11 About the box

Installation and operation manual

13

FXFN50~112A2VEB
CO

 Conveni-Pack: indoor unit

3P672850-1A – 2021.07

For the installer

11

About the box

11.1

Indoor unit

11.1.1

To remove the accessories from the
indoor unit

a

e

f

d

c

b

h

i

g

j

o

m

n

k

l

a

Paper pattern for installation (top part of packing box)

b

General safety precautions

c

Indoor unit installation and operation manual

d

Installation guide

e

Washers for hanger brackets

f

Screws (to temporarily attach the paper pattern for
installation to the indoor unit)

g

Tie wraps

h

Metal clamp

i

Sealing pads: Large (drain pipe), medium 1 (gas pipe),
medium 2 (liquid pipe), small (electrical wiring)

j

Drain hose

k

Power supply cable

l

Communication cable

m

Insulation piece: Small (liquid pipe)

n

Insulation piece: Large (gas pipe)

o

Insulation piece (drain pipe)

12

Unit installation

WARNING

Installation  shall  be  done  by  an  installer,  the  choice  of
materials  and  installation  shall  comply  with  the  applicable
legislation. In Europe, EN378 is the applicable standard.

WARNING

▪ Make  sure  to  install  all  necessary  countermeasures  in

case  of  refrigerant  leakage  according  to  standard
EN378  (see 

"12.1.2  Additional  installation  site

requirements for CO

 refrigerant"

 [

4

 14]).

▪ Make  sure  to  install  a  CO

2

  leak  detector  (field  supply)

and  enable  the  function  for  refrigerant  leak  detection
(see 

"16.1 Field setting"

 [

4

 22]).

12.1

Preparing the installation site

Avoid  installation  in  an  environment  with  a  lot  of  organic  solvents
such as ink and siloxane.

12.1.1

Installation site requirements of the
indoor unit

INFORMATION

The sound pressure level is less than 70 dBA.

CAUTION

Appliance NOT accessible to the general public, install it in
a secured area, protected from easy access.

This  unit,  both  indoor  and  outdoor,  is  suitable  for
installation 

in 

commercial 

and 

light 

industrial

environment.

NOTICE

This  is  a  class  A  product.  In  a  domestic  environment  this
product  may  cause  radio  interference  in  which  case  the
user may be required to take adequate measures.

Spacing

. Mind the following requirements:

(mm)

≥1500

≥2000

≥4000

≥1500

A

B

C

b

a

d

a

c

A

Minimum distance to the wall (see below)

B

Minimum and maximum distance to the floor (see below)

C

50~71 class:

≥269 mm: In case of installation with standard decoration
panel
≥311 mm: In case of installation with design decoration
panel
≥349 mm: In case of installation with self-cleaning
decoration panel
≥319 mm: In case of installation with standard panel +
fresh air intake kit
≥361 mm: In case of installation with design panel + fresh
air intake kit

112 class:

≥311 mm: In case of installation with standard decoration
panel
≥353 mm: In case of installation with design decoration
panel
≥391 mm: In case of installation with self-cleaning
decoration panel
≥361 mm: In case of installation with standard panel +
fresh air intake kit
≥403 mm: In case of installation with design panel + fresh
air intake kit

a

Indoor unit

b

Lighting (the figure shows ceiling-mounted lighting, but
recessed lighting is also allowed)

c

Air fan

d

Static volume (example: table)

Содержание FXFN50A2VEB

Страница 1: ...Installation and operation manual CO Conveni Pack indoor unit English Installation and operation manual CO Conveni Pack indoor unit FXFN50A2VEB FXFN71A2VEB FXFN112A2VEB...

Страница 2: ...e utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e standardi t...

Страница 3: ...ring to the indoor unit 20 14 3 To connect appropriate measures for appliances filled with CO 21 15 Commissioning 21 15 1 Checklist before commissioning 21 15 2 To perform a test run 21 16 Configurati...

Страница 4: ...are installed increased pressure may damage the liquid piping Refrigerant piping installation see 13 Piping installation 418 CAUTION Install the refrigerant piping or components in a position where t...

Страница 5: ...sed installer and MUST comply with applicable legislation Units MUST be treated at a specialised treatment facility for reuse recycling and recovery By ensuring this product is disposed of correctly y...

