Daikin FXFN50A2VEB Скачать руководство пользователя страница 7

4 About the system

Installation and operation manual

7

FXFN50~112A2VEB
CO

 Conveni-Pack: indoor unit

3P672850-1A – 2021.07

WARNING

Do NOT let the indoor unit get wet.

Possible consequence: 

Electrical

shock or fire.

About the refrigerant (see 

"7.3 About the refrigerant"

 [

4

 12])

WARNING

▪ Do NOT pierce or burn refrigerant

cycle parts.

▪ Be aware that the refrigerant inside

the system is odourless.

WARNING

The R744 refrigerant (CO

2

) inside the

unit is odourless, non-flammable and
normally does NOT leak.

ALWAYS install a CO

2

 detector

according to the specifications of
standard EN378.

If the refrigerant leaks in high
concentrations in the room, it may have
negative effects on its occupants such
as asphyxiation and carbon dioxide
poisoning. Ventilate the room and
contact the dealer where you
purchased the unit (see 

"7.3.1 About

refrigerant leak detection"

 [

4

 12]).

Do NOT use the unit until a service
person confirms that the part from
which the refrigerant leaked has been
repaired.

Troubleshooting (see 

"8 Troubleshooting"

 [

4

 12])

WARNING

Stop operation and shut OFF the
power if anything unusual occurs
(burning smells etc.).

Leaving the unit running under such
circumstances may cause breakage,
electrical shock or fire. Contact your
dealer.

4

About the system

NOTICE

The appliance shall be stored so as to prevent mechanical
damage.

WARNING

Do  NOT  modify,  disassemble,  remove,  reinstall  or  repair
the unit yourself as incorrect dismantling or installation may
cause an electrical shock or fire. Contact your dealer.

NOTICE

Do  NOT  use  the  system  for  other  purposes.  In  order  to
avoid  any  quality  deterioration,  do  NOT  use  the  unit  for
cooling  precision  instruments,  food,  plants,  animals,  or
works of art.

NOTICE

For future modifications or expansions of your system:

A  full  overview  of  allowable  combinations  (for  future
system  extensions)  is  available  in  technical  engineering
data  and  should  be  consulted.  Contact  your  installer  to
receive more information and professional advice.

CAUTION

If  this  unit  is  equipped  with  an  electrically  powered  safety
measure,  such  as  a  CO

2

  refrigerant  leak  detector  (field

supply),  in  order  to  be  effective,  the  unit  must  be
electrically powered at all times after installation, except for
short service periods.

Содержание FXFN50A2VEB

Страница 1: ...Installation and operation manual CO Conveni Pack indoor unit English Installation and operation manual CO Conveni Pack indoor unit FXFN50A2VEB FXFN71A2VEB FXFN112A2VEB...

Страница 2: ...e utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e standardi t...

Страница 3: ...ring to the indoor unit 20 14 3 To connect appropriate measures for appliances filled with CO 21 15 Commissioning 21 15 1 Checklist before commissioning 21 15 2 To perform a test run 21 16 Configurati...

Страница 4: ...are installed increased pressure may damage the liquid piping Refrigerant piping installation see 13 Piping installation 418 CAUTION Install the refrigerant piping or components in a position where t...

Страница 5: ...sed installer and MUST comply with applicable legislation Units MUST be treated at a specialised treatment facility for reuse recycling and recovery By ensuring this product is disposed of correctly y...

Страница 6: ...erwise condensation on the main unit or refrigerant pipes air filter dirt or drain blockage may cause dripping and objects under the unit may get dirty or damaged WARNING Do NOT place a flammable spra...

Страница 7: ...412 WARNING Stop operation and shut OFF the power if anything unusual occurs burning smells etc Leaving the unit running under such circumstances may cause breakage electrical shock or fire Contact yo...

Страница 8: ...eutral detergent squeeze it well and wipe the panel clean Wipe it with another dry cloth NOTICE NEVER press the button of the user interface with a hard pointed object The user interface may be damage...

Страница 9: ...owing airflow directions can be set Direction Screen Fixed position The indoor unit blows air in 1 of 5 fixed positions Swing The indoor unit alternates between the 5 positions Auto The indoor unit ad...

Страница 10: ...eration panel with benzine thinner chemical dust cloth etc The panel may get discoloured or the coating peeled off If it is heavily dirty soak a cloth in water diluted neutral detergent squeeze it wel...

Страница 11: ...1 2 3 Remove the air filter 1 2 3 4 Clean the suction grille Wash with a soft bristle brush and water or neutral detergent If the suction grille is very dirty use a typical kitchen cleaner leave it on...

Страница 12: ...If necessary replace the indoor unit 4 Refill the refrigerant if needed 5 Perform manual power reset and resume operation NOTICE After the refrigerant leakage is detected the unit will send a signal...

Страница 13: ...void installation in an environment with a lot of organic solvents such as ink and siloxane 12 1 1 Installation site requirements of the indoor unit INFORMATION The sound pressure level is less than 7...

Страница 14: ...nation with a CO2 refrigerant leak detector a safety alarm alone is NOT considered an appropriate measure where occupants are restricted in their movements CO2 refrigerant leak detector WARNING Instal...

Страница 15: ...charge kg in the building divided by total volume of the lowest floor m3 exceed the value for QLMV provide a mechanical ventilation in accordance with EN 378 3 2016 12 2 Mounting the indoor unit 12 2...

Страница 16: ...rlap between the decoration panel and the suspended ceiling Installation guide Use the installation guide to determine the correct vertical position 2 1 2 1 2 1 2 1 A B 1 1 2 C a b c 2 1 2 D A In case...

Страница 17: ...ion 2 Tighten the metal clamp until the screw head is less than 4 mm from the metal clamp part 3 Check for water leaks see To check for water leaks 417 4 Install the insulation piece drain pipe 5 Wind...

Страница 18: ...ld piping is wanted the installer MUST install a pressure relief valve on the following piping Outdoor unit to refrigeration indoor units on liquid piping Outdoor unit to air conditioning indoor units...

Страница 19: ...Turn up the seams of the insulation pieces 2 Attach to the base of the unit 3 Tighten the tie wrap on the insulation pieces 4 Wrap the sealing pad from the base of the unit to the top of the brazed co...

Страница 20: ...block L N earth a b a Circuit breaker b Residual current device 6 Divide the small sealing accessory and wrap it around the cables to prevent water from entering the unit 7 Seal all gaps with a seali...

Страница 21: ...the user NOTICE ALWAYS operate the unit with thermistors and or pressure sensors switches If NOT burning of the compressor might be the result 15 1 Checklist before commissioning After the installati...

Страница 22: ...d with the needs of the user If you want set the airflow direction range to Then 1 M SW C1 C2 Upper 13 23 4 01 Medium 02 Lower 03 Setting Air volume when thermostat control is OFF This setting must co...

Страница 23: ...changed to 08 See 7 3 1 About refrigerant leak detection 412 If the CO2 refrigerant leak detector field supply is Then 1 M SW C1 C2 NOT installed 12 22 1 01 Installed 08 2 or more user interfaces Whe...

Страница 24: ...rcuit board PM Power module PS Switching power supply PTC PTC thermistor Q Insulated gate bipolar transistor IGBT Q C Circuit breaker Q DI KLM Earth leak circuit breaker Q L Overload protector Q M The...

Страница 25: ......

Страница 26: ......

Страница 27: ......

Страница 28: ...3P672850 1A 2021 07 Copyright 2021 Daikin Verantwortung f r Energie und Umwelt...

Отзывы: