• Indoor Unit • Small concealed ceiling unit • FXDQ-M9
1
2
• VRV Systems • Indoor Unit
4
2
Specifications
Notes
(1) Cooling: indoor temp. 27ºCDB, 19ºCWB; outdoor temp. 35ºCDB; equivalent piping length: 8m; level difference: 0m
(2) Heating: indoor temp. 20ºCDB; outdoor temp. 7ºCDB, 6ºCWB; equivalent refrigerant piping: 8m; level difference: 0m
(3) Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
(4) Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
(5) Maximum allowable voltage range variation between phases is 2%.
(6) MCA/MFA: MCA = 1.25 x FLA
(7) MFA \< 4 x FLA
(8) Next lower standard fuse rating minimum 16A
(9) Select wire size based on the value of MCA
(10) Instead of a fuse, use a circuit breaker
Voltage range
Min.
%
-10
Max.
%
10
Current - 50Hz
Zmax
List
No requirements
Minimum circuit amps (MCA)
A
0.2
Maximum fuse amps (MFA)
A
16
Full load amps
(FLA)
Total
A
0.1
2-2 Electrical Specifications
FXDQ20M9
FXDQ25M9