Operation manual

11

EWLP012~065KAW1N

Condenserless water-cooled water chillers

4PW30043-1

6

To adjust or to consult other user parameters before saving the
modifications, select another user parameter using the 

A

 and/

or 

Z

 key and then repeat from instruction 3 onwards.

7

To  save the modifications, press the 

E

  key.  To  cancel the

modifications wait approximately 40 seconds.

In the first case, the controller saves the changes, leaves the list
of user parameters and returns to normal operation, displaying
the inlet water temperature.
In the second case, the display starts flashing. Approximately
40 

seconds later, the controller leaves the list of user

parameters without saving the modifications. The inlet water
temperature reappears on the display.

Defining the unit's serial address

To  control the unit from a supervisory system, an address card
(optional module) should be installed in the unit. The unit's serial
address required for communication with the supervisory system is
defined by parameter 

ha

.  The default, limit and step values for the

serial address are:

Default value

1

 

Limit values

1

  to 

16

Step value

1

To define the unit's serial address, proceed as follows:

1

Enter the list of user parameters.

Parameter code 

:d

 appears on the display.

2

Select parameter code 

ha

 using the 

A

 and/or 

Z

 key.

3

Press the 

R

 key to switch to the parameter value.

4

Select the appropriate setting using the 

A

 and/or 

Z

 key.

5

Press the 

R

 key to return to the list of parameter codes.

6

To adjust or to consult other user parameters before saving the
modifications, select another user parameter using the 

A

 and/

or 

Z

 key and then repeat from instruction 3 onwards.

7

To  save the modifications, press the 

E

  key.  To  cancel the

modifications wait approximately 40 seconds.

In the first case, the controller saves the changes, leaves the list
of user parameters and returns to normal operation, displaying
the inlet water temperature.
In the second case, the display starts flashing. Approximately
40 

seconds later, the controller leaves the list of user

parameters without saving the modifications. The inlet water
temperature reappears on the display.

T

ROUBLESHOOTING

This section provides useful information for diagnosing and correct-
ing certain troubles which may occur in the unit.

Before starting the trouble shooting procedure, carry out a thorough
visual inspection of the unit and look for obvious defects such as
loose connections or defective wiring.

Before contacting your local dealer, read this chapter carefully, it will
save you time and money.

When a safety device was activated, stop the unit and find out why
the safety device was activated before resetting it. Under no circum-
stances safety devices may be bridged or changed to a value other
than the factory setting. If the cause of the problem cannot be found,
call your local dealer.

Symptom 1: The unit does not start, but the 

T

 LED lights up

Symptom 2: The unit does not start, but the 

T

 LED is flashing

Symptom 3: The unit does not start and the 

T

 LED does not light up

Symptom 4: One of the following safety devices is activated

When carrying out an inspection on the supply panel or on
the switch box of the unit, always make sure that the circuit
breaker of the unit is switched off.

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

The temperature setting is not 
correct.

Check the controller setpoint.

Power supply failure.

Check the voltage on the supply 
panel.

Blown fuse or interrupted protection 
device.

Inspect fuses and protection devices. 
Replace by fuses of the same size 
and type (refer to chapter 

"Electrical 

specifications" on page 2

).

Loose connections.

Inspect connections of the field 
wiring and the internal wiring of the 
unit. Tighten all loose connections.

Shorted or broken wires.

Test circuits using a tester and repair 
if necessary.

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

The flowstart timer is still running.

The unit will start after approx. 15 
seconds. Make sure that water is 
flowing through the evaporator.

The anti-recycling timer is still active.

The circuit can only start up after 
approximately 4 minutes.

The guard timer is still active.

The circuit can only start up after 
approximately 1 minute.

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

One of the following safety devices is 
activated:

• Reverse phase protector 
• Overcurrent relay (K*S)
• Discharge thermal protector (Q*D)
• Evaporating temperature thermostat 

(S*T)

• Flow switch (S10L)
• High pressure switch (S*HP)

Check on the controller and refer to 
symptom "4. One of the following 
safety devices is activated".
 Refer to 
the explanation of the digital 
controller in the chapter 

"Resetting 

alarms" on page 7

.

The unit is in anti-freeze alarm.

Check on the controller and refer to 
symptom "4. One of the following 
safety devices is activated".
 Refer to 
the explanation of the digital 
controller in the chapter 

"Resetting 

alarms" on page 7

The remote ON/OFF input is 
enabled and the remote switch is off.

Put the remote switch on or disable 
the remote ON/OFF input.

The keyboard is locked. The user 
parameter  

h9

 is set to 

0

.

Unlock the controller keyboard.

Symptom 4.1:  Overcurrent relay of compressor

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

Failure of one of the phases.

Check fuses on the supply panel or 
measure the supply voltage.

Voltage too low.

Measure the supply voltage.

Overload of motor.

Reset. If the failure persists, call your 
local dealer.

RESET

Push the red button on the over-
current relay inside the switch box. 
The controller still needs to be reset.

Symptom 4.2:  Low pressure switch or anti-freeze alarm 

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

Water flow to water heat exchanger 
too low.

Increase the water flow.

Shortage of refrigerant.

Check for leaks and refill refrigerant, 
if necessary.

Unit is working out of its operation 
range.

Check the operation conditions of 
the unit.

Inlet temperature to the water heat 
exchanger is too low.

Increase the inlet water temperature.

Flow switch is not working or no 
water flow.

Check the flow switch and the water 
pump.

RESET

After pressure rise, the low pressure 
switch resets automatically, but the 
controller still needs to be reset.

Содержание Hydrocube EWLP012KAW1N

Страница 1: ...OPERATION MANUAL EWLP012KAW1N EWLP020KAW1N EWLP026KAW1N EWLP030KAW1N EWLP040KAW1N EWLP055KAW1N EWLP065KAW1N Condenserless water cooled water chillers...

Страница 2: ...THROW THIS MANUAL AWAY KEEP IT IN YOUR FILES FOR FUTURE REFERENCE Read the chapter Overview of the user parameters on page 8 before changing the parameters Before starting up the unit for the first t...

Страница 3: ...Hz 50 Voltage V 400 Voltage tolerance 10 Recommended fuses aM 3x 40 3x 50 3x 50 Compressor Phase 3 Frequency Hz 50 Voltage V 400 Nominal running current A 11 6 14 7 16 8 Control Phase 1 Frequency Hz...

Страница 4: ...I O PCB A2P input output The I O PCB A2P contains a reverse phase protector The reverse phase protector detects if the 3 phases of the power supply are connected correctly If a phase is not connected...

Страница 5: ...ut having to drain the water circuit Water filter delivered with the unit installed in the field The filter installed in front of the unit removes dirt from the water to prevent damage to the unit or...

Страница 6: ...Switch on the circuit breaker on the unit Make sure that the unit is OFF on the controller 2 The crankcase heater is switched on automatically 3 Check the supply voltage on the supply terminals L1 L2...

Страница 7: ...also be caused by an overcharge of refrigerant Working pressure It is important to check the high and low pressure of the refrigerant circuit to ensure the proper operation of the unit and to guarant...

Страница 8: ...normal operation displaying the inlet water temperature In the second case the display will start flashing Approximately 40 seconds later the controller leaves the list of direct para meters The inlet...

Страница 9: ...appear in the following order d to define the measurement unit C or F c7 to define the time delay between the pump startup and the compressor startup c8 to define the time delay between the unit shut...

Страница 10: ...e delay between pump and compressor startup User parameter c7 allows you to define the time delay between the pump startup and the compressor startup The default limit and step values for the time del...

Страница 11: ...eration displaying the inlet water temperature In the second case the display starts flashing Approximately 40 seconds later the controller leaves the list of user parameters without saving the modifi...

Страница 12: ...start but the T LED is flashing Symptom 3 The unit does not start and the T LED does not light up Symptom 4 One of the following safety devices is activated When carrying out an inspection on the sup...

Страница 13: ...the fans turn freely Clean if necessary Dirty or partially blocked condenser Remove any obstacle and clean condenser coil using brush and blower Inlet air temperature of the condenser is too high The...

Страница 14: ...he figures below represent the average saturated temperature of R407C in relation to the pressure readout High pressure side Low pressure side conditions high pressure 20 bar subcool 3 C NOTES 10 20 1...

Страница 15: ...NOTES NOTES...

Страница 16: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW30043 1...

Отзывы: