9
2-14
2.4 OPERATION MODES AND CONTROL
The relationship between the operation mode and setting temperature is as follows.
Operation mode
Setting temperature
Control sensor
Operation description
Frozen mode
–10.1˚C to –30.0˚C
Return air
Compressor ON/OFF control
(13.82˚F to –22.0˚F)
temperature sensor
+30.0˚C to –10.0˚C
Supply air
Capacity control operation
Chilled mode
(+86.0˚F to –14.0˚F)
temperature sensor
with suction modulating valve
and hot-gas bypass control
Defrosting mode
–
–
Hot-gas defrosting with
refrigerant metering control
09̲LXE10E-A33.indd 9
09̲LXE10E-A33.indd 9
07.2.1 10:53:19 AM
07.2.1 10:53:19 AM
https://daikin-p.ru
Содержание LXE10E-A33
Страница 18: ...17 9 2 Schematic wiring diagram LXE10E A33 https daikin p ru...
Страница 19: ...18 9 3 Stereoscopic wiring diagram LXE10E A33 BLK BLU GRN GRY RED WHT BRN YLW https daikin p ru...
Страница 59: ...Parts related with option 3 Others 58 K2 K5 K3 K4 K1 Indoor fan guard Evaporator coil K6 https daikin p ru...
Страница 71: ...MEMO https daikin p ru...