3
1
6
• VRV Systems • Indoor Unit
11
• Indoor Unit • 2-way blow ceiling mounted cassette • FXCQ-A
6
Capacity tables
6 - 3 Capacity Correction Factor
Indoor air
temperature
14.0 °CWB
16.0 °CWB
18.0 °CWB
19.0 °CWB
20.0 °CWB
22.0 °CWB
24.0 °CWB
20.0 °CDB
23.0 °CDB
26.0 °CDB
27.0 °CDB
28.0 °CDB
30.0 °CDB
32.0 °CDB
FXCQ20
TC
0.536
0.552
0.578
0.612
0.641
0.691
0.732
SHF
1.172
1.273
1.294
1.233
1.187
1.125
1.086
FXCQ25
TC
0.546
0.559
0.570
0.603
0.637
0.690
0.730
SHF
1.147
1.250
1.306
1.245
1.192
1.127
1.089
FXCQ32
TC
0.546
0.559
0.570
0.603
0.637
0.690
0.730
SHF
1.147
1.250
1.306
1.245
1.192
1.127
1.089
FXCQ40
TC
0.540
0.548
0.571
0.611
0.645
0.697
0.744
SHF
1.167
1.273
1.300
1.231
1.182
1.122
1.080
FXCQ50
TC
0.534
0.543
0.578
0.619
0.651
0.707
0.755
SHF
1.177
1.282
1.287
1.221
1.176
1.117
1.074
FXCQ63
TC
0.546
0.562
0.571
0.604
0.633
0.688
0.727
SHF
1.144
1.245
1.307
1.246
1.198
1.129
1.091
FXCQ80
TC
0.538
0.547
0.576
0.617
0.650
0.706
0.753
SHF
1.166
1.270
1.289
1.223
1.177
1.117
1.076
FXCQ125
TC
0.549
0.561
0.579
0.617
0.651
0.708
0.751
SHF
1.132
1.228
1.280
1.218
1.171
1.113
1.084
FXCQ-A
3D079901
Capacity correction factor Te = 11°C
Содержание FXCQ-A
Страница 1: ...Air Conditioning Technical Data 2 way blow ceiling mounted cassette EEDEN13 204 FXCQ A...
Страница 2: ......