7
|
Technical specifications
Installer reference guide
34
MCS341-DS1-111
Security gateway
4P529063-1A – 2020.12
All wiring must comply with the following requirements:
Connection
Cross section
Max. length
Remarks
LAN cable
—
100 m
▪
UTP CAT 5e or higher
▪
RJ45 connector
DIII-NET (F1/F2)
Ø0.75~1.25 mm²
(terminal sized for
maximum 1.5 mm²)
Total length
(a)
:
2000 m (<1500 m
when using shielded
wire)
Max. length
(b)
: 1000 m
▪
Cable type: 2-core vinyl insulated vinyl-
sheathed cable/vinyl cabtyre cable or 2-core
shielded cable
▪
Do NOT use multicore cables with 3 or more
cores
▪
Do NOT use mixed cable types
▪
NEVER bundle the cables
▪
When using a shielded cable, connect only
one end of each shield wire to the ground
▪
Make sure the wiring is routed and fixed, so
as NOT to touch unearthed accessible
conductive parts
▪
Make sure a strain relief is available for each
wire entering the electrical cabinet
▪
For more information on DIII‑NET, refer to the
DBACS design guide (ED72721)
230 V AC power
supply to the PU
According to
applicable legislation
(terminal sized for
maximum 4 mm²)
According to
applicable legislation
▪
Solid or stranded wire allowed
▪
The internal protection of the WAGO PSU is
fused at 2.5 A / 250 V
24 V DC power
supply to the
Security gateway
module
According to
applicable legislation
—
Solid or stranded wire allowed
(a)
Total length
is the sum of all wiring in the DIII‑NET network.
(b)
Max. length
is the maximum distance between any 2 connection points in the DIII‑NET network.
7.5 System requirements
The PC you use for setup of the Security gateway must comply with these
minimum requirements:
CPU
Intel i3 2.2 GHz or higher
Operating
system
Microsoft Windows 7 or higher
Memory
512 MB RAM or more
Free space
on hard
drive
10 GB or more
Network
10 BASE-T or higher