Table 14: Auxiliary Heater Kits Characteristics and Application: 480V — 3 Phase
Unit Model Number
MPS
Heater Kit
Model No . RXJJ
Heater Kw @ 480V
Heater Kit Fla
Unit Min . Ckt . Ampacity
Max . Fuse or Ckt . Bkr . Size
(Ckt . Bkr . Must Be HACR
Type For USA)
015 Low Static Drive
NONE
—
—
38
45
CE20D
19.2
23.1
38
45
CE40D
38.4
46.2
64
70
CE60D
57.6
69.3
93
100
CE75D
72
86.6
114
125
015 High Static Drive
NONE
—
—
40
50
CE20D
19.2
23.1
40
50
CE40D
38.4
46.2
67
70
CE60D
57.6
69.3
95
100
CE75D
72
86.6
117
125
020 Low Static Drive
NONE
—
—
52
60
CE20D
19.2
23.1
52
60
CE40D
38.4
46.2
67
70
CE60D
57.6
69.3
95
100
CE75D
72
86.6
117
125
020 High Static Drive
NONE
—
—
56
70
CE20D
19.2
23.1
56
70
CE40D
38.4
46.2
70
70
CE60D
57.6
69.3
99
100
CE75D
72
86.6
121
125
025 Low Static Drive
NONE
—
—
60
70
CE20D
19.2
23.1
60
70
CE40D
38.4
46.2
70
70
CE60D
57.6
69.3
99
100
CE75D
72
86.6
121
125
025 High Static Drive
NONE
—
—
63
80
CE20D
19.2
23.1
63
80
CE40D
38.4
46.2
74
80
CE60D
57.6
69.3
103
110
CE75D
72
86.6
124
125