Gas Pipe Manifold Pressure Adjustment for Propane Gas Fuel:
For Two Stage Furnace:
1 .
Read gas pressure at the Inlet Pressure Tap of the
Honeywell VR8305Q Gas Safety Control Valve (
) and confirm pressure is at 11.0" wc. Adjust upstream
pressure reducing gas regulator as required to obtain
11.0" wc gas pressure.
2 .
The gas pipe manifold pressure for high fire (stage
#2) should be set at 8.2" wc. Adjust the High Pressure
Adjustment Honeywell VR8305Q Gas Safety Control
Valve (
) as required. Screwing the adjustment
clockwise will increase pressure; counter clockwise will
decrease pressure.
3 .
The gas pipe manifold pressure for low fire (stage #1)
should be set at 2.05" wc. Adjust the Low Pressure
Adjustment Honeywell VR8305Q Gas Safety Control
Valve (
) as required. Screwing the adjustment
clockwise will increase pressure; counter clockwise will
decrease pressure.
For Modulating Furnace:
1 .
Read gas pressure at the Inlet Pressure Tap of the
Honeywell VR8305Q Gas Safety Control Valve (
) and confirm pressure is at 11.0" wc. Adjust upstream
pressure reducing gas regulator as required to obtain
11.0" wc gas pressure.
2 .
The gas pipe manifold pressure for high fire should be set
at 8.2" wc. Adjust the High Pressure Adjustment on the
Honeywell VR8305Q Gas Safety Control Valve (
) as required. Screwing the adjustment clockwise
will increase pressure; counter clockwise will decrease
pressure .
3 .
The gas pipe manifold pressure for low fire (stage #1)
should be set at 0.51" wc.
Adjust the Low Pressure Adjustment on the Honeywell
VR8305Q Gas Safety Control Valve (
) as
required until pressure at the Honeywell VR8305Q Gas
Safety Control Valve Outlet Pressure Tap reads 0.51"
wc. Screwing the adjustment clockwise will increase
pressure; counter clockwise will decrease pressure.
Adjust the Maxitrol M520B Modulating Valve (
)
Low Flow Adjustment screw until the gas pipe manifold
pressure reads 0.51" w.c.
o
PTIonal
G
as
h
eaT
www.DaikinApplied.com
29
IM 1058-8 • MAVERICK II ROOFTOP SYSTEMS
Содержание MPS015 F
Страница 70: ...Figure 64 VAV Control Inputs IM 1058 8 MAVERICK II ROOFTOP SYSTEMS 70 www DaikinApplied com Wiring Diagrams ...
Страница 80: ...Figure 70 CAV Power IM 1058 8 MAVERICK II ROOFTOP SYSTEMS 80 www DaikinApplied com Wiring Diagrams ...
Страница 81: ...Figure 70 continued CAV Power Wiring Diagrams www DaikinApplied com 81 IM 1058 8 MAVERICK II ROOFTOP SYSTEMS ...
Страница 82: ...Figure 71 CAV Control Inputs IM 1058 8 MAVERICK II ROOFTOP SYSTEMS 82 www DaikinApplied com Wiring Diagrams ...
Страница 86: ...Figure 76 Energy Recovery IM 1058 8 MAVERICK II ROOFTOP SYSTEMS 86 www DaikinApplied com Wiring Diagrams ...