EWLP012~065KAW1N
Condenserless water-cooled water chillers
4PW30043-1
Operation manual
2
Electrical specifications
(1)
A
D
ESCRIPTION
The EWLP condenserless water-cooled water chillers are available in 7 standard sizes.
Figure:
Main components
(1) Refer to the engineering data book for the complete list of specifications.
Model EWLP
012
020
026
030
Power supply
• Phase
3N~
• Frequency
(Hz)
50
• Voltage
(V)
400
• Voltage tolerance
(%)
±10
• Recommended fuses
(aM)
3x 16
3x 20
3x 25
3x 32
Compressor
• Phase
3~
• Frequency
(Hz)
50
• Voltage
(V)
400
• Nominal running current (A)
7.4
11.6
14.7
16.8
Control
• Phase
1~
• Frequency
(Hz)
50
• Voltage
(V)
230
• Recommended fuses
(aM)
factory installed
Model EWLP
040
055
065
Power supply
• Phase
3N~
• Frequency
(Hz)
50
• Voltage
(V)
400
• Voltage tolerance
(%)
±10
• Recommended fuses
(aM)
3x 40
3x 50
3x 50
Compressor
• Phase
3~
• Frequency
(Hz)
50
• Voltage
(V)
400
• Nominal running current (A)
11.6
14.7
16.8
Control
• Phase
1~
• Frequency
(Hz)
50
• Voltage
(V)
230
• Recommended fuses
(aM)
factory installed
13
14
15
16
17
500
500
500
5
10
2
3
1
4
10
11
11
9
2
3
4
3
1
1
7
5
9
8
6
6
18
18
12
12
7
8
500
500
500
500
500
EWLP012~030KAW1N
EWLP040~065KAW1N
1
Compressor
2
Evaporator
3
Accumulator
4
Switchbox
5
Chilled water in
6
Chilled water out
7
Discharge stop valve
8
Liquid stop valve
9
Evaporator entering water temperature sensor
10
Freeze up sensor
11
Digital display controller
12
Power supply intake
13
Ball valve (field installed)
14
Water filter (field installed)
15
Air purge valve (field installed)
16
T-joint for air purge (field installed)
17
Flow switch (with T-joint) (field installed)
18
Main switch
Required space around the unit for service