Specifications
EDUS39-900-F10
4
FXMQ-MF
2. Specifications
Notes:
1
N
ominal cooling capacities are based on the follo
w
ing conditions:
Outdoor temperature: 91°FDB, 82°FWB (68
%
RH)
Discharge set temp: 64°FDB
Equivalent ref. piping: 25ft (Horizontal)
2
N
ominal heating capacities are based on the follo
w
ing conditions:
Outdoor temperature: 32°FDB, 27°FWB (50
%
RH)
Discharge set temp: 77°FDB
Equivalent ref. piping: 25ft (Horizontal)
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4 Air filter is not standard accessory, but please mount it in the duct system of the suction side.
Select its duct collection efficiency (gravity method) 50
%
or more.
5 Within the range that the total capacity of indoor units is 50 to 100
%
, it is possible to connect to the outdoor unit.
6 This equipment cannot be incorporated into the remote group control of the
V
R
V
III system.
Model
FXMQ48MFVJU
FXMQ72MFVJU
FXMQ96MFVJU
1 Cooling Capacity
Btu/h
48,000
72,000
96,000
2 Heating Capacity
Btu/h
30,000
47,000
59,000
Casing
Galvanized Steel Plate
Galvanized Steel Plate
Galvanized Steel Plate
Dimensions: (H×W×D)
in.
18’1/2’’×29’1/4’’×43’5/16’’
18’1/2’’×54’3/8’’×43’5/16’’
18’1/2’’×54’3/8’’×43’5/16’’
Coil (Cross
Fin Coil)
Ro
w
s×Stages×Fin
Pitch
in.
3×26×13
3×26×13
3×26×13
Face Area
ft²
3.01
7.00
7.00
Fan
Model
D13/4G2DA1
D13/4G2DA1
D13/4G2DA1
Type
Sirocco Fan
Sirocco Fan
Sirocco Fan
Motor Output ×
N
umber of Units
W
380×1
380×1
380×1
Air Flo
w
Rate (H/L)
cfm
635
988
1,236
External Static
Pressure
4
in. WG
0.88
0.96
1.03
Drive
Direct Drive
Direct Drive
Direct Drive
Temperature Control
Microprocessor Thermostat for Cooling
and Heating
Microprocessor Thermostat for Cooling
and Heating
Microprocessor Thermostat for Cooling
and Heating
Sound Absorbing Thermal Insulation Material
Glass Fiber
Glass Fiber
Glass Fiber
Air Filter
4
4
4
Piping
Connections
Liquid Pipes
in.
3/8
(Flare Connection)
3/8
(Flare Connection)
3/8
(Flare Connection)
Gas Pipes
in.
5/8
(Flare Connection)
3/4
(Brazing Connection)
7/8
(Brazing Connection)
Drain Pipe
PS1B (female thread)
PS1B (female thread)
PS1B (female thread)
Machine Weight (Mass)
Lbs
190
271
271
Safety Devices
Fuse
Thermal Protector
for Fan Motor
Fuse
Thermal Protector
for Fan Motor
Fuse
Thermal Protector
for Fan Motor
Refrigerant Control
Electronic Expansion
V
alve
Electronic Expansion
V
alve
Electronic Expansion
V
alve
Standard Accessories
Operation Manual, Installation Manual,
Sealing Pads, Scre
w
s, Clamps.
Operation Manual, Installation Manual,
Sealing Pads, Connection Pipes,
Scre
w
s, Clamps.
Operation Manual, Installation Manual,
Sealing Pads, Connection Pipes,
Scre
w
s, Clamps.
Connectable Outdoor Units
5,
6
R-410A P series
R-410A P series
R-410A P series
Dra
w
ing
N
o.
C : 3D065463
C : 3D065463
C : 3D065463
Содержание FXMQ-MF
Страница 1: ...EDUS 39 900 F10_a AMERICAS FXMQ MF Outdoor Air Processing Unit ...
Страница 6: ...EDUS39 900 F10 Dimensions FXMQ MF 5 3 Dimensions 3 1 Indoor Units FXMQ48MFVJU Unit in 3D065452A ...
Страница 7: ...Dimensions EDUS39 900 F10 6 FXMQ MF FXMQ72MFVJU FXMQ96MFVJU Unit in 3D065453A ...
Страница 8: ...EDUS39 900 F10 Piping Diagrams FXMQ MF 7 4 Piping Diagrams 4D018650C ...
Страница 16: ...EDUS39 900 F10 Fan Performances FXMQ MF 15 9 Fan Performances FXMQ48MFVJU FXMQ72MFVJU 3D065649B 3D065650B ...
Страница 17: ...Fan Performances EDUS39 900 F10 16 FXMQ MF FXMQ96MFVJU 3D065651B ...
Страница 19: ...Sound Levels Reference EDUS39 900 F10 18 FXMQ MF FXMQ96MFVJU 4D068577 ...