16 Configuration
Installation and operation manual
20
FXFA20~125A2VEB
VRV system air conditioner
3P599604-1C – 2020.10
▪ For all-round airflow, use the table below.
If the distance to the floor is (m)
Then
(1)
M
SW
—
≤2.7
13 (23)
0
01
2.7<x≤3.0
02
3.0<x≤3.5
03
Setting: Decoration panel type
When installing or changing the decoration panel type, ALWAYS
check if the correct values are set.
If the … decoration panel is used
Then
(1)
M
SW
—
Standard or self-cleaning
13 (23)
15
01
Design
02
Setting: Airflow direction range
This setting must correspond with the needs of the user.
If you want set the airflow direction
range to…
Then
(1)
M
SW
—
Upper
13 (23)
4
01
Medium
02
Lower
03
Setting: Air volume when thermostat control is OFF
This setting must correspond with the needs of the user. It
determines the fan speed of the indoor unit during thermostat OFF
condition.
1
If you have set the fan to operate, set the air volume speed:
If you want…
Then
(1)
M
SW
—
During thermostat
OFF at cooling
operation
LL
(2)
12 (22)
6
01
Setup volume
(2)
02
OFF
(a)
03
Monitoring 1
(2)
04
Monitoring 2
(2)
05
Monitoring 3
(2)
06
H
(2)
07
During thermostat
OFF at heating
operation
LL
(2)
12 (22)
3
01
Setup volume
(2)
02
OFF
(a)
03
Monitoring 1
(2)
04
Monitoring 2
(2)
05
Monitoring 3
(2)
06
H
(2)
07
(a)
Only use in combination with optional remote sensor or when
setting
M
10 (20),
SW
2, —
3 is used.
Setting: Time to clean air filter
This setting must correspond with the air contamination in the room.
It determines the interval at which
"Time to clean filter"
notification
is displayed on the user interface.
If you want an interval of…
(air contamination)
Then
(1)
M
SW
—
±2500 h (light)
10 (20)
0
01
±1250 h (heavy)
02
Notification ON
3
01
Notification OFF
02
Setting: Thermostat sensor selection
This setting must correspond with how/if the remote controller
thermostat sensor is used.
When the remote controller thermostat
sensor is…
Then
(1)
M
SW
—
Used in combination with indoor unit
thermistor
10 (20)
2
01
Not used (indoor unit thermistor only)
02
Used exclusively
03
Setting: Thermostat differential changeover (if remote sensor is
used)
If the system contains a remote sensor, set the increase/decrease
increments.
If you want to change increments to…
Then
(1)
M
SW
—
1°C
12 (22)
2
01
0.5°C
02
Setting: Differential for automatic changeover
Set temperature difference between cooling setpoint and heating
setpoint in automatic mode (availability depends on the system
type). Differential is cooling setpoint minus heating setpoint.
(1)
Field settings are defined as follows:
•
M
: Mode number –
First number
: for group of units –
Number between brackets
: for individual unit
•
SW
: Setting number
• —: Value number
•
: Default
(2)
Fan speed:
•
LL
: Low fan speed (set during thermostat OFF)
•
L
: Low fan speed (set by the user interface)
•
H:
High fan speed
•
Setup volume
: The fan speed corresponds to the speed the user has set (low, medium, high) using the fan speed button on the user
interface.
•
Monitoring 1, 2, 3
: The fan is OFF, but runs for a short time every 6 minutes to detect the room temperature by
LL
(Monitoring 1), by
L
(Monitoring 2) or by
H
(Monitoring 3).