![Daikin MPS015 F Скачать руководство пользователя страница 128](http://html1.mh-extra.com/html/daikin/mps015-f/mps015-f_installation-and-maintenance-manual_2460261128.webp)
Figure 100: BMS Communications
–
Keypad/Display Menu Structure
Figure 101: Trending
–
Keypad/Display Menu Structure
LON Set-Up
Neuron ID= xxxxxxxxxxxx
SndHrtBT= 60s
RcvHrtBT= 30s
MinSndTm= 0s
Comm Status=_________
LON BSP= X.XXX
LON App Ver= XXXX
BACnet IP Set-Up
ApplyIPChgs= No
Name= xxxxxxxxxxxxxxxx
Dev Instance= xxxxxxxxxx
UDP Port= 47808
DHCP= On
Act IP= 0.0.0.0
ActMsk- 0.0.0.0
ActGwy= xxx.xxx.xxx.xxx
Gvn IP= 127.0.0.1
GvnMsk= 255.255.255.0
GvnGwy= 127.0.0.1
Unit Support= English
NC Dev 1= 0
NC Dev 2= 0
AHU Loc/Net= Network
Comm Status= ________
Rst Out of Srvc= No
BACnet BSP= X.X.XX
BACnet MSTP Set-Up
ApplyMSTPChgs= No
Name= xxxxxxxxxxxxxxxx
Dev Instance= xxxxxxxxxx
MSTP Address= XXX
Baud Rate= 76800
Max Master= 127
Max Info Frm= 10
Unit Support= English
Term Resistor= No
NC Dev 1= 0
NC Dev 2= 0
AHU Loc/Net= Network
Comm Status= ________
Rst Out of Srvc= No
BACnet BSP= X.X.XX
Network Unit Set-Up
Space Sensor= Local/Net
UNIT MODE SETTINGS
Ctrl Mode= Off
Occ Mode= Auto/net
RESET OPTIONS
Clg Reset= None
Htg Reset= None
Min OA Reset= None
Apply Changes= No
HEAT/COOL CHANGEOVER
Ctrl Temp SRC= RAT
Occ Clg Spt= 72°F
Occ Htg Spt= 68°F
FAN CONTROL OPTIONS
SAF Ctlr= DSP
RF/EF Ctlr= Tracking
D-Net Set-Up
ApplyD-NetChgs= No
DHCP= On
Act IP= 0.0.0.0
ActMsk- 0.0.0.0
ActGwy= xxx.xxx.xxx.xxx
Gvn IP= 127.0.0.1
GvnMsk= 255.255.255.0
GvnGwy= 127.0.0.1
Remote Srv En= Disable
Comm Status= ________
D-net BSP= X.X.XX
BMS Communications
LON Set-Up
►
BACnet MSTP Set-Up
►
BACnet IP Set-Up
►
D-Net Set-Up
►
Network Unit Set-Up
►
Trending
Trending Ena= No
Apply Chgs= No
Sample Time= 300s
TrendOnOff= Off
Export Data= No
Clear Trend= Done
Points 1–8 (Fixed)
►
Points 9–24 (from List)
►
Points 25–27 (with IDs)
►
Points 28–30 (with IDs)
►
Points 1–8 (Fixed)
Point 1= UnitSt
Point 2= Clg%
Point 3= Htg%
Point 4= SAF%
Point 5= OAD/Eco%
Point 6= CtrlTmp
Point 7= DAT
Point 8= OAT
Points 9–24 (from List)
Point 9= None
Point 10= None
Point 11= None
Point 12= None
Point 13= None
Point 14= None
Point 15= None
Point 16= None
Point 17= None
Point 18= None
Point 19= None
Point 20= None
Point 21= None
Point 22= None
Point 23= None
Point 24= None
Points 25–27 (with IDs)
Point 25
ID= F0AF0000
Type= 0000
Mem Num= 0100
Point 26
ID= F0AF0000
Type= 0000
Mem Num= 0100
Point 27
ID= F0AF0000
Type= 0000
Mem Num= 0100
Points 28–30 (with IDs)
Point 28
ID= F0AF0000
Type= 0000
Mem Num= 0100
Point 29
ID= F0AF0000
Type= 0000
Mem Num= 0100
Point 30
ID= F0AF0000
Type= 0000
Mem Num= 0100
IM 1058-8 • MAVERICK II ROOFTOP SYSTEMS
128
www.DaikinApplied.com
a
PPendIx
– k
eyPad
/d
IsPlay
m
enU
s
TrUCTUre
Содержание MPS015 F
Страница 70: ...Figure 64 VAV Control Inputs IM 1058 8 MAVERICK II ROOFTOP SYSTEMS 70 www DaikinApplied com Wiring Diagrams ...
Страница 80: ...Figure 70 CAV Power IM 1058 8 MAVERICK II ROOFTOP SYSTEMS 80 www DaikinApplied com Wiring Diagrams ...
Страница 81: ...Figure 70 continued CAV Power Wiring Diagrams www DaikinApplied com 81 IM 1058 8 MAVERICK II ROOFTOP SYSTEMS ...
Страница 82: ...Figure 71 CAV Control Inputs IM 1058 8 MAVERICK II ROOFTOP SYSTEMS 82 www DaikinApplied com Wiring Diagrams ...
Страница 86: ...Figure 76 Energy Recovery IM 1058 8 MAVERICK II ROOFTOP SYSTEMS 86 www DaikinApplied com Wiring Diagrams ...