Operation manual

7

EWLP012~065KAW1N

Condenserless water-cooled water chillers

4PW30043-1

Adjusting the cooling temperature setpoint

The EWLP units enable definition and modification of the cooling
temperature setpoint. The default, limit and step values for the
cooling setpoint are:

Default value

12

.

°C

Limit values

7

.

0

 to  

25

.

0

°C

Step value

0

.

1

°C

To adjust the cooling temperature setpoint, proceed as follows:

1

Press the 

R

 key for approximately 5 seconds to enter the list of

direct parameters.

The direct parameter code 

r1

 defining the cooling temperature

setpoint appears on the display.

2

Press the 

R

 key.

The actual cooling temperature setpoint appears on the display.

3

Press the 

A

  or 

Z

  key  to raise, respectively lower the

temperature setting.

4

Press the 

R

 key to return to parameter code 

r1

.

5

To save the adjusted temperature setpoint, press the 

E

 key. To

cancel the modification wait approximately 40 seconds.

In the first case, the controller saves the changes, leaves the list
of direct parameters and returns to its normal operation,
displaying the inlet water temperature.

In the second case the display starts flashing. Approximately
40 

seconds later, the controller leaves the list of direct

parameters without saving the modified parameter. The inlet
water temperature reappears on the display.

Consulting actual operational information

The actual operational information that can be consulted in the list of
direct parameters consists of:

r6

 : outlet water temperature evaporator,

r8

 : ambient temperature,

c9

 : total running hours of the compressor1,

ca

 : total running hours of the compressor2,

cv

 : total running hours of the pump.

To consult the actual operational information, proceed as follows:

1

Press the 

R

 key for approximately 5 seconds to enter the list of

direct parameters.

The direct parameter code 

r1

 defining the cooling temperature

setpoint appears on the display.

2

Depending on the information to be consulted, select parameter
code 

r6

r8

c9

ca

 or 

cv

 using the 

A

 and/or 

Z

 key.

3

Press the 

R

  key  to consult the actual value of the selected

parameter.

4

Press the 

R

 key to return to the parameter codes.

5

To  consult other actual operational information, repeat from
instruction 2 onwards.

6

To  return to normal operation, press the 

E

  key or wait

approximately 40 seconds.

In the first case, the controller immediately leaves the list of
direct parameters and returns to normal operation displaying the
inlet water temperature.

In the second case, the display will start flashing. Approximately
40 seconds later, the controller leaves the list of direct para-
meters. The inlet water temperature reappears on the display.

Resetting alarms

When an alarm is detected, the following happens:

the buzzer is activated (if enabled by means of user parameter 

p4

),

the alarm relay is energized,

the display starts flashing, alternately showing the alarm code
and the inlet water temperature.

The following alarm codes may appear on the screen:

a1

: indicates an anti-freeze alarm,

e1

: indicates that the NTC probe used to measure the

evaporator inlet water temperature is defective,

e2

: indicates that the NTC probe used to measure the outlet

water temperature is defective,

e3

: indicates that the NTC probe used to measure the ambient

temperature is defective,

ee

,

ep

: indicates that the EEPROM on the controller PCB inside the

unit is defective,

ei

,

e0

: indicates that the supply voltage is exceedingly low (

ei

) or

exceedingly high (

e0

). In these cases contact a licensed

electrician,

el

: indicates that the power supply has a "remarkable noise". In

this case contact a licensed electrician,

f l

: indicates that there was no water flow either during the

period of 15 seconds after the pump was started or for 5
seconds while the compressor is active,

h1

: indicates that a high pressure switch, the discharge thermal

protection or the overcurrent protection of the compressor
motor is activated, 

l1

: indicates that the low pressure switch is activated. 

To reset an alarm, proceed as follows:

1

Press the 

O

 key to acknowledge the alarm.

The buzzer is de-activated.

2

Find the cause of shutdown and correct.

Refer to the chapter 

"Troubleshooting" on page 11

.

3

If the alarm codes 

a1

f l

h1

 or 

l1

 appear on the display, reset

the alarm manually by pressing the 

A

  and 

Z

  key

simultaneously for approximately 5 seconds.

In all other cases the alarm is reset automatically.

Once the alarm is reset, the error code no longer appears on the
display. The controller continues its normal operation, displaying
the inlet water temperature.

NOTE

By pressing any button while the display is flashing
and cancelling of all changes is in progress, the can-
celling process is stopped, the display stops flashing
and the user can continue to change the settings.

NOTE

To  reset the timers 

c9

ca

  and 

cv

, refer to chapter

"Resetting warnings" on page 8

.

NOTE

If the alarm codes 

f l

  and 

h1

  are flashing alternately,

the alarm is most probably caused by the reverse
phase protector or by the fuse for control circuit (F4)
that is blown.

Содержание Hydrocube EWLP012KAW1N

Страница 1: ...OPERATION MANUAL EWLP012KAW1N EWLP020KAW1N EWLP026KAW1N EWLP030KAW1N EWLP040KAW1N EWLP055KAW1N EWLP065KAW1N Condenserless water cooled water chillers...

Страница 2: ...THROW THIS MANUAL AWAY KEEP IT IN YOUR FILES FOR FUTURE REFERENCE Read the chapter Overview of the user parameters on page 8 before changing the parameters Before starting up the unit for the first t...

Страница 3: ...Hz 50 Voltage V 400 Voltage tolerance 10 Recommended fuses aM 3x 40 3x 50 3x 50 Compressor Phase 3 Frequency Hz 50 Voltage V 400 Nominal running current A 11 6 14 7 16 8 Control Phase 1 Frequency Hz...

Страница 4: ...I O PCB A2P input output The I O PCB A2P contains a reverse phase protector The reverse phase protector detects if the 3 phases of the power supply are connected correctly If a phase is not connected...

Страница 5: ...ut having to drain the water circuit Water filter delivered with the unit installed in the field The filter installed in front of the unit removes dirt from the water to prevent damage to the unit or...

Страница 6: ...Switch on the circuit breaker on the unit Make sure that the unit is OFF on the controller 2 The crankcase heater is switched on automatically 3 Check the supply voltage on the supply terminals L1 L2...

Страница 7: ...also be caused by an overcharge of refrigerant Working pressure It is important to check the high and low pressure of the refrigerant circuit to ensure the proper operation of the unit and to guarant...

Страница 8: ...normal operation displaying the inlet water temperature In the second case the display will start flashing Approximately 40 seconds later the controller leaves the list of direct para meters The inlet...

Страница 9: ...appear in the following order d to define the measurement unit C or F c7 to define the time delay between the pump startup and the compressor startup c8 to define the time delay between the unit shut...

Страница 10: ...e delay between pump and compressor startup User parameter c7 allows you to define the time delay between the pump startup and the compressor startup The default limit and step values for the time del...

Страница 11: ...eration displaying the inlet water temperature In the second case the display starts flashing Approximately 40 seconds later the controller leaves the list of user parameters without saving the modifi...

Страница 12: ...start but the T LED is flashing Symptom 3 The unit does not start and the T LED does not light up Symptom 4 One of the following safety devices is activated When carrying out an inspection on the sup...

Страница 13: ...the fans turn freely Clean if necessary Dirty or partially blocked condenser Remove any obstacle and clean condenser coil using brush and blower Inlet air temperature of the condenser is too high The...

Страница 14: ...he figures below represent the average saturated temperature of R407C in relation to the pressure readout High pressure side Low pressure side conditions high pressure 20 bar subcool 3 C NOTES 10 20 1...

Страница 15: ...NOTES NOTES...