Installation and operation manual
2
FWEC1
Standard electronic controller
FC66002763
■
use keys
to change the value
■
Press
to save the new value setting or
to cancel
the modi
fi
cation
■
After completing the modification of the parameters
concerned press key
to exit the procedure
NB
The parameter con
fi
guration phase is of limited duration.
Once a certain time has elapsed (around 2 minutes) the
thermostat will switch back into the Off status and only the
saved changes will be retained.
AVAILABLE CONFIGURATIONS (PARAMETER P
00
)
The LCD controller can be configured in various ways
according to the type of system. Various con
fi
gurations can
be obtained through the
P00
parameter (see con
fi
guration
procedure of controller parameters).
001
■
System pipes:
2
■
Valve:
NO
■
Heating element:
NO
■
Fan speed:
3
■
Summer/winter switching logic:
LOCAL MANUAL
002
■
System pipes:
2
■
Valve:
NO
■
Heating element:
NO
■
Fan speed:
3
■
Summer/winter switching logic:
REMOTE MANUAL
003
■
System pipes:
2
■
Valve:
NO
■
Heating element:
NO
■
Fan speed: 3
■
Summer/winter switching logic:
AUTOMATIC WATER SIDE
004
■
System pipes:
2
■
Valve:
NO
■
Heating element:
NO
■
Fan speed:
4
■
Summer/winter switching logic:
LOCAL MANUAL
005
■
System pipes:
2
■
Valve:
NO
■
Heating element:
NO
■
Fan speed:
4
■
Summer/winter switching logic:
REMOTE MANUAL
006
■
System pipes:
2
■
Valve:
NO
■
Heating element:
NO
■
Fan speed:
4
■
Summer/winter switching logic:
AUTOMATIC WATER SIDE
■
P04
= water sensor:
-
000
: not available
-
001
: available
Based on the set value, the sensor alarm and the heating
element functions will be controlled
■
P05
= use logic – Digital input 1 for Cooling/Heating
switching:
-
000
: (open/closed) = (Cooling/Heating)
-
001
: (open/closed) = (Heating/Cooling)
■
P06
= use logic – Digital input 2 for On/Off switching:
-
000
: (open/closed) = (On/Off)
-
001
: (open/closed) = (Off/On)
PARAMETER CONFIGURATION PROCEDURE
■
Switch the thermostat off
■
Push the keys at the same time
■
Use keys
to modify the display value up to the
password value
10
, and press
.
If it is correct, you will have access to the parameters
■
Use keys
to scroll the various parameters (see
“Parameter list” described above)
■
Press
to con
fi
rm the parameter change (the value
will start
fl
ashing).
level indication:
001
= password
entry
Value of selected
parameter
Selected
parameter
P...
level indication:
003
= password entry
level indication:
1= password entry
Содержание FWEC1
Страница 2: ...1 3 2 1 2 3 ...
Страница 3: ...6 4 5 ...
Страница 4: ...NOTES ...
Страница 105: ...NOTES ...
Страница 106: ...FC66002487 FC66002491 1 2 ...
Страница 107: ...FWL M V FWL M V FWD FWB EPIMSB6 FC66002493 UT66000879 3 4 ...
Страница 108: ...EPIB6 UT66000880 UT66000881 5 6 ...
Страница 109: ...UT66000882 EPIB6 UT66000883 7 8 ...
Страница 110: ...UT66000884 EPIB6 UT66000885 9 10 ...
Страница 111: ...UT66000886 11 NOTES ...
Страница 112: ...Zandvoordestraat 300 B 8400 Oostende Belgium FC66002763 ...