background image

12 Unit installation

Installation and operation manual

14

FXFA20~125A2VEB

VRV system air conditioner

3P599604-1C – 2020.10

A

Minimum distance to the wall (see below)

B

Minimum and maximum distance to the floor (see below)

C

20~63 class:

224 mm:

 In case of installation with standard decoration

panel

266 mm:

 In case of installation with design decoration

panel

304 mm:

 In case of installation with self-cleaning

decoration panel

274 mm:

 In case of installation with fresh air intake kit

80~100 class:

266 mm:

 In case of installation with standard decoration

panel

308 mm:

 In case of installation with design decoration

panel

346 mm:

 In case of installation with self-cleaning

decoration panel

316 mm:

 In case of installation with fresh air intake kit

125 class:

308 mm:

 In case of installation with standard decoration

panel

350 mm:

 In case of installation with design decoration

panel

388 mm:

 In case of installation with self-cleaning

decoration panel

358 mm:

 In case of installation with fresh air intake kit

a

Indoor unit

b

Lighting (the figure shows ceiling-mounted lighting, but
recessed lighting is also allowed)

c

Air fan

d

Static volume (example: table)

A:  Minimum  distance  to  the  wall

.  Depends  on  the  air  flow

directions towards the wall.

≥1500

≥500

≥200

a

A

A

A

b

c

a

Air outlet and corners open

b

Air outlet closed, corners open (optional blocking pad kit
required)

c

Air outlet and corners closed (optional blocking pad kit
required)

B: Minimum and maximum distance to the floor

:

▪ Minimum: 2.7 m to avoid accidental touching.

▪ Maximum: Depends on the air flow directions and the capacity

class.  Also  make  sure  the  "Ceiling  height"  field  setting
corresponds  with  the  actual  situation.  See 

"16.1  Field

setting" 

[

4

 19].

If air flow direction…

Then B

FXFA20~100

FXFA125

All-round

≤3.5 m

≤4.2 m

4-way

(a)

≤4.0 m

≤4.5 m

3-way

(a)

≤3.5 m

≤4.2 m

(a)

Optional blocking kit required

INFORMATION

Some options may require additional service space. Refer
to  the  installation  manual  of  the  used  option  before
installation.

Minimum floor area requirements

CAUTION

The  total  refrigerant  charge  in  the  system  cannot  exceed
the  requirements  for  minimum  floor  area  of  the  smallest
room that is served. For minimum floor area requirements
for  indoor  units,  see  the  installation  and  operation  manual
of the outdoor unit.

12.2

Mounting the indoor unit

12.2.1

Guidelines when installing the indoor unit

INFORMATION

Optional  equipment.

  When  installing  optional  equipment,

also read the installation manual of the optional equipment.
Depending  on  the  field  conditions,  it  might  be  easier  to
install the optional equipment first.

Decoration  panel

.  Install  the  decoration  panel  always 

after

installing the unit.

NOTICE

After installing the decoration panel:

▪ Make  sure  there  is  no  gap  between  the  unit  body  and

the  decoration  panel. 

Possible  consequence: 

Air

might leak and cause dew drop.

▪ Make  sure  no  oil  remains  on  the  plastic  parts  of  the

decoration 

panel. 

Possible 

consequence:

Degradation and damage of plastic parts.

Ceiling  strength

.  Check  whether  the  ceiling  is  strong  enough  to

support the weight of the unit. If there is a risk, reinforce the ceiling
before installing the unit.

▪ For existing ceilings, use anchors.

▪ For  new  ceilings,  use  sunken  inserts,  sunken  anchors  or  other

field supplied parts.

A

c

b

d
e

a

A

50~100 mm

: In case of installation with standard panel

100~150 mm

: In case of installation with fresh air intake

kit or design panel

130~180 mm

: In case of installation with self-cleaning

decoration panel

a

Ceiling slab

b

Anchor

c

Long nut or turnbuckle

d

Suspension bolt

e

Suspended ceiling

Suspension bolts.

 Use M8~M10 suspension bolts for installation.

Attach  the  hanger  bracket  to  the  suspension  bolt.  Fix  it  securely
using  a  nut  and  washer  from  the  upper  and  lower  sides  of  the
hanger bracket.

