OM 1085-6 • MICROTECH III CONTROLLER 32 www.DaikinApplied.com
Troubleshooting Guide and FAQ
Two Speed Compressor, Multi-Fan Speed (Series1)
Table 14:
Unit Controller Configuration Jumpers for Two Speed Compressor, Multi-Fan Speed (Series1)
Unit Controller Option
Hardware Jumpers
Setting
Description
Normal / Test Mode
JP1
JP1 = Open
Normal Operation
JP1 = Shorted
Service / Test Mode
Fan Operation
JP2
1
JP2 = Open
Continuous Fan Operation (ON)
JP2 = Shorted
Cycling Fan Operation (AUTO)
Loop Fluid
JP3
JP3 = Open
Water Loop Fluid
JP3 = Shorted
Glycol Loop Fluid
Not Used
JP4
JP4 = Open
—
Room Sensor Setpoint Adjust Range
JP5
JP5 = Open
Short Range: -3 to +3 ºF (-1.67 to +1.67 ºC)
JP5 = Shorted
Long Range: 55 to 95 ºF (12.78 to 35 ºC)
Thermostat / Room Sensor
JP6
JP6 = Open
Thermostat Control
JP6 = Shorted
Room Sensor Control
Fan Speed Selection
JP7 & JP8
JP7 = Open
Single Speed Fan
JP8 = Open
JP7 = Shorted
Two Speed Fan (User Selectable)
JP8 = Open
JP7 = Open
Three Speed Fan (Automatic)
JP8 = Shorted
1
JP2 setting applies only if: (1) there is a room sensor and (2) the room sensor does not have the Fan ON/AUTO switch input option wired.
Table 15:
I/O Expansion Module Configuration Jumpers for Two Speed Compressor, Multi-Fan Speed (Series1)
I/O Expansion Module Option
Hardware Jumpers
Setting
Description
Compressor
JP1 & JP2
JP1 = Open
Single Compressor, Single Stage Capacity
JP2 = Open
JP1 = Shorted
Single Compressor, Dual Stage Capacity
JP2 = Open
JP1 = Open
Dual Compressor, Single Stage Capacity
JP2 = Shorted
Secondary Heating
JP3 & JP4
JP3 = Open
None
JP4 = Open
JP3 = Shorted
Supplemental Electric Heat
JP4 = Open
JP3 = Open
Boilerless Electric Heat
JP4 = Shorted
JP3 = Shorted
Hydronic Heating
JP4 = Shorted
Dehumidification
JP5 & JP6
JP5 = Open
None
JP6 = Open
JP5 = Shorted
HGR Dehumidification
JP6 = Open
JP5 = Open
Half Stage Dehumidification
JP6 = Shorted
Not Used
JP7
JP7 = Open
—
Not Used
JP8
JP8 = Open
—