EDUS39-600-F1_a
Installation
FXFQ-M
33
11-4 COMPUTERIZED CONTROL: FORCED OFF
AND ON/OFF OPERATION
1. Wire specifications and how to perform wiring
• Connect the input from outside to terminals T1 and T2
of the terminal block for remote controller.
2. Actuation
• The following table explains FORCED OFF and ON/
OFF OPERATIONS in response to Input A. The T1-T2
terminals are standard on all Daikin indoor units and
allow for remote starting and stopping of equipment.
Individual indoor units can be field prgrammed at the
remote controller to change the T1-T2 sequence of
operation of the equipment based upon the application.
3. How to select FORCED OFF and ON/OFF OPERATION
• Turn the power on and then use the remote controller to
select operation. These codes are programmed at the
remote controller. Individual unit groups can be pro-
grammed independently.
11-5 CENTRALIZED CONTROL
• For centralized control, it is necessary to designate the
group number. For details, refer to the manual of each
optional controller for centralized control.
11-6 SETTING AIR FILTER SIGN
• Remote controllers are equipped with air-filter signs to dis-
play the time to clean air filters.
• Change the SECOND CODE NO. according to Table 5
depending on the amount of dirt or dust in the room.
SECOND CODE NO. is factory set to [01] for filter contam-
ination-light.
•
.
Table 5
When using wireless remote controllers
• When using wireless remote controllers, address setting is
necessary. Refer to the installation manual attached to the
wireless remote controller for setting instructions.
Wire specification
2-conductor, stranded, non-shielded cop-
per cable / PVC or vinyl jacket
Gauge
AWG 18
Length
Max. 328 ft. (1000 m)
External terminal
Contact that can ensure the minimum
applicable load of 15 V DC, 10 mA.
FORCED OFF (Manual Restart)
Mode No. 12
First Code No. 1
Second Code No. 01
DEFAULT SETTING
ON/OFF OPERATION
Mode No. 12
First Code No. 1
Second Code No. 02
Input A OFF (Open Circuit)
An open circuit between termi-
nals T1 and T2 allows the unit to
run normally.
Input A OFF (Open Circuit)
An open circuit between termi-
nals T1 and T2 prevents unit
operation.
Input A ON (Closed Circuit)
Closing the normally open cir-
cuit between terminals T1 and
T2 stops operation of the unit.
When T1-T2 is opened, the unit
must be restarted with the
remote controller.
.
Input A ON (Closed Circuit)
A closed circuit between termi-
nals T1 and T2 allows normal
operation of the unit.
Setting
Spacing time of
display air
filter sign
(long life type)
Mode
No.
FIRST
CODE
NO.
SECOND
CODE NO.
Air filter
contamination-
light
Approx. 2500 hrs
10
(20)
0
01
Air filter
contamination-
heavy
Approx. 1250 hrs
02
Содержание FXFQ-M
Страница 1: ...EDUS 39 600 F1_a AMERICAS FXFQ M Ceiling Mounted Cassette Type Multi Flow...
Страница 3: ...External Appearance EDUS39 600 F1_a FXFQ M 2 1 External Appearance FXFQ12 36M...
Страница 6: ...EDUS39 600 F1_a Dimensions FXFQ M 5 3 Dimensions FXFQ12MVJU FXFQ18MVJU 3D042631...
Страница 7: ...Dimensions EDUS39 600 F1_a FXFQ M 6 FXFQ24MVJU 3D042632...
Страница 8: ...EDUS39 600 F1_a Dimensions FXFQ M 7 FXFQ30MVJU FXFQ36MVJU 3D042633A...
Страница 10: ...EDUS39 600 F1_a Wiring Diagrams FXFQ M 9 5 Wiring Diagrams FXFQ12M 18M 24M 30M 36MVJU 3D042620B...
Страница 11: ...Electric Characteristics EDUS39 600 F1_a FXFQ M 10 6 Electric Characteristics...
Страница 37: ...Accessories EDUS39 600 F1_a FXFQ M 36...