SiBE05-513A
Control Specification
Function and Control
33
2. Determine upper limit frequency
Set a minimum value as an upper limit frequency among the frequency upper limits of the
following functions:
Compressor protection, input current, discharge pipes, freeze-up protection, dew prevention,
fin thermistor temperature.
3. Determine lower limit frequency
Set a maximum value as an lower limit frequency among the frequency lower limits of the
following functions:
Pressure difference upkeep.
4. Determine prohibited frequency
There is a certain prohibited frequency such as a power supply frequency.
Indoor Frequency Command (
∆
D signal)
The difference between a room temperature and the temperature set by the remote controller
will be taken as the “
∆
D signal” and is used for frequency command.
∗
Th OFF = Thermostat OFF
Frequency Initial Setting
<Outline>
When starting the compressor, or when conditions are varied due to the change of the room, the
frequency must be initialized according to the
∆
D value of the indoor unit and the Q value of the
indoor unit.
Q value: Indoor unit output determined from indoor unit volume, air flow rate and other factors.
PI Control
(Determine Frequency Up / Down by
∆
D Signal)
1. P control
Calculate
∆
D value in each sampling time (20 seconds), and adjust the frequency according
to its difference from the frequency previously calculated.
2. I control
If the operating frequency is not change more than a certain fixed time, adjust the frequency
up and down according to the
∆
D value, obtaining the fixed
∆
D value.
When the
∆
D value is small...lower the frequency.
When the
∆
D value is large...increase the frequency.
3. Frequency management when other controls are functioning
When frequency is drooping;
Frequency management is carried out only when the frequency droops.
For limiting lower limit
Frequency management is carried out only when the frequency rises.
4. Upper and lower limit of frequency by PI control
The frequency upper and lower limits are set depending on indoor unit.
When low noise commands come from the indoor unit or when outdoor unit low noise or
quiet commands come from indoor unit, the upper limit frequency must be lowered than the
usual setting.
Temperature
difference
∆
D
signal
Temperature
difference
∆
D
signal
Temperature
difference
∆
D
signal
Temperature
difference
∆
D
signal
0
∗
Th
OFF
2.0
4
4.0
8
6.0
C
0.5
1
2.5
5
4.5
9
6.5
D
1.0
2
3.0
6
5.0
A
7.0
E
1.5
3
3.5
7
5.5
B
7.5
F
Содержание Inverter FLKS25BVMB
Страница 10: ...SiBE05 513A List of Functions 1 Part 1 List of Functions 1 List of Functions 2 ...
Страница 13: ...List of Functions SiBE05 513A 4 List of Functions ...
Страница 14: ...SiBE05 513A Specifications 5 Part 2 Specifications 1 Specifications 6 1 1 Cooling Only 6 1 2 Heat Pump 8 ...
Страница 19: ...Specifications SiBE05 513A 10 Specifications ...
Страница 25: ...Printed Circuit Board Connector Wiring Diagram SiBE05 513A 16 Printed Circuit Board Connector Wiring Diagram ...
Страница 55: ...Control Specification SiBE05 513A 46 Function and Control ...
Страница 83: ...Instruction SiBE05 513A 74 System Configuration ...
Страница 129: ...Check SiBE05 513A 120 Service Diagnosis ...
Страница 153: ...Outdoor Unit SiBE05 513A 144 Removal Procedure When reassembling make sure to fit the hook Step Procedure Points ...
Страница 167: ...Outdoor Unit SiBE05 513A 158 Removal Procedure ...
Страница 168: ...SiBE05 513A Others 159 Part 8 Others 1 Others 160 1 1 Test Run from the Remote Controller 160 1 2 Jumper Settings 161 ...
Страница 171: ...Others SiBE05 513A 162 Others ...
Страница 177: ...Wiring Diagrams SiBE05 513A 168 Appendix ...
Страница 181: ...SiBE05 513A iv Index ...