Страница 6: ...erwise condensation on the main unit or refrigerant pipes air filter dirt or drain blockage may cause dripping and objects under the unit may get dirty or damaged WARNING Do NOT place a flammable spra...

Страница 7: ...412 WARNING Stop operation and shut OFF the power if anything unusual occurs burning smells etc Leaving the unit running under such circumstances may cause breakage electrical shock or fire Contact yo...

Страница 8: ...eutral detergent squeeze it well and wipe the panel clean Wipe it with another dry cloth NOTICE NEVER press the button of the user interface with a hard pointed object The user interface may be damage...

Страница 9: ...owing airflow directions can be set Direction Screen Fixed position The indoor unit blows air in 1 of 5 fixed positions Swing The indoor unit alternates between the 5 positions Auto The indoor unit ad...

Страница 10: ...eration panel with benzine thinner chemical dust cloth etc The panel may get discoloured or the coating peeled off If it is heavily dirty soak a cloth in water diluted neutral detergent squeeze it wel...

Страница 11: ...1 2 3 Remove the air filter 1 2 3 4 Clean the suction grille Wash with a soft bristle brush and water or neutral detergent If the suction grille is very dirty use a typical kitchen cleaner leave it on...

Страница 12: ...If necessary replace the indoor unit 4 Refill the refrigerant if needed 5 Perform manual power reset and resume operation NOTICE After the refrigerant leakage is detected the unit will send a signal...

Страница 13: ...void installation in an environment with a lot of organic solvents such as ink and siloxane 12 1 1 Installation site requirements of the indoor unit INFORMATION The sound pressure level is less than 7...

Страница 14: ...nation with a CO2 refrigerant leak detector a safety alarm alone is NOT considered an appropriate measure where occupants are restricted in their movements CO2 refrigerant leak detector WARNING Instal...

Страница 15: ...charge kg in the building divided by total volume of the lowest floor m3 exceed the value for QLMV provide a mechanical ventilation in accordance with EN 378 3 2016 12 2 Mounting the indoor unit 12 2...

Страница 16: ...rlap between the decoration panel and the suspended ceiling Installation guide Use the installation guide to determine the correct vertical position 2 1 2 1 2 1 2 1 A B 1 1 2 C a b c 2 1 2 D A In case...

Страница 17: ...ion 2 Tighten the metal clamp until the screw head is less than 4 mm from the metal clamp part 3 Check for water leaks see To check for water leaks 417 4 Install the insulation piece drain pipe 5 Wind...

Страница 18: ...ld piping is wanted the installer MUST install a pressure relief valve on the following piping Outdoor unit to refrigeration indoor units on liquid piping Outdoor unit to air conditioning indoor units...

Страница 19: ...Turn up the seams of the insulation pieces 2 Attach to the base of the unit 3 Tighten the tie wrap on the insulation pieces 4 Wrap the sealing pad from the base of the unit to the top of the brazed co...

Страница 20: ...block L N earth a b a Circuit breaker b Residual current device 6 Divide the small sealing accessory and wrap it around the cables to prevent water from entering the unit 7 Seal all gaps with a seali...

Страница 21: ...the user NOTICE ALWAYS operate the unit with thermistors and or pressure sensors switches If NOT burning of the compressor might be the result 15 1 Checklist before commissioning After the installati...

Страница 22: ...d with the needs of the user If you want set the airflow direction range to Then 1 M SW C1 C2 Upper 13 23 4 01 Medium 02 Lower 03 Setting Air volume when thermostat control is OFF This setting must co...

Страница 23: ...changed to 08 See 7 3 1 About refrigerant leak detection 412 If the CO2 refrigerant leak detector field supply is Then 1 M SW C1 C2 NOT installed 12 22 1 01 Installed 08 2 or more user interfaces Whe...

Страница 24: ...rcuit board PM Power module PS Switching power supply PTC PTC thermistor Q Insulated gate bipolar transistor IGBT Q C Circuit breaker Q DI KLM Earth leak circuit breaker Q L Overload protector Q M The...

Страница 25: ......

Страница 26: ......

Страница 27: ......

Страница 28: ...3P672850 1A 2021 07 Copyright 2021 Daikin Verantwortung f r Energie und Umwelt...

Отзывы: