background image

English

9

CAUTION

• The drain piping will be clogged with water and water leakage 

may result if the water is accumulated in the drain piping.

• Conduct drain-up piping work if the gradient is insuffi-

cient.

• Attach a support bracket at 3.3 to 4.9 ft (1 to 1.5 m) 

intervals for the prevention of piping deflection.

• Be sure to use the drain hose (2) and metal clamp (1).

Insert the drain hose (2) deep into the base of the 
drain socket, and securely fasten the metal clamp (1) 
within the taped part on the insertion front end of the 
hose.

Be sure to fasten the screw of the metal clamp (1) until 
the margin of the screw thread decreases to 3/16 in. 
(4 mm) or less.

NOTE

Be sure to follow the instructions as below.

• Do not connect the drain piping directly to a sewer that 

smells of ammonia.
The ammonia in the sewer may reach through the drain 
piping and corrode the heat exchanger of the indoor unit.

• Do not bend or twist the provided drain hose (2) in order 

not to impose excessive force on the hose. (Doing so 
may result in water leakage.)

• Take the procedure shown in the following illustration to 

perform concentrated drain piping.

• The Socket for maintenance can be used for natural 

drainage as shown below. As the drain pump operation 
does not need for natural drainage, it can be disable by 
field setting to reduce power consumption. 

(Refer to Table 6)

• Select the diameter of the concentrated drain piping to 

suit the capacity of equipment connecting to the concen-
trated drain piping.

(2) Check the smooth draining of the piping on completion of 

the installation of the piping.

[Before electrical work]

CAUTION

• A licensed electrical engineering technician must con-

duct electrical wiring work (including grounding work).

• If no licensed electrical engineering technician is avail-

able, take steps 3 and 4 after the test operation of the air 
conditioner is finished.

1. Remove the control box cover, 

and connect the single-

phase electric wires to terminals L1 and L2 of the ter-
minal block and the ground wiring to the ground ter-
minal

.

Perform wiring according to 

10-1. CONNECTING 

POWER SUPPLY, GROUND, REMOTE CONTROLLER, 
AND TRANSMISSION WIRING

 in 

10. WIRING EXAM-

PLE AND HOW TO SET THE REMOTE CONTROLLER

.

3.3 - 4.9 ft

(1 -1.5 m)

Support bracket

Downward slope of at least 1/100

(accessory)

(accessory)

Metal clamp (1)

Tape

Drain hose (2)

Concentrated drain piping

The drain piping will be clogged with water 
and water leakage may result if the water is 
accumulated in the drain piping.

Maintain 

a downward slope of at least 

1/100

 so that no air bank will be formed.

18 - 3/8 in.

 

(467 mm)

3-15/16 in. 

(100 mm) 

or more

Seal and insulate 
the drain socket.

Ceiling slab

3.3 - 4.9 ft

(1-1.5 m)

12 in. (300 mm) max.

28 in. (700 mm)

max.

Support bracket

Drain-up piping 
(field supply)

Adjustable 
(18-3/8 in. (467 mm) max.)

Metal clamp (1) (accessory)

Drain hose (2) (accessory)

Drain hose (2) (accessory)

Horizontal or 
upward slope

If there is an air bank, noise may be generated 
as a result of a water backflow when the drain 
pump comes to a stop.

Locate the drain hose horizontally 
or with a little upward gradient.

01_EN_3PN14093-18K.fm  Page 9  Monday, January 5, 2015  2:52 PM

Содержание FXMQ07PBVJU

Страница 1: ...JU READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE LIRE SOIGNEUSEMENT CES INSTRUCTIONS AVANT L INSTALLATION CONSERVER CE MANUEL A PORTEE DE...

Страница 2: ...c gas if it comes in contact with fire Exposure to this gas could cause severe injury or death After completing the installation work check that the re frigerant gas does not leak throughout the syste...

Страница 3: ...res to check for the tightness of the refrigerant piping installation Read the chapter Refrigerant Piping Work and follow the procedures Since R410A is a blend the required additional refriger ant mus...

Страница 4: ...Control system may malfunction Where the air contains high levels of salt such as that near the ocean and where voltage fluctuates greatly such as that in factories Also in vehicles or vessels This un...

Страница 5: ...wable limit Refer to the installation manual of the outdoor unit Items to be checked If not properly done what is likely to occur Check Are the indoor and outdoor units fixed firmly The units may drop...

Страница 6: ...lower part of the product see arrow view A 1 Refer to Fig 2 3 3 Inspection hatch 3 for the lower part of the product and the lower part of the control box see arrow view A 2 Refer to Fig 2 3 Unit in m...

Страница 7: ...may be easier to install accessories sold separately before installing the indoor unit Refer to the installation manuals provided to the accessories as well Be sure to use the accessories and specifi...

Страница 8: ...event the intrusion of dirt dust and moisture into the piping CAUTION Be sure to use the specified type of refrigerant for the refrigeration cycle and do not contaminate the refrigerant with air Venti...

Страница 9: ...fluorine the flux will deteriorate refrigerant oil As for the branching of the refrigerant piping or refrigerant refer to the installation manual provided with the outdoor unit 7 DRAIN PIPING WORK 1...

Страница 10: ...trated drain piping 2 Check the smooth draining of the piping on completion of the installation of the piping Before electrical work CAUTION A licensed electrical engineering technician must con duct...

Страница 11: ...essure Attach a canvas duct each to the air outlet and air inlet so that the vibration of the equipment will not be transmitted to the duct or ceiling Use a sound absorbing material insulation materia...

Страница 12: ...tric potential in the ground during lighting storms 9 2 ELECTRICAL CHARACTERISTICS MCA Minimum Circuit Ampacity A MOP Maximum Overcurrent Protective Device A kW Fan Motor Rated Output kW FLA Full Load...

Страница 13: ...h the included clamp When use the insulation tube Cut off the insulation tube as need length WARNING Trim and lay the wiring neatly and attach the control box cover securely An electric shock or fire...

Страница 14: ...door unit No 2 system For group control or use with 2 remote con trollers Tightening torque lbf ft N m Terminal block for remote controller and transmission wires 0 58 0 72 0 80 0 96 Terminal block fo...

Страница 15: ...E NO The Field Settings included with the remote control lists the order of the settings and method of operation Setting is made in all units in a group To set for individual indoor units or to check...

Страница 16: ...th the outdoor unit and check the defective point CAUTION If there is any change after airflow adjustment in the ventila tion paths e g the duct and air outlet be sure to make air flow auto adjustment...

Страница 17: ...rmance of this unit is based on the following airflow rate Dirt Time for display MODE NO FIRST CODE NO SECOND CODE NO Standard Approxi mately 2500 hours 10 20 0 01 Excessive dust Approxi mately 1250 h...

Страница 18: ...1502 HT 3PN14093 18K EM14A035 00_CV_3PN14093 18K fm Page 3 Tuesday December 9 2014 11 27 AM...

Отзывы: