• Indoor Unit • 2-way blow ceiling mounted cassette • FXCQ-A
1
2
• VRV Systems • Indoor Unit
4
2
Specifications
Standard Accessories : Declaration of conformity;
Standard Accessories : Installation manual;
Standard Accessories : Operation manual;
Notes
(1) Cooling: indoor temp. 27ºCDB, 19ºCWB; outdoor temp. 35ºCDB; equivalent piping length: 7.5m (horizontal)
(2) Heating: indoor temp. 20ºCDB; outdoor temp. 7ºCDB, 6ºCWB; equivalent refrigerant piping: 7.5m (horizontal)
(3) Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
(4) Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
(5) Maximum allowable voltage range variation between phases is 2%.
(6) MCA/MFA: MCA = 1.25 x FLA
(7) MFA
≤
4 x FLA
(8) Next lower standard fuse rating minimum 16A
(9) Select wire size based on the value of MCA
(10) Instead of a fuse, use a circuit breaker
2-2 Electrical Specifications
FXCQ20A
FXCQ25A
FXCQ32A
FXCQ40A
FXCQ50A
FXCQ63A
FXCQ80A
FXCQ125A
Power supply
Name
VE
Phase
1~
Frequency
Hz
50
Voltage
V
220-240
Voltage range
Min.
%
-10
Max.
%
10
Current - 50Hz
Minimum circuit amps (MCA)
A
0.3
0.4
0.5
0.6
1.1
Maximum fuse amps (MFA)
A
16
Full load amps
(FLA)
Total
A
0.2
0.3
0.4
0.5
0.9