SiBE05-513A
Troubleshooting
Service Diagnosis
93
4.12
Input Over Current Detection
Remote
Controller
Display
E8
Method of
Malfunction
Detection
An input over-current is detected by checking the input current value with the compressor
running.
Malfunction
Decision
Conditions
The following current with the compressor running continues for 2.5 seconds.
Cooling /
Heating: Above 12A
Supposed
Causes
Over-current due to compressor failure
Over-current due to defective power transistor
Over-current due to defective outdoor unit PCB
Error detection due to outdoor unit PCB
Over-current due to short-circuit
Troubleshooting
Check No.07
Refer to P.116
Check No.08
Refer to P.116
Note:
If the model doesn’t have SPM, replace the outdoor unit PCB.
Replace the outdoor unit
PCB.
∗
Inverter checker
Part No.: 1225477
Correct the power supply or
replace the SPM.
(Replace the outdoor unit
PCB.)
(R4698)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Input current flowing
above its stop level?
NO
YES
Any LED off?
YES
NO
Check with the inverter checker (
∗
).
Turn off the power, and reconnect
the harnesses. Turn on the power
again and get restarted.
Turn off the power and disconnect
the harnesses U, V and W.
Get restarted and measure the
input current.
Check No. 08
Check the discharge pressure.
Check No. 07
Check the installation condition.
∗
An input over-current may result from wrong internal wiring. If the wires have been disconnected and
reconnected for part replacement, for example, and the system is interrupted by an input over-current,
take the following procedure.
Содержание Inverter FLKS25BVMB
Страница 10: ...SiBE05 513A List of Functions 1 Part 1 List of Functions 1 List of Functions 2 ...
Страница 13: ...List of Functions SiBE05 513A 4 List of Functions ...
Страница 14: ...SiBE05 513A Specifications 5 Part 2 Specifications 1 Specifications 6 1 1 Cooling Only 6 1 2 Heat Pump 8 ...
Страница 19: ...Specifications SiBE05 513A 10 Specifications ...
Страница 25: ...Printed Circuit Board Connector Wiring Diagram SiBE05 513A 16 Printed Circuit Board Connector Wiring Diagram ...
Страница 55: ...Control Specification SiBE05 513A 46 Function and Control ...
Страница 83: ...Instruction SiBE05 513A 74 System Configuration ...
Страница 129: ...Check SiBE05 513A 120 Service Diagnosis ...
Страница 153: ...Outdoor Unit SiBE05 513A 144 Removal Procedure When reassembling make sure to fit the hook Step Procedure Points ...
Страница 167: ...Outdoor Unit SiBE05 513A 158 Removal Procedure ...
Страница 168: ...SiBE05 513A Others 159 Part 8 Others 1 Others 160 1 1 Test Run from the Remote Controller 160 1 2 Jumper Settings 161 ...
Страница 171: ...Others SiBE05 513A 162 Others ...
Страница 177: ...Wiring Diagrams SiBE05 513A 168 Appendix ...
Страница 181: ...SiBE05 513A iv Index ...