Control Devices
EDUS391000-C
48
Controls
2.6
DST301BA61 Schedule Timer
Enables you to connect and control weekly schedule for up to 128 indoor units all together.
2.6.1
System Configuration and Electric Wiring
With a schedule timer, you can set on/off time twice a day by units of 1 week for up to 128 indoor units.
System Configuration
If using the schedule timer alone, you do not have to set the centralized control group No. for group control.
Transmission Wiring
<Indoor Unit Wiring>
1. If using the schedule timer alone:
For the schedule timer’s power supply, connect the schedule timer (D1, D2) with the connector (X18A) on the indoor
unit PC board by crimped style terminal with the attached electric wire.
2. If using in combination with other optional controllers for centralized control:
Transmission wiring for control: AWG 18 or 16 sheathed vinyl cord or cable (2 wire) ..... Max. 3280 ft (Total Max. 6560 ft)
<Transmission Wiring Connection Example>
1 series wiring, 2 bus wiring, and 3 star wiring are the same as with the central remote controller.
Simultaneous control of up to 128 indoor units is managed by a
week schedule.
The start and stop time for twice a day can be set for the week in
increments of 1 minute.
By combining with a central remote controller and schedule timer,
you can construct a system that matches the size and use of the
building.
If used together with a central remote controller, you can set up to 8
schedule patterns which can be distributed among zones as desired
using the central remote controller.
Is equipped with a compensation function for power failure up to 48
hours.
Features thin design of a mere 5/8" in thickness. (Uses JIS
recessed box for 2.)
Applicable wiring methods include bus and star in addition to
crossover type.
Can be used in combination with other D-BACS equipment.
Содержание FXAQ-MVJU
Страница 1: ...EDUS 391000 C AMERICAS AMERICAS Controls ...
Страница 9: ...Control Devices EDUS391000 C 8 Controls Other Features ...
Страница 63: ...Control Devices EDUS391000 C 62 Controls 2 7 7 Electric Wiring Connection ground wire to ground terminal ...
Страница 64: ...EDUS391000 C Control Devices Controls 63 ...
Страница 65: ...Control Devices EDUS391000 C 64 Controls ...
Страница 66: ...EDUS391000 C Control Devices Controls 65 1P167242A ...
Страница 70: ...EDUS391000 C Adapter Controls 69 C 3K019189B ...
Страница 74: ...EDUS391000 C Adapter Controls 73 3 3 DTA109A51 DIII NET Expander Adapter 1P013360 ...
Страница 75: ...Adapter EDUS391000 C 74 Controls 1P013360 ...
Страница 76: ...EDUS391000 C Adapter Controls 75 1P013360 ...
Страница 77: ...Adapter EDUS391000 C 76 Controls 3 4 KRP1C74 75 Wiring Adapter C 2P263038A ...
Страница 78: ...EDUS391000 C Adapter Controls 77 C 2P263038A ...
Страница 79: ...Adapter EDUS391000 C 78 Controls C 2P263038A KRP1C74 Compact multi flow ...
Страница 82: ...EDUS391000 C Adapter Controls 81 ...
Страница 83: ...Adapter EDUS391000 C 82 Controls ...
Страница 84: ...EDUS391000 C Adapter Controls 83 C 1P161221 ...
Страница 89: ...Adapter EDUS391000 C 88 Controls ...