(mm)

780

710

a1

b

b

a2

c

a1

Nut (field supply)

a2

Double nut (field supply)

b

Washer (accessories)

c

Hanger bracket (attached to the unit)

Paper  pattern  for  installation 

(upper  part  of  the  packing).  Use

the paper pattern to determine the correct horizontal positioning. It
contains  the  necessary  dimensions  and  centers.  You  can  attach
the paper pattern to the unit.

Содержание FXFA100A2VEB

Страница 1: ...eration manual VRV system air conditioner English Installation and operation manual VRV system air conditioner FXFA20A2VEB FXFA25A2VEB FXFA32A2VEB FXFA40A2VEB FXFA50A2VEB FXFA63A2VEB FXFA80A2VEB FXFA100A2VEB FXFA125A2VEB ...

Страница 2: ... fie utilizate în conformitate cu instrucţiunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z našimi navodili on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно н...

Страница 3: ... wiring components 18 14 2 To connect the electrical wiring to the indoor unit 18 15 Commissioning 19 15 1 Checklist before commissioning 19 15 2 To perform a test run 19 16 Configuration 19 16 1 Field setting 19 17 Technical data 21 17 1 Wiring diagram 21 17 1 1 Unified wiring diagram legend 21 1 About the documentation 1 1 About this document Target audience Authorised installers end users INFOR...

Страница 4: ...per earthing Do NOT earth the unit to a utility pipe surge absorber or telephone earth Incomplete earthing may cause electrical shock Install the required fuses or circuit breakers Secure the electrical wiring with cable ties so that the cables do NOT come in contact with sharp edges or piping particularly on the high pressure side Do NOT use taped wires stranded conductor wires extension cords or...

Страница 5: ...on piping Protection devices piping and fittings shall be protected as far as possible against adverse environmental effects Provision shall be made for expansion and contraction of long runs of piping Piping in refrigerating systems shall be designed and installed such as to minimise the likelihood of hydraulic shock damaging the system The indoor equipment and pipes shall be securely mounted and...

Страница 6: ...bol means that the battery contains a heavy metal above a certain concentration Possible chemical symbols are Pb lead 0 004 Waste batteries must be treated at a specialized treatment facility for reuse By ensuring waste batteries are disposed of correctly you will help to prevent potential negative consequences for the environment and human health 3 2 Instructions for safe operation WARNING Do NOT...

Страница 7: ...ting any maintenance task CAUTION Do NOT insert fingers rods or other objects into the air inlet or outlet When the fan is rotating at high speed it will cause injury WARNING NEVER replace a fuse with a fuse of a wrong ampere ratings or other wires when a fuse blows out Use of wire or copper wire may cause the unit to break down or cause a fire CAUTION After a long use check the unit stand and fit...

Страница 8: ...he unit yourself as incorrect dismantling or installation may cause an electric shock or fire Contact your dealer In case of accidental refrigerant leaks make sure there are no naked flames The refrigerant itself is entirely safe non toxic and mildly flammable but it will generate toxic gas when it accidentally leaks into a room where combustible air from fan heaters gas cookers etc is present Alw...

Страница 9: ...ooling Heating and Auto operation modes Setback A function that keeps the room temperature in a specific range when the system is turned off by the user the schedule function or the OFF timer 6 2 1 Basic operation modes The indoor unit can operate in various operation modes Icon Operation mode Cooling In this mode cooling will be activated as required by the setpoint or by Setback operation Heatin...

Страница 10: ...fan is rotating at high speed it will cause injury NOTICE NEVER inspect or service the unit by yourself Ask a qualified service person to perform this work However as end user you may clean the air filter suction grille air outlet and outside panels WARNING NEVER replace a fuse with a fuse of a wrong ampere ratings or other wires when a fuse blows out Use of wire or copper wire may cause the unit ...

Страница 11: ...er interface 7 2 2 To clean the suction grille NOTICE Do NOT use water of 50 C or higher Possible consequence Discoloration and deformation 1 Open the suction grille Standard panel 1 Design panel 1 1 2 2 2 Remove the suction grille Standard panel 45 1 2 Design panel 1 2 3 Remove the air filter 1 2 3 4 Clean the suction grille Wash with a soft bristle brush and water or neutral detergent If the suc...

Страница 12: ...time Authorized person only MUST replace the sensor NOTICE Functionality of the safety measures are periodically automatically checked In case of malfunction error code will display on the user interface NOTICE The R32 refrigerant leakage sensor is a semiconductor detector which may incorrectly detect substances other than R32 refrigerant Avoid using chemical substances e g organic solvents hair s...

