31
English
•
Hook the strap (b) for preventing the suction grille from falling.
(Refer to Fig. 49-
(3)
)
10. FIELD SETTING
CAUTION
Before carrying out field setting, check the items mentioned in the clause 2 “
1. Items to be checked after the
installation work is completed
” on page 4.
•
Check if all the installation and piping works for the air conditioners are completed.
•
Check if the control box lids of the air conditioner are closed.
〈〈
After turn on the power supply, carry out field setting from the remote controller according to the
installation state.
〉〉
•
Carry out setting at 3 places, “Mode No.”, “FIRST CODE No.” and “SECOND CODE No.”.
The settings shown by “
” in the table indicate those when shipped from the factory.
•
The method of setting procedure and operation is shown in the installation manual attached to the remote
controller.
(Note)Though setting of “Mode No.” is carried out as a group, if you intend to carry out individual setting by
each indoor unit or confirmation after setting, carry out setting with the Mode No. shown in the paren-
thesis ( ).
•
Do not carry out setting other than those shown in the table.
10-1 SETTING OF CEILING HEIGHT
•
Set the SECOND CODE No. according to the ceiling height as shown in the Table 4.
Table 4
10-2 SETTING FILTER SIGN
•
A message to inform the air filter cleaning time will be indicated on the remote controller.
•
Set the SECOND CODE No. shown in the Table 5 according to the amount of dust or pollution in the room.
Setting
Ceiling height (m)
Mode No.
FIRST
CODE No.
SECOND
CODE No.
FUQ71CVEB
FUQ100 · 125CVEB
Standard
2.7 or less
3.2 or less
13 (23)
0
01
High ceiling 1
2.7 - 3.0
3.2 - 3.6
02
High ceiling 2
3.0 - 3.5
3.6 - 4.0
03
Fig. 49
(1)
(2)
(2)
(3)
(3)
Hook the strap
Strap (b) for preventing
the suction grille from falling
Strap (a) for preventing
the suction grille from falling
(3 places)
(1 place)
Corner cover
(Piping section)
Hook the strap on the nearer one