Troubleshooting
SiBE01-829
64
Service Diagnosis
4.7
Hardware Error (Tact Switch Pin Short)
Remote
Controller
Display
UA
Method of
Malfunction
Detection
The supply power is detected for its requirement (different from pair type and multi type) by the
indoor / outdoor transmission signal.
Malfunction
Decision
Conditions
The pair type and multi type are interconnected.
Supposed
Causes
Wrong models interconnected
Wrong indoor unit PCB mounted
Indoor unit PCB defective
Wrong outdoor unit PCB mounted or defective
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Check the indoor and outdoor unit
model numbers.
(R7342)
YES
NO
NO
YES
Check the code numbers
(2P01234, for example) of the
indoor and outdoor unit PCB with
the Parts List.
Match the compatible
models.
Replace the indoor unit
PCB (1) (or the outdoor unit
PCB).
Change for the specified
PCB (1) or (2).
Matched compatibly?
Indoor unit and
outdoor unit matched?
Содержание FTYN25GXV1B
Страница 1: ...SiBE01 829 Applied Models Non Inverter Pair Heat Pump SPLIT Pair Wall Mounted Type G Series...
Страница 11: ...Introduction SiBE01 829 x...
Страница 12: ...SiBE01 829 List of Function 1 Part 1 List of Function 1 Functions 2...
Страница 15: ...Functions SiBE01 829 4 List of Function...
Страница 16: ...SiBE01 829 Specifications 5 Part 2 Specifications 1 Specifications 6...
Страница 19: ...Specifications SiBE01 829 8 Specifications...
Страница 23: ...Printed Circuit Board Connector Wiring Diagram SiBE01 829 12 Printed Circuit Board Connector Wiring Diagram...
Страница 81: ...Check SiBE01 829 70 Service Diagnosis...
Страница 86: ...Others SiBE01 829 108 Others...
Страница 92: ...Wiring Diagrams SiBE01 829 114 Appendix...
Страница 96: ...SiBE01 829 iv Drawings Flow Charts...