Страница 13: ...ntling of the system treatment of the refrigerant oil and other parts MUST comply with applicable legislation Units MUST be treated at a specialised treatment facility for reuse recycling and recovery For the installer 11 About the box 11 1 Indoor unit 11 1 1 To remove the accessories from the indoor unit 1 1 1 8 4 1 1 1 a 4 1 1 7 e f d c b h i m g j k l a Paper pattern for installation upper part...

Страница 14: ...tion before installation Minimum floor area requirements CAUTION The total refrigerant charge in the system cannot exceed the requirements for minimum floor area of the smallest room that is served For minimum floor area requirements for indoor units see the installation and operation manual of the outdoor unit 12 2 Mounting the indoor unit 12 2 1 Guidelines when installing the indoor unit INFORMA...

Страница 15: ...ine the correct vertical position 2 1 2 1 2 1 2 1 A B 1 1 2 C a b c 2 1 2 D A In case of installation with standard decoration panel B In case of installation with fresh air intake kit C In case of installation with self cleaning decoration panel D In case of installation with design decoration panel a Suspended ceiling b Installation guide accessory c Unit Level Make sure the unit is level at all...

Страница 16: ...is less than 4 mm from the metal clamp part 3 Check for water leaks see To check for water leaks 416 4 Install the insulation piece drain pipe 5 Wind the large sealing pad insulation around the metal clamp and drain hose and fix it with tie wraps 6 Connect the drain piping to the drain hose 4 mm A A A A A A f 6 5 2 c e 4 b a d b a d c 3 1 2 6 1 a Drain pipe connection attached to the unit b Drain ...

Страница 17: ...rial Phosphoric acid deoxidised seamless copper Flare connections Only use annealed material Piping temper grade and thickness Outer diameter Ø Temper grade Thickness t a 6 4 mm 1 4 Annealed O 0 8 mm t Ø 9 5 mm 3 8 12 7 mm 1 2 15 9 mm 5 8 a Depending on the applicable legislation and the maximum working pressure of the unit see PS High on the unit name plate larger piping thickness might be requir...

Страница 18: ...current device Must comply with applicable legislation a MCA Minimum circuit ampacity Stated values are maximum values see electrical data of indoor unit for exact values 14 2 To connect the electrical wiring to the indoor unit NOTICE Follow the wiring diagram delivered with the unit located at the inside of the service cover For instructions on how to connect the optional equipment see the instal...

Страница 19: ...e system is properly earthed and the earth terminals are tightened The fuses or locally installed protection devices are installed according to this document and have NOT been bypassed The power supply voltage matches the voltage on the identification label of the unit There are NO loose connections or damaged electrical components in the switch box There are NO damaged components or squeezed pipe...

Страница 20: ...tion in the room It determines the interval at which Time to clean filter notification is displayed on the user interface If you want an interval of air contamination Then 1 M SW 2500 h light 10 20 0 01 1250 h heavy 02 Notification ON 3 01 Notification OFF 02 Setting Thermostat sensor selection This setting must correspond with how if the remote controller thermostat sensor is used When the remote...

Страница 21: ... earth Connection Protective earth screw Connector A Rectifier Earth Relay connector Field wiring Short circuit connector Fuse Terminal INDOOR Indoor unit Terminal strip Symbol Meaning Symbol Meaning OUTDOOR Outdoor unit Wire clamp Residual current device Symbol Colour Symbol Colour BLK Black ORG Orange BLU Blue PNK Pink BRN Brown PRP PPL Purple GRN Green RED Red GRY Grey WHT White YLW Yellow Symb...

Страница 22: ...G Refrigerant leak detector S NPH Pressure sensor high S NPL Pressure sensor low S PH HPS Pressure switch high S PL Pressure switch low S T Thermostat S RH Humidity sensor S W SW Operation switch SA F1S Surge arrester SR WLU Signal receiver SS Selector switch SHEET METAL Terminal strip fixed plate T R Transformer TC TRC Transmitter V R V Varistor V R Diode bridge Insulated gate bipolar transistor ...

Страница 23: ......

Страница 24: ...3P599604 1C 2020 10 Copyright 2020 Daikin Verantwortung für Energie und Umwelt ...

Отзывы: