Thermal Overload Relay
Designed to provide current-dependent protection for loads
with normal starting against impermissibility high temperature
rises due to overload, phase asymmetry or phase failure.
Increase in motor current beyond set point as a result to
overload or phase failure will trip the overload and disconnect
the motor.
The Relay trip points are factory set. Do not change unless
the motor ampacity changes or the Relay is replaced with
a new device with incorrect set point adjustment. Any other
non-authorized trip points or set points adjustment voids all or
portions of the unit’s warranty. Authorized set point adjustment
is accomplishment as follows:
1 .
For motors with 1.15 service factor, rotate the arrow on the
dial to correspond to the motor FLA (See
2 .
For motors with a 1.0 service factor, multiply the motor
FLA with 0.9; then rotate the arrow on the dial to
correspond to that value.
To reset a tripped Relay, push the blue RESET button. To
disconnect, push the Red stop Button.
Other Relay features:
• Three connection systems options, Screw type, spring
loaded and ring cable lug connection.
• Switch position indicator to indicate a trip and TEST
function for wiring.
• Large rotary button to adjust current to Motor RLA.
• Selector switch for manual/and automatic RESET.
Figure 85: Overload Relay
Circuit Breaker
Circuit breakers are installed upstream of all VFDs to provide
short circuit protection. These breakers are not adjustable.
To reset a tripped circuit breaker: Clear the trip by rotating the
lever down to the OFF position. Then rotate lever up to the ON
position (see
Breakers, like MMPs, have three distinct modes of operation
which are clearly indicated by the handle position. The
positions are ON (usually up, OFF (usually down), and
TRIPPED (midway). Some circuit breakers may have a push-
to-test button .
CAUTION
If a circuit breaker has tripped due to an overload or a fault
current (short circuit), prior to resetting, the connected wiring
circuits must be checked to determine the cause of the
interruption .
Reset After Tripping Information
If a breaker is tripped, the handle/lever will be halfway between
the OFF and ON positions. To reset a tripped circuit breaker:
1 .
Press the handle or rotate the lever to the OFF position.
2 .
Press the handle or rotate the lever the opposite
direction to the ON position.
WARNING
In certain applications the circuit breaker may be mounted
upside down. Therefore, when the handle is in the DOWN
position it may not be turned OFF. The handle position
corresponds to ON and OFF text clearly printed on the face
of the unit. Be sure the mounting orientation and desired
handle position is verified prior to performing service on the
equipment. Only qualified service personnel should work on
this equipment.
Improper position of the breaker handle
during service may result in electric shock or death .
Figure 86: Circuit Breaker
m
aInTenanCe
www.DaikinApplied.com
103
IM 1058-8 • MAVERICK II ROOFTOP SYSTEMS
Содержание MPS015 F
Страница 70: ...Figure 64 VAV Control Inputs IM 1058 8 MAVERICK II ROOFTOP SYSTEMS 70 www DaikinApplied com Wiring Diagrams ...
Страница 80: ...Figure 70 CAV Power IM 1058 8 MAVERICK II ROOFTOP SYSTEMS 80 www DaikinApplied com Wiring Diagrams ...
Страница 81: ...Figure 70 continued CAV Power Wiring Diagrams www DaikinApplied com 81 IM 1058 8 MAVERICK II ROOFTOP SYSTEMS ...
Страница 82: ...Figure 71 CAV Control Inputs IM 1058 8 MAVERICK II ROOFTOP SYSTEMS 82 www DaikinApplied com Wiring Diagrams ...
Страница 86: ...Figure 76 Energy Recovery IM 1058 8 MAVERICK II ROOFTOP SYSTEMS 86 www DaikinApplied com Wiring Diagrams ...