background image

Installation

EDUS39-600-F1_a

24

FXFQ-M

3.

SELECTING INSTALLATION SITE

 Attach an additional insulation pipe cover to the unit body 
when it is believed that the relative humidity in the ceiling 
exceeds 80%. Use glass wool, polyethylene foam, or some-
thing similar with a minimum 3/8 inch thickness  as insulation.

For this unit, you are able to select air flow direction.
To enable the discharge of air in 2 or 3 directions, it is neces-
sary to purchase the optional blocking pad kit.

(1) Select an installation site where the following conditions 

are fulfilled and that meets with your customer’s approval:
• No possible dripping of water from the refrigerant pipe, 

drain pipe, or water pipe into the upper space of the 
indoor unit, including the back of the ceiling.

• Optimum air distribution can be ensured.
• Nothing blocks air passage.
• Condensate can be properly drained.
• False ceiling is not noticeably on an incline.
• Sufficient clearance for maintenance and service can 

be ensured.

• Piping between indoor and outdoor units is possible 

within the allowable limit. Refer to the installation man-
ual of the outdoor unit.

DANGER

• Do not install unit in an area where flammable materials are 

present due to risk of explosion resulting in serious injury or 
death.

WARNING

• If supporting structural members are not strong enough to 

take the unit’s weight, the unit could fall out of place and 
cause serious injury.

NOTE

• Install the indoor and outdoor units, power supply wiring 

and connecting wires at least 3.5ft. away from televisions or 
radios in order to prevent image interference or noise.
Depending on the radio waves, a distance of 3.5 ft. may not 
be  enough to eliminate the noise.

(2) Ceiling height

This indoor unit may be installed on ceilings up to 11.5 ft. 
(30, 36: 13.8 ft.) in height as shown in the following table:

(3)  Airflow direction 

The below figures are approximations. Select   airflow 
directions best suited to the room and point of installation. 
For air discharge in 2 or 3 directions, it is necessary to 
make field settings by remote controller and to close the 
air outlet(s). Refer to the section FIELD SETTING in the 
installation manual of the optional blocking pad kit. 

(4) Use suspension bolts for installation.  Ensure the 

ceiling is strong enough to support the weight of the 
unit  If  any risk, reinforce the ceiling before installing 
the unit.

(5)

 Refer to  the installation pattern for instructions and to 
check for points requiring reinforcing.)

(length: in.)

Number of discharge outlets used

FXFQ12M~24M

4-way air 

discharge

3-way air 

discharge

2-way air 

discharge

Ceiling 

height

Standard

8.9

9.9

11.5

Number of discharge outlets used

FXFQ30M·36M

4-way air 

discharge

3-way air 

discharge

2-way air 

discharge

Ceiling 

height

Standard

10.5

11.8

13.8

Model

H

FXFQ12 · 18 · 24MVJU

9 7/16 or more

FXFQ30 · 36MVJU

11 3/4 or more

[Air flow direction]

Air discharge in 

4 directions

Air discharge in 

3 directions

Air discharge in 

2 directions

H

H

*59
or more

*59
or more

*59
or more

*59
or more

Air 
discharge

Air 
discharge

39 3/8 or more

Air 
inlet

Air inlet

Air discharge

Air 

discharge

[Space required for installation] 

NOTE)  Leave 7 7/8 or more space where marked 
             with the *, on sides where the air outlet is closed.

Содержание FXFQ-M

Страница 1: ...EDUS 39 600 F1_a AMERICAS FXFQ M Ceiling Mounted Cassette Type Multi Flow...

Страница 2: ...pearance 2 2 Specifications 3 3 Dimensions 5 4 Piping Diagrams 8 5 Wiring Diagrams 9 6 Electric Characteristics 10 7 Capacity Tables 11 7 1 Cooling Capacity 11 7 2 Heating Capacity 12 8 Air Velocity a...

Страница 3: ...External Appearance EDUS39 600 F1_a FXFQ M 2 1 External Appearance FXFQ12 36M...

Страница 4: ...eating Sound Absorbing Thermal Insulation Material Foamed Polystyrene Foamed Polyethylene Foamed Polystyrene Foamed Polyethylene Foamed Polystyrene Foamed Polyethylene Piping Connections Liquid Pipes...

Страница 5: ...ve Direct Drive Temperature Control Microprocessor Thermostat for Cooling and Heating Microprocessor Thermostat for Cooling and Heating Sound Absorbing Thermal Insulation Material Foamed Polystyrene F...

Страница 6: ...EDUS39 600 F1_a Dimensions FXFQ M 5 3 Dimensions FXFQ12MVJU FXFQ18MVJU 3D042631...

Страница 7: ...Dimensions EDUS39 600 F1_a FXFQ M 6 FXFQ24MVJU 3D042632...

Страница 8: ...EDUS39 600 F1_a Dimensions FXFQ M 7 FXFQ30MVJU FXFQ36MVJU 3D042633A...

Страница 9: ...Thermistor for liquid line temperature R3T Thermistor for gas line temperature Capacity Gas Liquid 12 18 M 1 2 12 7 mm 1 4 6 4 mm 24 30 36 M 5 8 15 8 mm 3 8 9 5 mm C 4D024460A Heat exchanger Gas pipi...

Страница 10: ...EDUS39 600 F1_a Wiring Diagrams FXFQ M 9 5 Wiring Diagrams FXFQ12M 18M 24M 30M 36MVJU 3D042620B...

Страница 11: ...Electric Characteristics EDUS39 600 F1_a FXFQ M 10 6 Electric Characteristics...

Страница 12: ...8 18 4 13 1 18 7 12 7 19 0 12 8 24 75 18 9 15 0 21 5 16 1 24 0 17 5 26 5 17 8 28 0 18 2 28 5 17 7 79 18 9 15 0 21 5 16 1 24 0 17 5 26 5 17 8 27 6 18 0 28 1 17 6 83 18 9 15 0 21 5 16 1 24 0 17 5 26 5...

Страница 13: ...0 56 0 23 2 22 1 21 0 20 0 19 5 18 4 24 22 0 20 0 23 3 23 3 23 3 23 2 23 2 23 2 26 0 24 0 24 5 24 4 24 4 24 3 24 3 24 3 30 0 28 0 25 6 25 5 25 5 25 5 25 4 24 5 35 0 32 0 26 7 26 6 26 6 26 6 26 0 24 5...

Страница 14: ...nd Temperature Distributions FXFQ M 13 8 Air Velocity and Temperature Distributions FXFQ12M Cooling mode FXFQ12M Heating mode 3D052941 AIRFLOW DISTRIBUTIONS TEMPERATURE DISTRIBUTIONS AIRFLOW DISTRIBUT...

Страница 15: ...city and Temperature Distributions EDUS39 600 F1_a FXFQ M 14 FXFQ18M Cooling mode FXFQ18M Heating mode 3D052942 AIRFLOW DISTRIBUTIONS TEMPERATURE DISTRIBUTIONS AIRFLOW DISTRIBUTIONS TEMPERATURE DISTRI...

Страница 16: ...00 F1_a Air Velocity and Temperature Distributions FXFQ M 15 FXFQ24M Cooling mode FXFQ24M Heating mode 3D052943 AIRFLOW DISTRIBUTIONS TEMPERATURE DISTRIBUTIONS AIRFLOW DISTRIBUTIONS TEMPERATURE DISTRI...

Страница 17: ...city and Temperature Distributions EDUS39 600 F1_a FXFQ M 16 FXFQ30M Cooling mode FXFQ30M Heating mode 3D052944 AIRFLOW DISTRIBUTIONS TEMPERATURE DISTRIBUTIONS AIRFLOW DISTRIBUTIONS TEMPERATURE DISTRI...

Страница 18: ...00 F1_a Air Velocity and Temperature Distributions FXFQ M 17 FXFQ36M Cooling mode FXFQ36M Heating mode 3D052945 AIRFLOW DISTRIBUTIONS TEMPERATURE DISTRIBUTIONS AIRFLOW DISTRIBUTIONS TEMPERATURE DISTRI...

Страница 19: ...Cassette Type Multi Flow Notes Operation noise differs with operation and ambient conditions dBA Model 208 230V 60Hz H L FXFQ12MVJU 31 28 FXFQ18MVJU 33 28 FXFQ24MVJU 34 29 FXFQ30MVJU 38 32 FXFQ36MVJU...

Страница 20: ...EDUS39 600 F1_a Installation FXFQ M 19 10 Installation Center of Gravity inches A B FXFQ12 18 24MVJU 9 1 8 4 1 2 FXFQ30 36MVJU 11 3 8 6 3 4 4D042639A...

Страница 21: ...ater stove cooking device or other heat source Exposure to this gas can cause severe injury or death Safely dispose of the packing materials Packing materials such as nails and other metal or wooden p...

Страница 22: ...r frostbite To avoid injury give the pipes time to return to normal temperature or if you must touch them be sure to wear proper gloves CAUTION While following the instructions in this installation ma...

Страница 23: ...es Control system may malfunction Where the air contains high levels of salt such as that near the ocean and where voltage fluctuates greatly such as that in factories Also in vehicles or vessels This...

Страница 24: ...Operation manual Quantity 1 each 2 pcs Shape 10 Large 11 Medium 12 Small Model Optional decoration panel Color White FXFQ12 18 24 30 36MVJU BYC125KW1 Remote controller Wired type BRC1D71 Items to be...

Страница 25: ...ft away from televisions or radios in order to prevent image interference or noise Depending on the radio waves a distance of 3 5 ft may not be enough to eliminate the noise 2 Ceiling height This indo...

Страница 26: ...or M10 size bolt Use a hole in anchor for existing ceilings and a sunken insert sunken anchor or other new ceiling parts to rein force the ceiling to bear the weight of the unit Adjust clearance from...

Страница 27: ...e center of the ceiling opening is indicated on the paper pattern for installation The center of the unit is indicated on the label attached to the unit and on the paper pattern for installation After...

Страница 28: ...door unit is charged with refrigerant DANGER Refrigerant gas may produce toxic gas if it comes in contact with fire such as from a fan heater stove or cooking device Exposure to this gas could result...

Страница 29: ...N Be sure to insulate any field piping all the way to the piping connection inside the unit Any exposed piping may cause condensation or burns if touched 7 4 Brazing refrigerant piping Before brazing...

Страница 30: ...g pipes at a height of less than 21 5 8 549 3 mm Install the drain raising pipes at a right angle to the indoor unit and no more than 11 13 16 298 4 mm from the unit NOTE The incline of attached drain...

Страница 31: ...ground units to water pipes telephone wires or lightning rods because incomplete grounding could cause a severe shock hazard resulting in severe injury or death Do not ground to gas pipes because a g...

Страница 32: ...when wiring make sure the lid on the electric parts box fits snugly by arranging the wires neatly and attaching the electric parts box lid firmly When attaching the electric parts box lid make sure no...

Страница 33: ...r into the recess between the upper and lower part of remote controller and working from the 2 positions pry off the upper part The remote controller PC board is attached to the upper part of remote c...

Страница 34: ...ending on the amount of dirt or dust in the room SECOND CODE NO is factory set to 01 for filter contam ination light Table 5 When using wireless remote controllers When using wireless remote controlle...

Страница 35: ...etween the unit body and decoration panel 14 TEST OPERATION Refer to the installation manual of the outdoor unit The operation lamp of the remote controller will flash when a malfunction occurs Check...

Страница 36: ...FXFQ12MVJU FXFQ18MVJU FXFQ24MVJU FXFQ30MVJU FXFQ36MVJU Item 1 Decoration Panel BYC125K W1 2 Filter related High efficiency filter 65 KAFP552H80 KAFP552H160 High efficiency filter 90 KAFP553H80 KAFP55...

Страница 37: ...Accessories EDUS39 600 F1_a FXFQ M 36...

Страница 38: ...1645 Wallace Drive Suite 110 Carrollton TX75006 info daikinac com www daikinac com EDUS39 600 F1_a Printed in U S A 08 2009 AMERICAS Aug 2009...

Отзывы: