Troubleshooting
SiUS091601E
81
Service Diagnosis
4.9
Outdoor Unit PCB Abnormality
Error Code
E1
Method of Error
Detection
The system checks if the microprocessor is working in order.
The system checks if the zero-cross signal comes in properly.
Error Decision
Conditions
The microprocessor program runs out of control.
The zero-cross signal is not detected.
Supposed
Causes
Defective outdoor unit PCB
Noise
Momentary drop of voltage
Momentary power failure
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Continuously ON or OFF
Blink
YES
(R21201)
NO
Replace the outdoor unit
PCB (main PCB).
Ground the system.
Zero-cross signal
abnormality.
Replace the outdoor unit
PCB (main PCB).
Check if the outdoor unit is
grounded.
Is LED A blinking?
Grounded?
Turn on the power again.
∗
Before you check the LED A,
cancel the standby electricity
saving function by starting fan
operation with the remote
controller.
∗
Wait at least for 7 sec. after
turning on the power.
Содержание FVXS09NVJU
Страница 12: ...SiUS091601E 1 List of Functions Part 1 List of Functions 1 Functions 2 ...
Страница 15: ...SiUS091601E Specifications 4 Part 2 Specifications 1 Specifications 5 ...
Страница 65: ...SiUS091601E Remote Controller 54 Part 5 Remote Controller 1 FTX Series 55 2 FVXS Series 57 ...
Страница 121: ...SiUS091601E Check Service Diagnosis 110 12 class 15 class Multimeter R23024 R20701 1 2 3 4 Multimeter ...
Страница 144: ...Revision History Month Year Version Revised contents 02 2016 SiUS091601E First edition ...