Troubleshooting Guide and FAQ
Troubleshooting Guide and FAQ
The following Troubleshooting Guide is intended to be a
helpful reference and source of supplemental information. It
provides answers to common questions about the controls
subjects covered in previous sections of this manual. The
troubleshooting topics are organized into five categories:
WSHP equipment configuration, unit controller and I/O
expansion modules, BACnet or
LonWorks
communication
modules, Flasher tools, and finally J-Link tools.
WSHP Equipment Configuration
This section describes the equipment options for each model.
show the hardware jumper settings used by the
unit controller and I/O expansion module. The tables are
categorized by model and compressor type.
,
summarize the valid configuration
options by model.
Enfinity Single Stage Compressor Control
Table 5:
Unit Controller Configuration Jumpers for Enfinity Single Stage Compressor
Unit Controller Option
Hardware Jumpers Setting
Description
Normal / Test Mode
JP1
JP1 = Open
Normal Operation
JP1 = Shorted
Service / Test Mode
Fan Operation
JP2
JP2 = Open
Continuous Fan Operation (ON)
JP2 = Shorted
Cycling Fan Operation (AUTO)
Loop Fluid
JP3
JP3 = Open
Water Loop Fluid
JP3 = Shorted
Glycol Loop Fluid
Alarm “A” Terminal Polarity Select (v3.1 & Newer)
JP4
JP4 = Open
Fault de-energizes alarm output to 0VAC.
JP4 = Shorted
Fault energizes alarm output to 24VAC.
Room Sensor Setpoint Adjust Range
JP5
JP5 = Open
Short Range: -3 to +3 ºF (-1.67 to +1.67 ºC)
JP5 = Shorted
Long Range: 55 to 95 ºF (12.78 to 35 ºC)
Thermostat / Room Sensor
JP6
JP6 = Open
Thermostat Control
JP6 = Shorted
Room Sensor Control
Not Used
JP7
JP7 = Open
—
Not Used
JP8
JP8 = Open
—
Table 6: I/O Expansion Module Configuration Jumpers for Enfinity Single Stage Compressor
I/O Expansion Module Option
Hardware Jumpers
Setting
Description
Number of Compressors
JP1
JP1 = Open
Single Compressor
JP1 = Shorted
Dual Compressor
Dehumidification
JP2
JP2 = Open
None
JP2 = Shorted
HGR Dehumidification
Secondary Heating
JP3 & JP4
JP3 = Open
None
JP4 = Open
JP3 = Shorted
Supplemental Electric Heat
JP4 = Open
JP3 = Open
Boilerless Electric Heat
JP4 = Shorted
Fan Speed Selection
JP5 & JP6
JP5 = Open
Single Speed Fan
JP6 = Open
JP5 = Shorted
Two Speed Fan
JP6 = Open
JP5 = Open
Three Speed Fan
JP6 = Shorted
Not Used
JP7
JP7 = Open
—
Lead Compressor Select (v3.1 & Newer)
JP8
JP8 = Open
Compressor #1 is Lead
JP8 = Shorted
Compressor #2 is Lead (Dual Compressor Models Only)