SiBE05-513A
Control Specification
Function and Control
41
3.11.1 Fully Closing with Power ON
Initialize the electronic expansion valve when turning on the power, set the opening position and
develop pressure equalizing.
3.11.2
Pressure Equalization
Control
When the compressor is stopped, open and close the electronic expansion valve and develop
pressure equalization.
3.11.3
Opening
Limit
Outline
Limit a maximum and minimum opening of the electronic expansion valve.
Detail
A maximum electronic expansion valve opening : 480 pulses
A minimum electronic expansion valve opening : 52 pulses
The electronic expansion valve is fully closed in the room where cooling is stopped and is
opened with fixed opening during defrosting.
3.11.4
Starting Operation
Control
Control the electronic expansion valve opening when the system is starting, and prevent the
system to be super heated or moistened.
3.11.5 High Temperature of the
Discharge Pipe
When the compressor is operating, if the discharge pipe temperature exceeds a certain value,
open the electronic expansion valve and remove the refrigerant to the low pressure side and
lower discharge temperature.
3.11.6 Disconnection of the
Discharge Pipe Thermistor
Outline
Detect a disconnected discharge pipe thermistor by comparing the discharge pipe temperature
with the condensation temperature. If any is disconnected, open the electronic expansion valve
according to the outdoor air temperature and the operating frequency and operate for a
specified time, and then stop.
After 3 minutes of waiting, restart the unit and check if any is disconnected. If any is
disconnected stop the system after operating for a specified time. If the disconnection is
detected 4 times in succession, then the system will be down.
Detail
Detect Disconnection
If the timer for open control (cooling : 13min., heating : 15min.) becomes over, and the 9-minute
timer for the compressor operation continuation is not counting time, the following adjustment
must be made.
1. When the operation mode is cooling
When the discharge pipe temperature is lower than the outdoor heat exchanger
temperature, the discharge pipe thermistor disconnection must be ascertained.
2. When the operation mode is heating (only for heat pump model)
When the discharge pipe temperature is lower than the max temperature of indoor unit heat
exchanger, the discharge pipe thermistor disconnection must be ascertained.
Adjustment when the thermistor is disconnected
When compressor stop repeats specified time, the system should be down.
Содержание Inverter FLKS25BVMB
Страница 10: ...SiBE05 513A List of Functions 1 Part 1 List of Functions 1 List of Functions 2 ...
Страница 13: ...List of Functions SiBE05 513A 4 List of Functions ...
Страница 14: ...SiBE05 513A Specifications 5 Part 2 Specifications 1 Specifications 6 1 1 Cooling Only 6 1 2 Heat Pump 8 ...
Страница 19: ...Specifications SiBE05 513A 10 Specifications ...
Страница 25: ...Printed Circuit Board Connector Wiring Diagram SiBE05 513A 16 Printed Circuit Board Connector Wiring Diagram ...
Страница 55: ...Control Specification SiBE05 513A 46 Function and Control ...
Страница 83: ...Instruction SiBE05 513A 74 System Configuration ...
Страница 129: ...Check SiBE05 513A 120 Service Diagnosis ...
Страница 153: ...Outdoor Unit SiBE05 513A 144 Removal Procedure When reassembling make sure to fit the hook Step Procedure Points ...
Страница 167: ...Outdoor Unit SiBE05 513A 158 Removal Procedure ...
Страница 168: ...SiBE05 513A Others 159 Part 8 Others 1 Others 160 1 1 Test Run from the Remote Controller 160 1 2 Jumper Settings 161 ...
Страница 171: ...Others SiBE05 513A 162 Others ...
Страница 177: ...Wiring Diagrams SiBE05 513A 168 Appendix ...
Страница 181: ...SiBE05 513A iv Index ...