan status 9 Flake icon Indicate working in Cooling mode 10 Hot spring icon Indicate work...

Страница 17: ...uit of the controller Mounting front cover Lock front cover on the backplate by tightening the cover screw underneath with Philip screwdriver Wiring Example 1 All wires must be inserted above the reta...

Страница 18: ...cription Remarks 1 Normal Display Display current room or set point temperature and current time day Setting SP parameter in engineer table to choose current room or set point temperature 2 Temperatur...

Страница 19: ...d com 19 IM 1272 OPTILINE VERTICAL FAN COILS Figure 10 User Mode Operation Sequence Figure 11 Overview for the Settings of Clock and Programmable Schedules MODE Press MODE FAN or POWER button to escap...

Страница 20: ...IM 1272 OPTILINE VERTICAL FAN COILS 20 www DaikinApplied com Addendum Figure 12 Detailed State Diagram for Clock Setting...

Страница 21: ...13 Detailed State Diagram for Schedule Setting Press Mode button to select day shows steadily deselect day flash Press MODE button to toggle Cooling Heating Set points Press MODE button to toggle Cool...

Страница 22: ...0 8 00 8 00 8 00 8 00 60 F 60 F 60 F 60 F 60 F 60 F 60 F Sch 3 MODE 18 00 18 00 18 00 18 00 18 00 18 00 18 00 70 F 70 F 70 F 70 F 70 F 70 F 70 F Sch 4 MODE 22 00 22 00 22 00 22 00 22 00 22 00 22 00 60...

Страница 23: ...LS Control Actions ON OFF Valve Controls When Cooling or Heating is on a Running Gear MODE icon will be shown on the LCD Figure 14 Cooling and Heating Control Auto Changeover Dead band Option 0 Figure...

Страница 24: ...o be ESIC ESIH refer to Engineer table for details When the contact is deactivated Open Room will be back to be occupied it will set the set point values back to normal 3 The icon MODE MODE MODE or MO...

Страница 25: ...ter into engineer mode 2 Press UP or DOWN button to rotate the menu item and press MODE button to enter into the item 3 Press UP or DOWN button to change the setting and press MODE button to confirm t...

Страница 26: ...0 10 0 10 0 0 0 18 0 18 0 0 1 C F E12 Pb Proportional Band or Stage Width 2 0 0 10 0 3 6 0 18 0 0 1 C F E13 LOC Bit Definition Bit 0 Mode Button 1 Down Buttons 2 Up Button 3 Fan Button 4 Power Button...

Страница 27: ...F Type Step Default Range Default Range E21 dirH Heating Valve N C N O Setting 1 0 1 0 0 1 0 N O 1 N C E22 dbOP Dead band Options 1 0 1 1 0 1 0 DB is aligned to Cooling SP 1 SP is in the middle of DB...

Страница 28: ...t to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied Representative for warranty details To find your local Daikin Applied Representative...

Отзывы: