2 Specific installer safety instructions

Installation and operation manual

4

FXFN50~112A2VEB

CO

 Conveni-Pack: indoor unit

3P672850-1A – 2021.07

2

Specific installer safety
instructions

Always observe the following safety instructions and regulations.

CAUTION

Do  NOT  insert  fingers,  rods  or  other  objects  into  the  air
inlet or outlet. When the fan is rotating at high speed, it will
cause injury.

General installation requirements

WARNING

Installation  shall  be  done  by  an  installer,  the  choice  of
materials  and  installation  shall  comply  with  the  applicable
legislation. In Europe, EN378 is the applicable standard.

WARNING

▪ Make  sure  to  install  all  necessary  countermeasures  in

case  of  refrigerant  leakage  according  to  standard
EN378  (see 

"12.1.2  Additional  installation  site

requirements for CO

 refrigerant"

 [

4

 14]).

▪ Make  sure  to  install  a  CO

2

  leak  detector  (field  supply)

and  enable  the  function  for  refrigerant  leak  detection
(see 

"16.1 Field setting"

 [

4

 22]).

WARNING

Make  sure  installation,  servicing,  maintenance,  repair  and
applied materials follow the instructions from Daikin and, in
addition,  comply  with  applicable  legislation  and  are
performed  by  qualified  persons  only.  In  Europe  and  areas
where  IEC  standards  apply,  EN/IEC  60335-2-40  is  the
applicable standard.

Installation site (see 

"12.1 Preparing the installation

site"

 [

4

 13])

CAUTION

Appliance NOT accessible to the general public, install it in
a secured area, protected from easy access.

This  unit,  both  indoor  and  outdoor,  is  suitable  for
installation 

in 

commercial 

and 

light 

industrial

environment.

CAUTION

Excessive  concentrations  of  refrigerant  R744  (CO

2

)  in  a

closed  room  can  lead  to  unconsciousness  and  oxygen
deficiency. Take appropriate measures.

See 

"To  determine  the  minimum  number  of  appropriate

measures"

 [

4

 14].

WARNING

In  case  of  mechanical  ventilation,  take  care  the  ventilated
air  is  exhausted  to  the  outdoor  space  and  NOT  into
another closed area.

WARNING

Install  the  unit  ONLY  in  locations  where  the  doors  of  the
occupied space are NOT tight fitting.

WARNING

When  using  safety  shut-off  valves,  make  sure  to  install
measures such as a bypassing piping with a pressure relief
valve (from liquid pipe to gas pipe). When the safety shut-
off  valves  close  and  no  measures  are  installed,  increased
pressure may damage the liquid piping.

Refrigerant piping installation (see 

"13 Piping

installation"

 [

4

 18])

CAUTION

Install  the  refrigerant  piping  or  components  in  a  position
where  they  are  unlikely  to  be  exposed  to  any  substance
which  may  corrode  components  containing  refrigerant,
unless  the  components  are  constructed  of  materials  that
are  inherently  resistant  to  corrosion  or  are  suitably
protected against corrosion.

WARNING

▪ Use  K65  piping  for  high-pressure  applications  with  a

working pressure of 120 bar or 90 bar, depending on its
location in the system.

▪ Use  K65  unions  and  fittings  approved  for  a  working

pressure of 120 bar or 90 bar, depending on its location
in the system.

▪ ONLY  brazing  is  allowed  for  connection  of  pipes.  No

other types of connections are allowed.

▪ Expanding of pipes is NOT allowed.

Electrical installation (see 

"14 Electrical installation"

 [

4

 19])

WARNING

ALWAYS use multicore cable for power supply cables.

WARNING

▪ All  wiring  MUST  be  performed  by  an  authorised

electrician  and  MUST  comply  with  the  applicable
legislation.

▪ Make electrical connections to the fixed wiring.

▪ All  components  procured  on-site  and  all  electrical

construction  MUST  comply  with  the  applicable
legislation.

WARNING

▪ If  the  power  supply  has  a  missing  or  wrong  N-phase,

equipment might break down.

▪ Establish  proper  earthing.  Do  NOT  earth  the  unit  to  a

utility  pipe,  surge  absorber,  or  telephone  earth.
Incomplete earthing may cause electrical shock.

▪ Install the required fuses or circuit breakers.

▪ Secure  the  electrical  wiring  with  cable  ties  so  that  the

cables do NOT come into contact with sharp edges or
piping, particularly on the high-pressure side.

▪ Do  NOT  use  taped  wires,  stranded  conductor  wires,

extension  cords,  or  connections  from  a  star  system.
They can cause overheating, electrical shock or fire.

WARNING

Use  an  all-pole  disconnection  type  breaker  with  at  least
3  mm  between  the  contact  point  gaps  that  provide  full
disconnection under overvoltage category III.

WARNING

If the supply cord is damaged, it MUST be replaced by the
manufacturer,  its  service  agent  or  similarly  qualified
persons in order to avoid a hazard.

Commissioning (see 

"15 Commissioning"

 [

4

 21])

WARNING

If the panels on the indoor units are not installed yet, make
sure  to  power  OFF  the  system  after  finishing  the  test  run.
To  do  so,  turn  OFF  operation  via  the  user  interface.  Do
NOT stop operation by turning OFF the circuit breakers.

Содержание FXFN50A2VEB

Страница 1: ...Installation and operation manual CO Conveni Pack indoor unit English Installation and operation manual CO Conveni Pack indoor unit FXFN50A2VEB FXFN71A2VEB FXFN112A2VEB...

Страница 2: ...e utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e standardi t...

Страница 3: ...ring to the indoor unit 20 14 3 To connect appropriate measures for appliances filled with CO 21 15 Commissioning 21 15 1 Checklist before commissioning 21 15 2 To perform a test run 21 16 Configurati...

Страница 4: ...are installed increased pressure may damage the liquid piping Refrigerant piping installation see 13 Piping installation 418 CAUTION Install the refrigerant piping or components in a position where t...

Страница 5: ...sed installer and MUST comply with applicable legislation Units MUST be treated at a specialised treatment facility for reuse recycling and recovery By ensuring this product is disposed of correctly y...

Страница 6: ...erwise condensation on the main unit or refrigerant pipes air filter dirt or drain blockage may cause dripping and objects under the unit may get dirty or damaged WARNING Do NOT place a flammable spra...

Страница 7: ...412 WARNING Stop operation and shut OFF the power if anything unusual occurs burning smells etc Leaving the unit running under such circumstances may cause breakage electrical shock or fire Contact yo...

Страница 8: ...eutral detergent squeeze it well and wipe the panel clean Wipe it with another dry cloth NOTICE NEVER press the button of the user interface with a hard pointed object The user interface may be damage...

Страница 9: ...owing airflow directions can be set Direction Screen Fixed position The indoor unit blows air in 1 of 5 fixed positions Swing The indoor unit alternates between the 5 positions Auto The indoor unit ad...

Страница 10: ...eration panel with benzine thinner chemical dust cloth etc The panel may get discoloured or the coating peeled off If it is heavily dirty soak a cloth in water diluted neutral detergent squeeze it wel...

Страница 11: ...1 2 3 Remove the air filter 1 2 3 4 Clean the suction grille Wash with a soft bristle brush and water or neutral detergent If the suction grille is very dirty use a typical kitchen cleaner leave it on...

Страница 12: ...If necessary replace the indoor unit 4 Refill the refrigerant if needed 5 Perform manual power reset and resume operation NOTICE After the refrigerant leakage is detected the unit will send a signal...

Страница 13: ...void installation in an environment with a lot of organic solvents such as ink and siloxane 12 1 1 Installation site requirements of the indoor unit INFORMATION The sound pressure level is less than 7...

Страница 14: ...nation with a CO2 refrigerant leak detector a safety alarm alone is NOT considered an appropriate measure where occupants are restricted in their movements CO2 refrigerant leak detector WARNING Instal...

Страница 15: ...charge kg in the building divided by total volume of the lowest floor m3 exceed the value for QLMV provide a mechanical ventilation in accordance with EN 378 3 2016 12 2 Mounting the indoor unit 12 2...

Страница 16: ...rlap between the decoration panel and the suspended ceiling Installation guide Use the installation guide to determine the correct vertical position 2 1 2 1 2 1 2 1 A B 1 1 2 C a b c 2 1 2 D A In case...

Страница 17: ...ion 2 Tighten the metal clamp until the screw head is less than 4 mm from the metal clamp part 3 Check for water leaks see To check for water leaks 417 4 Install the insulation piece drain pipe 5 Wind...

Страница 18: ...ld piping is wanted the installer MUST install a pressure relief valve on the following piping Outdoor unit to refrigeration indoor units on liquid piping Outdoor unit to air conditioning indoor units...

Страница 19: ...Turn up the seams of the insulation pieces 2 Attach to the base of the unit 3 Tighten the tie wrap on the insulation pieces 4 Wrap the sealing pad from the base of the unit to the top of the brazed co...

Страница 20: ...block L N earth a b a Circuit breaker b Residual current device 6 Divide the small sealing accessory and wrap it around the cables to prevent water from entering the unit 7 Seal all gaps with a seali...

Страница 21: ...the user NOTICE ALWAYS operate the unit with thermistors and or pressure sensors switches If NOT burning of the compressor might be the result 15 1 Checklist before commissioning After the installati...

Страница 22: ...d with the needs of the user If you want set the airflow direction range to Then 1 M SW C1 C2 Upper 13 23 4 01 Medium 02 Lower 03 Setting Air volume when thermostat control is OFF This setting must co...

Страница 23: ...changed to 08 See 7 3 1 About refrigerant leak detection 412 If the CO2 refrigerant leak detector field supply is Then 1 M SW C1 C2 NOT installed 12 22 1 01 Installed 08 2 or more user interfaces Whe...

Страница 24: ...rcuit board PM Power module PS Switching power supply PTC PTC thermistor Q Insulated gate bipolar transistor IGBT Q C Circuit breaker Q DI KLM Earth leak circuit breaker Q L Overload protector Q M The...

Страница 25: ......

Страница 26: ......

Страница 27: ......

Страница 28: ...3P672850 1A 2021 07 Copyright 2021 Daikin Verantwortung f r Energie und Umwelt...

Отзывы: