SiBE01-829
Check
Service Diagnosis
69
5.3
Outdoor Unit Fan System Check
Check No.09
5.4
Hall IC Check
Check No.16
1. Check the connector connection.
2. With the power ON, operation OFF, and the connector connected, check the following.
∗
Output voltage of about 5 V between pins 1 and 3.
∗
Generation of 3 pulses between pins 2 and 3 when the fan motor is operating.
Failure of (1)
Æ
faulty PCB
Æ
Replace the PCB.
Failure of (2)
Æ
faulty Hall IC
Æ
Replace the fan motor.
Both (1) and (2) result
Æ
Replace the PCB.
Check the
fan motor lead wire
connector for secure
connection.
Abnormal
YES
NO
YES
Continuity
Are the
resistance at connector
leads
∞
? 1. red - black,
2. white - black
Check the fan
capacitor for continuity.
Does the outdoor
fan rotate?
Does
the outdoor unit fan
start just after the power
is turned on?
Check the outdoor fan system.
YES
NO
NO
Normal
No continuity
Repair.
Replace the fan motor.
Replace the fan motor.
Replace the fan motor.
The outdoor fan system is
normal.
(R8502)
Содержание FTYN25GXV1B
Страница 1: ...SiBE01 829 Applied Models Non Inverter Pair Heat Pump SPLIT Pair Wall Mounted Type G Series...
Страница 11: ...Introduction SiBE01 829 x...
Страница 12: ...SiBE01 829 List of Function 1 Part 1 List of Function 1 Functions 2...
Страница 15: ...Functions SiBE01 829 4 List of Function...
Страница 16: ...SiBE01 829 Specifications 5 Part 2 Specifications 1 Specifications 6...
Страница 19: ...Specifications SiBE01 829 8 Specifications...
Страница 23: ...Printed Circuit Board Connector Wiring Diagram SiBE01 829 12 Printed Circuit Board Connector Wiring Diagram...
Страница 81: ...Check SiBE01 829 70 Service Diagnosis...
Страница 86: ...Others SiBE01 829 108 Others...
Страница 92: ...Wiring Diagrams SiBE01 829 114 Appendix...
Страница 96: ...SiBE01 829 iv Drawings Flow Charts...